| 2017-08-16 15:37:47 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1) RECEPTACLE CONTROL INDICATED ON PLAN IS NOT |
| | COMPLETE. PROVIDE CORRECTION PER FBC C405.7.1 THE |
| | FOLLOWING AREAS REQUIRE CONTROL: AUTOMATIC RECEPTACLE |
| | CONTROL. THE FOLLOWING SHALL BE AUTOMATICALLY |
| | CONTROLLED: |
| | A. AT LEAST 50% OF ALL 125-VOLT 15 AND 20 AMP |
| | RECEPTACLES IN ALL PRIVATE OFFICES, CONFERENCE ROOMS, |
| | ROOMS USED PRIMARILY FOR PRINTING AND/OR COPYING |
| | FUNCTIONS, BREAK ROOMS, CLASSROOMS, AND INDIVIDUAL |
| | WORKSTATIONS. |
| | B. AT LEAST 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR |
| | MODULAR FURNITURE NOT SHOWN ON THE CONSTRUCTION |
| | DOCUMENTS. |
| | THIS CONTROL SHALL FUNCTION ON: |
| | A. A SCHEDULED BASIS USING A TIME-OF-DAY OPERATED |
| | CONTROL DEVICE THAT TURNS RECEPTACLES OFF A SPECIFIC |
| | PROGRAMMED TIMES ? AN INDEPENDENT PROGRAM SCHEDULE |
| | SHALL BE PROVIDED FOR CONTROLLED AREAS OF NO MORE THAN |
| | 5000 SQ. FT. AND NOT MORE THAN ONE FLOOR (THE OCCUPANT |
| | SHALL BE ABLE TO MANUALLY OVERRIDE THE CONTROL DEVICE |
| | FOR UP TO TWO HOURS), OR |
| | B. AN OCCUPANT SENSOR THAT SHALL TURN RECEPTACLES OFF |
| | WITHIN 20 MINUTES OF ALL OCCUPANTS LEAVING A SPACE, OR |
| | C. AN AUTOMATED SIGNAL FROM ANOTHER CONTROL OR ALARM |
| | SYSTEM THAT SHALL TURN RECEPTACLES OFF WITHIN 20 |
| | MINUTES AFTER DETERMINING THAT THE AREA IS UNOCCUPIED. |
| | ALL CONTROLLED RECEPTACLES SHALL BE PERMANENTLY MARKED |
| | TO VISUALLY DIFFERENTIATE THEM FROM UNCONTROLLED |
| | RECEPTACLES AND ARE TO BE UNIFORMLY DISTRIBUTED |
| | THROUGHOUT THE SPACE. |
| | |
| | 2) PRIMARY OVERCURRENT PROTECTION FOR 45KVA TRANSFORMER |
| | THAT FEEDS PANEL LA17 EXCEEDS THE VALUE PERMITTED BY |
| | CODE. PROVIDE CORRECTION. NEC TABLE 450.3(B) |
| | |
| | 3) ARE THE DISCONNECTS ON THE BUS DUCT CAPABLE OF BEING |
| | LOCKED IN THE OPEN POSITION, OR WILL THERE BE |
| | DISCONNECTS PROVIDED AT THE TRANSFORMER LOCATION? |
| | PROVIDE CLARIFICATION. NEC 450.14, FBC 107.2.1 |
| | |
| | 4) PROVIDE DETAIL ON RISER DIAGRAM FOR ALL FEEDERS, |
| | SOME ARE MISSING THE SIZE OF CONDUIT AND WIRE. FBC |
| | 107.2.1, NEC 310.15, 240.4, 215.5 |
| | |
| | 5) SPECIFY THE WIRE SIZE FOR THE GROUNDING ELECTRODE |
| | CONDUCTOR FOR TRANSFORMERS. NEC 250.30(4) |
| | |
| | 6) PROVIDE INTERIOR LIGHTING CALCULATION SHOWING |
| | COMPLIANCE WITH THE FBC ENERGY CODE. FBC C405.5 |
| | |
| | 7) PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT |
| | CURRENT AT PANELS TO CONFIRM STATED AIC RATING OF |
| | PANELS IS ADEQUATE. NEC 110.10 |
| | |
| | 8) PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT |
| | NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND DATA, |
| | WIRELESS SYSTEMS, ETC. FBC 105.1, FBC 107.2.1 |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |