Plan Review Details - Permit 17071087
Plan Review Stops For Permit 17071087
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-01-05 Cont ID  
Sent By shill Date 2018-01-05 Time 12:12 Rev Time 0.00
Received By shill Date 2018-01-05 Time 07:16 Sent To I
Notes
2018-01-05 12:13:27****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 4. DETAIL 1-S1.0 SPECS SELF DRILLING SCREWS PER
 MANUFACTURER REQUIREMENTS. DETAIL 2-M2 ALSO REFERS TO
 MANUFACTURER INSTRUCTIONS. FBC B 1609, REVISE DETAILS
 TO SPECIFY FASTENING INCLUDING DIAMETER, LENGTH,
 FASTENING PATTERN. IF THIS WILL BE DELEGATED
 ENGINEERING PER FLORIDA ADMINISTRATIVE CODE 61G15-30,
 PROVIDE THE DELEGATED ENGINEERING (UNIT FASTENING TO
 CURB, ANY OTHER ) AT THIS TIME. STRUCTURAL ENGINEER OF
 RECORD (SEOR) TO REVIEW DELEGATED ENGINEERING PRIOR TO
 SUBMITTAL.
  
 DETAIL WAS NOT REVISED BUT A NEW NOTE REFERS TO THIS AS
 "DELEGATED ENGINEERING". SUBJECT TO INSPECTOR'S
 DISCRETION, A REVISION MAY BE REQUIRED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-02 Cont ID  
Sent By shill Date 2017-08-02 Time 16:07 Rev Time 0.00
Received By shill Date 2017-08-02 Time 16:07 Sent To  
Notes
2017-08-02 16:07:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FS489, CLARIFY SCOPE OF WORK FOR WADMAN FABRICATORS.
 I WAS UNABLE TO FIND A LICENSE NUMBER FOR THIS COMPANY
 ON DBPR WEBSITE. WILL THIS WORK BE DONE ON SITE OR OFF
 SITE?
  
 2. S1.0, FBC B TABLE 1607.1(26), ALL ROOF SURFACES
 SUBJECT TO MAINTENANCE WORKERS TO BE DESIGNED TO A 300#
 LIVE LOAD, 20# SPECIFIED, CLARIFY OR REVISE.
  
 3. THIS APPEARS TO BE LOCATED IN EXPOSURE C, SEE FBC
 1609.4, SEE ALSO ASCE7-10 AND COMMENTARY. THE LARGE
 OPEN SPACE (PARKING LOT) CREATES A PATCH CONDITION IN
 THAT DIRECTION, THE AREA TO THE NORTH AND AREA TO THE
 NORTHWEST ARE OPEN; REVISE PLAN (AND DESIGN, IF
 NECESSARY) TO EXPOSURE C OR EMAIL RATIONALE FOR
 EXPOSURE B VIA EMAIL PRIOR TO RESUBMITTAL.
  
 4. DETAIL 1-S1.0 SPECS SELF DRILLING SCREWS PER
 MANUFACTURER REQUIREMENTS. DETAIL 2-M2 ALSO REFERS TO
 MANUFACTURER INSTRUCTIONS. FBC B 1609, REVISE DETAILS
 TO SPECIFY FASTENING INCLUDING DIAMETER, LENGTH,
 FASTENING PATTERN. IF THIS WILL BE DELEGATED
 ENGINEERING PER FLORIDA ADMINISTRATIVE CODE 61G15-30,
 PROVIDE THE DELEGATED ENGINEERING (UNIT FASTENING TO
 CURB, ANY OTHER ) AT THIS TIME. STRUCTURAL ENGINEER OF
 RECORD (SEOR) TO REVIEW DELEGATED ENGINEERING PRIOR TO
 SUBMITTAL.
  
 OTHER STRUCTURAL SPECS ARE ALSO TOO GENERAL TO SHOW
 COMPLIANCE WITH FBC B 1609, RESISTANCE TO WIND LOADS.
 FOR INSTANCE, 1-M2 REFERS TO "HOLD DOWN BRACKETS".
  
 5. SOME PAGES ARE NOT SIGNED AND SEALED IN ACCORDANCE
 WITH FLORIDA STATUTE 471. PRIOR TO RESUBMITTAL, VERIFY
 THAT ALL PAGES INCLUDE AN ORIGINAL "WET" SIGNATURE. FOR
 INSTANCE, SEE STRUCTURAL PAGES (NOT ORIGINAL SIGNATURE,
 WAS DIGITALLY SIGNED AND SEALED). CHECK ALL PAGES PRIOR
 TO RESUBMITTAL.
  
 6. TITLE BLOCK FOR DONALD C. CARROLL, PE IS NOT CLEAR.
 SEE FS471, FAC61G15-23.002. REVISE S1.0 TO INCLUDE OR
 CLARIFY.
  
 7. SEE FLORIDA STATUTE 471.0195; THE DBPR WEBSITE
 (MYFLORIDALICENSE.COM) DOES NOT REFLECT THAT THE
 FOLLOWING HAVE TAKEN THE ADVANCED FLORIDA BUILDING CODE
 COURSE. PLEASE SEND EVIDENCE THAT THE COURSE WAS
 COMPLETED TO FBPE AND REQUEST THAT THEY UPDATE THE
 WEBSITE. THIS COURSE IS DUE WITHIN ONE YEAR AFTER THE
 ADOPTION OF THE FBC (WAS DUE JUNE 30, 2016).
  
 JASON M. SCATES, PE
 RICKY N TERRELL, PE
 RANDALL C. HAASE, PE
  
 THIS WILL NOT DELAY PERMIT ISSUANCE.
  
 8. FBC 109, VALUE TO INCLUDE LABOR, MATERIALS,
 OVERHEAD, PROFIT, INCLUDING ITEMS PROVIDED BY OTHERS.
 PLAN NOTES THAT SOME ITEMS WILL BE PROVIDED BY WALMART;
 VERIFY THAT THE VALUE OF THOSE ITEMS ARE INCLUDED IN
 PERMIT VALUE.
  
 9. SHEETS S1.1 THROUGH S4.0 ARE BLANK; PLEASE REMOVE,
 FBC 107.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-12-28 Cont ID  
Sent By jpearson Date 2017-12-28 Time 08:57 Rev Time 0.00
Received By jpearson Date 2017-12-28 Time 08:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-01 Cont ID  
Sent By jpearson Date 2017-08-01 Time 10:04 Rev Time 0.00
Received By jpearson Date 2017-08-01 Time 10:04 Sent To  
Notes
2017-08-01 10:04:41CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL SPECS FOR ALL NEW EQUIPMENT TO BE
 INSTALLED INCLUDING MINIMUM CIRCUIT AMPACITY
 REQUIREMENTS AND MAXIMUM OVERCURRENT PROTECTION
 REQUIRED PER MANUFACTURER. NEC 110.3; FBC 107.2.1
 2. PROVIDE VOLTAGE DROP CALCULATIONS FOR EACH BRANCH
 CIRCUIT TO ANY NEW EQUIPMENT INSTALLED. ALTHOUGH NOT
 SUPPLIED WITH THE AMPACITY REQUIREMENTS NOTED IN
 COMMENT #1, AN ESTIMATED VOLTAGE DROP CALCULATION SHOWS
 THAT SOME EXISTING WIRING APPEARS TO NOT BE SIZED
 ADEQUATELY TO COMPLY WITH FBC ENERGY CODE. PROVIDE
 CORRECTIONS AS NECESSARY SO THAT CONDUCTORS ARE SIZED
 FOR A MAXIMUM VOLTAGE DROP OF 3%. FBC C405.7.3.2, FBC
 107.2.1
 3. SHEET E1, RTU SCHEDULE, SHOWS A DIFFERENT VALUE FOR
 THE REQUIRED OCPD AND THE EXISTING OCPD. THE BRANCH
 CIRCUIT OVERCURRENT PROTECTION DEVICE RATING SHALL BE
 THE SIZE AND TYPE MARKED ON THE EQUIPMENT. NEC 110.3,
 440.22(C)
 4. SHEET RE3, CASE DEFROST DETAIL, STATES THAT B PHASE
 IS A HIGH LEG, BUT ALSO STATES THAT THIS IS A 208 VOLT
 SYSTEM WHICH DOES NOT HAVE A HIGH LEG. PLEASE CLARIFY
 AND/OR CORRECT. FBC 107.2.1
 5. PROVIDE PANEL SCHEDULE FOR ANY PANEL AFFECTED BY
 PROPOSED WORK. INCLUDE DETAILS OF WIRING AND BREAKER
 SIZE FOR NEW AND ALTERED CIRCUITS. INCLUDE TOTAL LOAD
 CALCULATED FOR PANEL TO CONFIRM THE CAPACITY OF PANEL
 IS SUFFICIENT TO SUPPLY LOADS. NEC 215.5, 408.4,
 408.30; FBC 107.2.1, 107.3.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-12-20 Cont ID  
Sent By wjolin Date 2017-12-20 Time 14:15 Rev Time 0.00
Received By wjolin Date 2017-12-20 Time 13:56 Sent To  
Notes
2017-12-20 14:15:07I HAVE REVIEWED THE RESPONSE LETTER DATED AUG. 10, 2017
 FROM MS. SHERRY BROWN OF GLOBAL SECURITY. THE LETTER
 INDICATES 3 REASONS WHY FIRE ALARM NOTIFICATION
 APPLIANCES ARE NEEDED; HOWEVER, NONE OF THE REASONS ARE
 SUPPORTED BY NFPA 72. IF THE FIRE INSPECTOR FIELD
 RESULTS INDICATE LOW AUDIBILITY IN THE NEW FREEZERS,
 THEN TO MEET THE AUDIOBILITY REQUIREMENTS OF NFPA 72,
 TYPICALLY FIRE ALARM NOTIFICATION DEVICES WILL BE
 REQUIRED IN THESE LARGE COOLERS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-08-02 Cont ID  
Sent By wjolin Date 2017-08-02 Time 11:03 Rev Time 0.00
Received By wjolin Date 2017-08-02 Time 10:27 Sent To  
Notes
2017-08-02 11:03:25TO MEET THE AUDIOBILITY REQUIREMENTS OF NFPA 72,
 TYPICALLY FIRE ALARM NOTIFICATION DEVICES WILL BE
 REQUIRED IN THESE LARGE COOLERS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-05 Cont ID  
Sent By shill Date 2018-01-05 Time 12:17 Rev Time 0.00
Received By shill Date 2017-12-12 Time 16:21 Sent To  
Notes
2017-12-13 16:21:57B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-08-09 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-27 Time 10:55 Sent To  
Notes
2017-07-31 10:55:45B25

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-12-21 Cont ID  
Sent By ccole Date 2017-12-21 Time 16:21 Rev Time 0.00
Received By ccole Date 2017-12-21 Time 15:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-09 Cont ID  
Sent By ccole Date 2017-08-09 Time 08:03 Rev Time 0.00
Received By ccole Date 2017-08-09 Time 07:15 Sent To  
Notes
2017-08-09 08:45:441ST REVIEW FBC-2014 MECHANICAL , EXISTING BUILDING, &
 ENERGY CONSERVATION CODES.
 PERMIT #17071087
 8/9/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET R3: REFER TO SECTION 1104.2 AND INDICATE THE
 AMOUNT OF REFRIGERANT IN EACH CIRCUIT.
  
 2) REM2: CLARIFY IF EMERGENCY VENTILATION WILL BE
 PROVIDED AT LEAK DETECTION ALARM LOCATIONS.
  
 3) PROVIDE REFRIGERANT PIPING SPECIFICATIONS- SECTION
 1107.5.
  
 4) PROVIDE SUBMITTALS FOR THE LEAK DETECTORS, PIPING
 INSULATION, AND PIPING PENETRATION SEALANTS. PLEASE
 NOTE THAT ALL SUBMITTALS SHALL BE APPROVED BY THE
 ENGINEER OF RECORD.
  
 5) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR ALL
 NEW RTU'S- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 6) PROVIDE DUCT SMOKE DETECTORS IN THE RETURN AIR
 SYSTEMS OF ALL NEW AND REPLACED RTU'S- SECTION 606.2.1.
 PLEASE NOTE THIS REQUIREMENT WILL BE WAIVED IF
 MANUFACTURER'S SPECIFICATIONS INDICATE THE UNITS ARE
 NOT CAPABLE OF SUPPLYING OVER 2000 CFMS OF AIR.
  
 7) REFER TO TABLE 403.3 AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL NEW ROOMS AND SPACES.
  
 8) THE PLAN IS SPECIFYING "NEW" AND "REPLACED" RTU'S.
 PROVIDE STRUCTURAL ENGINEERING FOR THE ROOF OPENINGS
 AND SUPPORTS FOR THE NEW RTU'S.
  
 9) M2: SUBMIT THE LENNOX BRACKET SPECIFICATIONS WITH
 APPROVAL STAMP BY THE ENGINEER OF RECORD. THE EOR SHALL
 SPECIFY HOW MANY BRAQCKETS AND SCREWS ARE REQUIRED PER
 WIND LOAD CALCULATIONS- SECTION 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  