Plan Review Details - Permit 17071132
Plan Review Stops For Permit 17071132
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-08-17 Cont ID  
Sent By thunt Date 2017-08-17 Time 15:12 Rev Time 0.00
Received By thunt Date 2017-08-14 Time 13:55 Sent To  
Notes
2017-08-15 13:55:47GIVEN TO TLARGE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-09 Cont ID  
Sent By tklarge Date 2017-08-09 Time 14:50 Rev Time 0.00
Received By tklarge Date 2017-08-03 Time 15:30 Sent To  
Notes
2017-08-04 15:31:03RESUB ROUTED TO PLUMB <5K

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-01 Cont ID  
Sent By tklarge Date 2017-08-01 Time 10:50 Rev Time 0.00
Received By tklarge Date 2017-07-27 Time 09:55 Sent To  
Notes
2017-07-31 09:56:39REVISION ROUTED TO TKLARGE

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-09-06 Cont ID  
Sent By thunt Date 2017-08-17 Time 15:09 Rev Time 0.00
Received By thunt Date 2017-08-17 Time 15:01 Sent To  
Notes
2017-08-17 15:12:379/6/17 ACCEPT EMAIL FROM KAMM CONSULTING PROVIDING DOCS
 FOR USEAGE OF AAV
  
 AAV'S ARE PROHIBITED FOR USE IN TANKS OF ANY TYPE (FPC
 918.8) AND NOT PER SCHIER INSTALLATION SPECIFICATIONS.
 SHOW HOW YOU INTEND ON VENTING THE SYSTEM TO COMPLY.
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6696
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-08-09 Cont ID  
Sent By tklarge Date 2017-08-09 Time 14:49 Rev Time 0.00
Received By tklarge Date 2017-08-09 Time 14:32 Sent To  
Notes
2017-08-09 14:43:441) PROVIDE A NARRATIVE AS TO HOW THE SIZING
 CALCULATIONS FOR THE GREASE INTERCEPTOR WERE DONE. I DO
 NOT UNDERSTAND HOW YOU ARRIVED AT THESE NUMBERS AND
 CANNOT CONFIRM COMPLIANCE WITH THE PLUMBING CODE .
 CLARIFY.
 2) THE MINIMUM SLOPE ON A 2 INCH PIPE IS 1/4 INCH PER
 FOOT PER 2014 FPC TABLE 704.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-01 Cont ID  
Sent By tklarge Date 2017-08-01 Time 10:50 Rev Time 0.00
Received By tklarge Date 2017-08-01 Time 09:58 Sent To  
Notes
2017-08-01 10:01:381) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE GREASE TRAP. 2014 FBC-PLUMBING
 SEC.1003.2.
 2) SUBMIT SIZING CALCULATIONS FOR THE GREASE TRAP. THE
 TRAP MAY BE SIZED USING STANDARD PDI G101. 2014
 FBC-PLUMBING SEC.1003.3.4.
 3) THE INLET & OUTLET OF THE GREASE TRAP SHALL BE
 INDIRECTLY WASTED PER 2014 FBC- PLUMBING SEC. 802.1.8.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  