Plan Review Details - Permit 17071224
Plan Review Stops For Permit 17071224
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-21 Cont ID  
Sent By jpearson Date 2017-08-21 Time 07:37 Rev Time 0.00
Received By jpearson Date 2017-08-21 Time 07:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-08-02 Cont ID  
Sent By jpearson Date 2017-08-02 Time 07:19 Rev Time 0.00
Received By jpearson Date 2017-08-02 Time 07:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-08-21 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-17 Time 12:52 Sent To  
Notes
2017-08-18 12:52:18RESUB ROUTED TO JPEARSON'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-15 Time   Rev Time 0.00
Received By cpuell Date 2017-08-11 Time 17:25 Sent To  
Notes
2017-08-14 17:26:08CCOLES DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-08-09 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-31 Time 15:33 Sent To  
Notes
2017-08-01 15:34:06B14

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-08-21 Cont ID  
Sent By ccole Date 2017-08-21 Time 11:06 Rev Time 0.00
Received By ccole Date 2017-08-21 Time 08:10 Sent To  
Notes
2017-08-21 10:07:20MECHANICAL PROVISO:
  
 SEPARATE PERMITS ARE REQUIRED FOR THE ROTARY OVEN
 EXHAUST, AND THE WALK-IN COOLER AND FREEZER.
  
 CCOLE- 8/21/17

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-15 Cont ID  
Sent By ccole Date 2017-08-15 Time 12:17 Rev Time 0.00
Received By ccole Date 2017-08-15 Time 11:48 Sent To  
Notes
2017-08-15 12:23:421ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17071224
 8/15/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.1: THE BUILDING PRESSURIZATION TABLE IS
 INCORRECTLY INDICATING NEUTRAL PRESSURE, HOWEVER IT
 SHOULD READ -200. PLEASE CORRECT AND PROVIDE THE MAKE
 UP AIR FOR THE ROTARY OVEN IN THE CALCULATION TABLE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-09 Cont ID  
Sent By ccole Date 2017-08-09 Time 09:12 Rev Time 0.00
Received By ccole Date 2017-08-09 Time 09:05 Sent To  
Notes
2017-08-09 09:19:041ST REVIEW FBC-2014 MECHANICAL
 REVISION PERMIT #17071224
 8/9/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW 2.5 TON AC SYSTEM- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 2) REVISE THE ENERGY COMPLIANCE FORM TO INCLUDE THE NEW
 AC SYSTEM.
  
 3) SHEET M0.1: PLEASE PROVIDE THE BUILDING
 PRESSURIZATION AND KITCHEN EXHAUST TABLES THAT ARE
 MISSING FROM THE REVISED PLAN SHEET.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-08-03 Cont ID  
Sent By gjohnson Date 2017-08-03 Time 14:22 Rev Time 0.00
Received By gjohnson Date 2017-08-03 Time 11:43 Sent To  
Notes
***NONE***