Plan Review Details - Permit 17071125
Plan Review Stops For Permit 17071125
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-02-06 Cont ID  
Sent By rmcdouga Date 2018-02-06 Time 17:35 Rev Time 0.00
Received By rmcdouga Date 2018-02-06 Time 17:35 Sent To E
Notes
2018-02-06 17:40:07BRADLEY J. COOPER ACKNOWLEDGED SIGNING AND SEALING
 THESE PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-02-05 Cont ID  
Sent By rmcdouga Date 2018-02-05 Time 17:14 Rev Time 0.00
Received By rmcdouga Date 2018-02-05 Time 17:14 Sent To  
Notes
2018-02-05 17:19:52PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE POOL PLANS ARE REQUIRED TO HAVE THE FLORIDA
 ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE,
 COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC
 61G15 - 23.002 THE HANDWRITTEN SIGNATURE THAT IS ON THE
 PLANS THAT WERE SUBMITTED DO NOT MATCH THE ONE THAT WAS
 PROVIDED BY BRADLEY J. CASH. WE NOW HAVE THREE SETS OF
 PLANS WITH THREE DIFFERENT SIGNATURES AND NONE OF THEM
 MATCH THE ONE THAT WAS PROVIDED BY MR. CASH.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-01-18 Cont ID  
Sent By rmcdouga Date 2018-01-18 Time 16:47 Rev Time 0.00
Received By rmcdouga Date 2018-01-16 Time 07:10 Sent To  
Notes
2018-01-18 17:05:54PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SIGNATURE OF THE ENGINEER ON THE PLANS DOES NOT
 APPEAR TO BE BRADLEY COOPER'S. THE REVIEW WILL REMAIN
 IN A FAILED STATUS UNTIL BRADLEY COOPER PROVIDES HIS
 SIGNATURE FOR COMPARISION. THE POOL PLANS ARE REQUIRED
 TO HAVE THE FLORIDA ENGINEER'S SEAL AND ORIGINAL
 HANDWRITTEN SIGNATURE, COPIES OR OTHER FACSIMILES ARE
 NOT ACCEPTABLE. FAC 61G15 - 23.002
  
 NOTE: THE SIGNATURE ON THE PLANS DO NOT MATCH THE
 SIGNATURE THAT WAS PROVIDED BY BRADLEY COOPER. SUBMIT
 PLANS WITH BRADLEY COOPER'S ORIGINAL SIGNATURE THAT WE
 NOW HAVE ON FILE. FAC 61G15-23..2
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-12-15 Cont ID  
Sent By rmcdouga Date 2017-12-15 Time 17:09 Rev Time 0.00
Received By rmcdouga Date 2017-12-15 Time 16:41 Sent To P
Notes
2017-12-15 17:08:25PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE POOL PLANS ARE REQUIRED TO HAVE THE FLORIDA
 ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE,
 COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC
 61G15 - 23.002
  
 2) THE STATE OF FLORIDA CERTIFICATE OF AUTHORIZATION
 FOR BROWARD ENGINEERING ASSOCIATES, INC. (2651) IS
 DELINQUENT.
  
 3) PLEASE REVISE GENERAL STRUCTURAL NOTE 1 ON SHEET 7
 TO ACI 318 - 11. WHEN IT WAS CORRECTED THE NUMBER OF
 THE ACI STANDARD (318) WAS LEFT OUT. FBC CHAPTER 35
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-17 Cont ID  
Sent By rmcdouga Date 2017-10-17 Time 09:04 Rev Time 0.00
Received By rmcdouga Date 2017-10-17 Time 06:31 Sent To  
Notes
2017-10-17 07:46:21PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE POOL PLANS ARE REQUIRED TO HAVE THE FLORIDA
 ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE,
 COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC
 61G15 - 23.002
  
 2) ON SHEET 7 THE EDITIONS OF NFPA 70 AND FBC THAT ARE
 SPECIFIED ARE NOT CORRECT. PLEASE REVISE TO THE 2011
 NFPA 70 AND THE 2014 FBC. FBC CHAPTER 35.
  
 3) PLEASE REVISE GENERAL STRUCTURAL NOTE 1 ON SHEET 7
 TO ACI 318 - 11. FBC CHAPTER 35
  
 4) ADDRESS THE PLUMBING REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-02-07 Cont ID  
Sent By jleahy Date 2018-02-07 Time 09:09 Rev Time 0.00
Received By jleahy Date 2018-02-07 Time 09:09 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-09-20 Cont ID  
Sent By jleahy Date 2017-09-20 Time 09:55 Rev Time 0.00
Received By jleahy Date 2017-09-20 Time 09:55 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2017-12-04 Cont ID  
Sent By mgonzale Date 2017-12-04 Time 11:30 Rev Time 0.00
Received By mgonzale Date   Time   Sent To  
Notes
2017-12-04 11:31:38PASSED WITH PROVISOS: SWIMMING POOL DISCHARGE MAY
 CONNECT TO CITY OF WEST PALM BEACH SEWER. SEE BELOW FOR
 CONDITIONS.
  
 SWIMMING POOL DISCHARGES
 BACKGROUND:
 SWIMMING POOL DISCHARGES CAN BE A SOURCE OF ILLICIT
 DISCHARGES IN MUNICIPAL SEPARATE STORM SEWER SYSTEMS
 (MS4). CHLORINE AND OTHER CHEMICALS USED IN MAINTAINING
 POOLS AND SPAS, WHICH OFTEN INCLUDE ACIDIC OR ALKALINE
 CLEANING COMPOUNDS, CAN HAVE A NEGATIVE IMPACT ON THE
 PLANT AND AQUATIC LIFE IN SURFACE WATERS. EVEN AT LOW
 LEVELS, CHLORINE CAN BE TOXIC TO AQUATIC LIFE.
 SUBSECTION 62-302.530(19), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.) LIMITS THE DISCHARGE OF CHLORINE TO SURFACE
 WATER BODIES TO < 0.01 MILLIGRAM PER LITER (MG/L). IN
 ADDITION, TURBIDITY ASSOCIATED WITH BACKWASHING AND
 CLEANING CAN ALSO VIOLATE SURFACE WATER QUALITY
 STANDARDS.
 EXISTING REGULATIONS:
 THE FLORIDA DEPARTMENT OF HEALTH REGULATES PUBLIC
 SWIMMING POOLS AND BATHING PLACES. SUBSECTION 64E-9.007
 (15) ?POOL WASTE WATER DISPOSAL? STATES IN PART: ?POOL
 WASTE WATER SHALL BE DISCHARGED THROUGH AN AIR GAP;
 DISPOSAL SHALL BE TO SANITARY SEWERS, STORM SEWERS,
 DRAINFIELDS, OR BY OTHER MEANS, IN ACCORDANCE WITH
 LOCAL MUNICIPAL AND BUILDING OFFICIAL REQUIREMENTS
 INCLUDING OBTAINING ALL NECESSARY PERMITS.?
 OTHER STATES INCLUDING MICHIGAN, PENNSYLVANIA, MARYLAND
 AND NEW JERSEY, REQUIRE PUBLIC SWIMMING POOLS TO OBTAIN
 A GENERAL NATIONAL POLLUTANT DISCHARGE ELIMINATION
 SYSTEM (NPDES) PERMIT TO DISCHARGE WASTEWATER FROM
 PUBLIC SWIMMING POOLS. THERE IS NO SUCH REQUIREMENT IN
 THE FLORIDA. DECHLORINATED SWIMMING POOL DISCHARGES ARE
 AUTHORIZED IN FLORIDA IN ACCORDANCE WITH
 62-624.200(2)(Q), F.A.C.; PROVIDED THAT THEY DO NOT
 CAUSE A VIOLATION OF WATER QUALITY STANDARDS.
 GUIDANCE:
 TO HELP PROTECT FLORIDA?S ENVIRONMENT, THE FOLLOWING
 BEST MANAGEMENT PRACTICES SHOULD BE FOLLOWED WHEN
 DRAINING SWIMMING POOLS OR DISCHARGING FILTER BACKWASH
 INTO THE ENVIRONMENT.
 ONLY DRAIN YOUR POOL WHEN NECESSARY. AVOID
 DRAINING/BACKWASHING YOUR POOL DURING PERIODS OF
 DROUGHT AND DURING SIGNIFICANT RAINFALL EVENTS. DO NOT
 DRAIN YOUR POOL WHEN WATERING RESTRICTIONS ARE IN
 PLACE.
 BEFORE DRAINING YOUR POOL, ALLOW THE WATER TO STAND FOR
 AT LEAST 48 HOURS AFTER THE LAST ADDITION OF CHLORINE
 OR UNTIL THE FREE CHLORINE RESIDUAL IS < 0.01 MG/L. (IF
 YOU NEED TO DRAIN YOUR POOL QUICKLY, YOU CAN PURCHASE
 CHLORINE-NEUTRALIZING CHEMICALS SUCH AS SODIUM
 THIOSULFATE AT YOUR LOCAL POOL SUPPLY COMPANY.)
 TEST THE FREE CHLORINE RESIDUAL BEFORE DISCHARGING. A
 FREE CHLORINE RESIDUAL SHOULD NOT BE DETECTED. THE
 CHLORINE RESIDUAL CAN BE TESTED USING A STANDARD POOL
 TEST KIT. (REFER TO 64E-9.004 (11), F.A.C. FOR
 ADDITIONAL INFORMATION.)
 THE WATER SHOULD BE CLEAR AND FREE OF SOLIDS.
 THE PH MUST BE BETWEEN 6.5 AND 8.5 BEFORE IT IS
 DISCHARGED.
 ALGAECIDES CONTAINING COPPER OR SILVER CAN INTERRUPT
 NORMAL ALGAL AND PLANT GROWTH IN SURFACE WATER BODIES
 AND SHOULD BE USED WITH CAUTION. FOLLOW THE
 MANUFACTURER?S INSTRUCTIONS BEFORE DISCHARGING WATER
 THAT HAS HAD AN ALGAECIDE ADDED RECENTLY.
 CONTROL THE RATE OF DISCHARGE ACROSS YOUR PROPERTY TO
 AVOID EROSION AND NUISANCE CONDITIONS FOR NEIGHBORING
 PROPERTIES. NUISANCE CONDITIONS SUCH AS THE CREATION OF
 ODORS, MOSQUITO BREEDING CONDITIONS, OR FLOODING CAN
 OCCUR WHEN WATER IS PONDED FOR A PROLONGED PERIOD.
 DIRECT THE DISCHARGE OVER A VEGETATED SURFACE SO THAT
 SOME LEVEL OF FILTRATION CAN OCCUR.
 DO NOT DISCHARGE ON AREAS RECENTLY TREATED WITH
 HERBICIDES OR PESTICIDES.
  
 DISPOSAL TO SANITARY SEWER SYSTEMS:
 POOL AND SPA WASTEWATER SHOULD NOT BE DISCHARGED INTO
 THE SANITARY SEWER SYSTEM WITHOUT THE PERMISSION OF THE
 WASTEWATER TREATMENT FACILITY.
 AVOID DISCHARGING TO THE SANITARY SEWER SYSTEM DURING
 OR IMMEDIATELY AFTER A SIGNIFICANT RAINFALL EVENT.
  
 THIS DOCUMENT WAS DEVELOPED IN PART USING INFORMATION
 OBTAINED FROM THE FOLLOWING SOURCES. IT SHOULD NOT BE
 CONSIDERED COMPREHENSIVE AS OTHER LOCAL PERMITTING
 REQUIREMENTS MAY APPLY.
 ENVIRONMENTAL TIMES. ?FROM THE POOL TO THE LAGOON. POOL
 OWNERS CAN PROTECT THE LAKE WORTH LAGOON.? REPRINTED
 FROM THE ?LAKE WORTH LAGOON UPDATE.? SPRING 2004.
 MARYLAND DEPARTMENT OF ENVIRONMENTAL PROTECTION. ?FACT
 SHEET FOR GENERAL NO. 01SI DISCHARGES FROM SWIMMING
 POOL AND SPAS?
 MARYLAND DEPARTMENT OF ENVIRONMENTAL PROTECTION. ?JUST
 THE FACTS ABOUT??SWIMMING POOL & SPA GUIDELINES
  
  
 MANNY GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2017-09-18 Cont ID  
Sent By tklarge Date 2017-09-18 Time 07:46 Rev Time 0.00
Received By tklarge Date 2017-09-18 Time 07:19 Sent To  
Notes
2017-09-18 07:46:53THERE IS NO GAS ASSOCIATED WITH THIS POOL.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-02-09 Cont ID  
Sent By tklarge Date 2018-02-09 Time 06:37 Rev Time 0.00
Received By tklarge Date 2018-02-01 Time 10:36 Sent To  
Notes
2018-02-02 10:36:12RESUB ROUTED TO RMCDOUGAL PER SHILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-01-18 Cont ID  
Sent By rmcdouga Date 2018-01-18 Time 17:06 Rev Time 0.00
Received By rmcdouga Date 2018-01-08 Time 09:34 Sent To  
Notes
2018-01-18 17:07:48PLANS ARE AT MY DESK PENDING AUTHENTICATION OF THE
 ENGINEER'S SIGNATURE.
2018-01-10 09:35:00RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-27 Cont ID  
Sent By tklarge Date 2017-12-27 Time 08:06 Rev Time 0.00
Received By tklarge Date 2017-12-06 Time 13:30 Sent To  
Notes
2017-12-07 13:30:29RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-17 Cont ID  
Sent By rmcdouga Date 2017-10-17 Time 09:04 Rev Time 0.00
Received By rmcdouga Date 2017-07-27 Time 14:21 Sent To  
Notes
2017-07-28 14:21:32ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-02-09 Cont ID  
Sent By tklarge Date 2018-02-09 Time 06:36 Rev Time 0.00
Received By tklarge Date 2018-02-08 Time 06:39 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-01-16 Cont ID  
Sent By tklarge Date 2018-01-16 Time 05:14 Rev Time 0.00
Received By tklarge Date 2018-01-16 Time 03:03 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-12-27 Cont ID  
Sent By tklarge Date 2017-12-27 Time 08:05 Rev Time 0.00
Received By tklarge Date 2017-12-27 Time 05:59 Sent To  
Notes
2017-12-27 06:21:541) SUBMIT DOCUMENTATION FROM THE PALM BEACH COUNTY
 HEALTH DEPARTMENT THAT AN APPLICATION FOR AN OPERATING
 PERMIT HAS BEEN SUBMITTED TO THE HEALTH DEPARTMENT FOR
 THIS SWIMMING POOL. FL. STATUTE 514.03 (1).
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL
 HEAT PUMPS. THE HEAT PUMPS SHALL COMPLY WITH THE 2014
 FBC - ENERGY SEC.C404.7.1 AND TABLE C404.2.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN GRATES. THE MAXIMUM VELOCITY OF THE WATER PASSING
 THROUGH THE OPENINGS SHALL NOT EXCEED 1 1/2 FEET PER
 SECOND AT 100 PERCENT OF THE DESIGN RECIRCULATION
 FLOW.. 2014 FBC SEC.454.1.6.5.10.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-09-18 Cont ID  
Sent By tklarge Date 2017-09-18 Time 07:18 Rev Time 0.00
Received By tklarge Date 2017-09-14 Time 06:28 Sent To  
Notes
2017-09-14 14:23:191) SUBMIT DOCUMENTATION FROM THE PALM BEACH COUNTY
 HEALTH DEPARTMENT THAT AN APPLICATION FOR AN OPERATING
 PERMIT HAS BEEN SUBMITTED TO THE HEALTH DEPARTMENT FOR
 THIS SWIMMING POOL. FL. STATUTE 514.03 (1).
 2) THE FILTRATION SYSTEM SHALL BE CAPABLE OF MEETING
 ALL OTHER REQUIREMENTS OF 2014 FBC-BUILDING, CHAPTER
 454 WHILE ALSO PROVIDING A FLOW RATE OF AT LEAST 3/4
 GPM FOR EACH LIVING UNIT AT NONTRANSIENTFACILITIES.
 2014 FBC-BUILDING SEC.454.1.1.1.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL
 HEAT PUMPS. THE HEAT PUMPS SHALL COMPLY WITH THE 2014
 FBC - ENERGY SEC.C404.7.1 AND TABLE C404.2.
 4) THE FLOOR INLETS SHALL NOT EXCEED 10 FEET FROM
 ADJACENT POOL WALLS AND SHALL NOT EXCEED 20 FEET
 BETWEEN ADJACENT FLOOR INLETS. 2014 FBC-BUILDING
 SEC.454.1.6.5.9.4.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN GRATES. THE MAXIMUM VELOCITY OF THE WATER PASSING
 THROUGH THE OPENINGS SHALL NOT EXCEED 1 1/2 FEET PER
 SECOND AT 100 PERCENT OF THE DESIGN RECIRCULATION
 FLOW.. 2014 FBC SEC.454.1.6.5.10.2.
 6) THE FLOW RATE THROUGH EACH FLOOR INLET SHALL NOT
 EXCEED 20 GPM. 2014 FBC SEC.454.1.6.5.9.6.
 7) SHT. 7 OF 7 - PIPING NOTES - #6 READS THAT THE POOL
 WATER SHALL DISCHARGE TO THE SANITARY SYSTEM. POOL
 WATER IS NOT PERMITTED TO DISCHARGE TO THE CITY'S
 SANITARY OR STORM PER CITY CODE OF ORDINANCES ART.III,
 SEC. 90-126 (SANITARY) AND ART.V, SEC.90-203
 (STORMWATER). PLEASE CONTACT MANNY GONZALEZ WITH THE
 CITY OF WEST PALM BEACH ENGINEERING DEPT.AT
 561-494-1085.
 8) A MINIMUM OF A DOUBLE CHECK VALVE BACKFLOW PREVENTER
 SHALL BE INSTALLED ON THE POTABLE WATER SUPPLY FOR THE
 POOL PER THE CITY OF WPB CROSS CONNECTION MANUAL.
 9) ALL CHEMICALS SHALL BE FED INTO THE RETURN LINE
 AFTER THE PUMP, HEATER AND FILTERS PER 2014 FBC SEC.
 454.1.6.5.16.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2017-08-24 Time   Rev Time 0.00
Received By kmartin Date 2017-08-24 Time 13:14 Sent To B
Notes
***NONE***