Plan Review Details - Permit 17070927
Plan Review Stops For Permit 17070927
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-27 Cont ID  
Sent By tklarge Date 2017-07-27 Time 10:46 Rev Time 0.00
Received By tklarge Date 2017-07-27 Time 10:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-25 Cont ID  
Sent By tklarge Date 2017-07-25 Time 06:19 Rev Time 0.00
Received By tklarge Date 2017-07-25 Time 06:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-07-27 Cont ID  
Sent By tklarge Date 2017-07-27 Time 10:45 Rev Time 0.00
Received By tklarge Date 2017-07-27 Time 10:38 Sent To  
Notes
2017-07-27 10:45:491) THE BACKFLOW DEVICE SHALL BE LOCATED AT THE WATER
 METER PER THE CITY OF WPB CROSS-CONNECTION MANUAL. 2ND
 REQUEST.THE SUBMITTED DRAWING SHOWS THE DEVICE AT THE
 FICUS TREES. CONTACT THE UTILITIES DEPT.AT
 561-822-2240. FOR APPROVAL OF THE BACKFLOW LOCATION.
 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE. THE
 SUBMITTED SPECIFICATIONS DO NOT SHOW THAT THE DEVICE IS
 LEAD FREE. 2ND REQUEST.
 3) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF
 SOUTHERN CALIFORNIA'S ( USC ) LIST OF APPROVED DEVICES.
 4) CONTACT FIELD CUSTOMER SERVICE AT 561-822-2240 TO
 CONFIRM IF THE DEVICE YOU ARE PURCHASING MEETS THE
 CITY'S REQUIREMENTS.
 5) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS THAT SHOW THE DEVICE IS LEAD FREE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-25 Cont ID  
Sent By tklarge Date 2017-07-25 Time 06:19 Rev Time 0.00
Received By tklarge Date 2017-07-25 Time 06:13 Sent To  
Notes
2017-07-25 06:19:211) DRAWINGS DONE IN PECIL ARE UNACCEPTABLE. WPB AMEND.
 TO FBC SEC. 107.2.1.
 2) THE BACKFLOW DEVICE SHALL BE LOCATED AT THE WATER
 METER PER THE CITY OF WPB CROSS-CONNECTION MANUAL.
 3) DOCUMENTATION REQUIRED FOR BACKFLOW PREVENTION
 DEVICE PERMITS :
 EFFECTIVE DATE: JANUARY 4TH, 2016
 THE PERMIT APPLICATION SHALL BE SUBMITTED WITH THE
 FOLLOWING DOCUMENTATION:
 1) TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL AND SIZE OF THE
 DEVICE SHALL BE NOTED IN THE DESCRIPTION OF WORK
 SECTION ON THE PERMIT APPLICATION.
 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE.
 3) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF
 SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED DEVICES.
 4) CONTACT FIELD CUSTOMER SERVICE AT 561-822-2240 TO
 CONFIRM IF THE DEVICE YOU ARE PURCHASING MEETS THE
 CITY?S REQUIREMENTS.
 5) BACKFLOW PREVENTION DEVICES SHALL BE LOCATED
 IMMEDIATELY AFTER THE METER AND MUST BE TESTED AND
 CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES
 DEPARTMENT. PLEASE CONTACT THE CITY OF WEST PALM BEACH
 PUBLIC UTILITIES CENTRAL OPERATIONS AT 561-822-2210 TO
 ARRANGE FOR THE UTILITIES DEPARTMENT TO CERTIFY THE
 DEVICE.
 NOTE: THE PERMIT CARD AND MANUFACTURER?S SPECIFICATIONS
 SHALL BE ON THE JOBSITE FOR INSPECTION.
  
 THE ESTIMATED REVIEW TIME FOR THESE PERMITS IS
 APPROXIMATELY 72 HOURS.
 THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL CAN BE FOUND AT :
 HTTP://WPB.ORG/UTILITIES/BACKFLOW
 UNIVERSITY OF SOUTHERN CALIFORNIA WEBSITE ADDRESS:
 WWW.USC.EDU/DEPT/FCCCHR
 QUESTIONS REGARDING PERMITTING REQUIREMENTS MAY BE
 DIRECTED TO:
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-805-6692
 [email protected]
  
  