Plan Review Details - Permit 17070904
Plan Review Stops For Permit 17070904
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-09-22 Cont ID  
Sent By shill Date 2017-09-22 Time 17:20 Rev Time 0.00
Received By shill Date 2017-09-22 Time 17:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-07 Cont ID  
Sent By shill Date 2017-08-07 Time 12:44 Rev Time 0.00
Received By shill Date 2017-08-07 Time 10:09 Sent To  
Notes
2017-08-07 10:29:11****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. GOVERNING CODE IS FBC 5TH EDITION (FBC 2014), REVISE
 SHEET A002 BUILDING CODE ANALYSIS (AND ANY OTHER
 AFFECTED SHEETS).
  
 2. TITLE BLOCK IS NOT IN COMPLIANCE WITH FS481;
 ARCHITECT BUSINESS NUMBER IS REQUIRED, PLEASE REVISE
 TITLE BLOCK TO INCLUDE.
  
 3. CARD READERS ARE SHOWN ON SHEET A111. THIS IS NOT
 REVIEWED AT THIS TIME; A SEPARATE PERMIT (INCLUDING
 PERMIT APPLICATION, REVIEWS, AND FEES) IS REQUIRED.
 ACCESS CONTROL WILL BE REVIEWED AT THAT TIME.
  
 4. A202, OTHER LOCATIONS, STAFF DINING ISLAND IS SHOWN
 AS 36" TALL. FBC A 902.3, DINING SURFACES SHALL BE 28"
 - 34".
  
 5. FBC B 713.14.1, REVISE PLAN TO CLARIFY COMPLIANCE AS
 IT DOES NOT APPEAR THAT A FIRE RATED LOBBY IS PROPOSED.
  
  
 *********************************
 INTERNAL USE ONLY
  
 USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG
 SQUARE FEET - 16400
  
 CONSTRUCTION TYPE: 14-I-A
 UNITS:
 FLOORS:
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE: 16400
 SQ FT FOOTPRINT: 16400
 SQ FT ROOF: 16400
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 280
 PROP USE: OFFICE
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED B
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-10-04 Cont ID  
Sent By jpearson Date 2017-10-04 Time 10:27 Rev Time 0.00
Received By jpearson Date 2017-10-04 Time 06:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-16 Cont ID  
Sent By jpearson Date 2017-08-16 Time 15:37 Rev Time 0.00
Received By jpearson Date 2017-08-16 Time 15:37 Sent To  
Notes
2017-08-16 15:37:47CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) RECEPTACLE CONTROL INDICATED ON PLAN IS NOT
 COMPLETE. PROVIDE CORRECTION PER FBC C405.7.1 THE
 FOLLOWING AREAS REQUIRE CONTROL: AUTOMATIC RECEPTACLE
 CONTROL. THE FOLLOWING SHALL BE AUTOMATICALLY
 CONTROLLED:
 A. AT LEAST 50% OF ALL 125-VOLT 15 AND 20 AMP
 RECEPTACLES IN ALL PRIVATE OFFICES, CONFERENCE ROOMS,
 ROOMS USED PRIMARILY FOR PRINTING AND/OR COPYING
 FUNCTIONS, BREAK ROOMS, CLASSROOMS, AND INDIVIDUAL
 WORKSTATIONS.
 B. AT LEAST 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR
 MODULAR FURNITURE NOT SHOWN ON THE CONSTRUCTION
 DOCUMENTS.
 THIS CONTROL SHALL FUNCTION ON:
 A. A SCHEDULED BASIS USING A TIME-OF-DAY OPERATED
 CONTROL DEVICE THAT TURNS RECEPTACLES OFF A SPECIFIC
 PROGRAMMED TIMES ? AN INDEPENDENT PROGRAM SCHEDULE
 SHALL BE PROVIDED FOR CONTROLLED AREAS OF NO MORE THAN
 5000 SQ. FT. AND NOT MORE THAN ONE FLOOR (THE OCCUPANT
 SHALL BE ABLE TO MANUALLY OVERRIDE THE CONTROL DEVICE
 FOR UP TO TWO HOURS), OR
 B. AN OCCUPANT SENSOR THAT SHALL TURN RECEPTACLES OFF
 WITHIN 20 MINUTES OF ALL OCCUPANTS LEAVING A SPACE, OR
 C. AN AUTOMATED SIGNAL FROM ANOTHER CONTROL OR ALARM
 SYSTEM THAT SHALL TURN RECEPTACLES OFF WITHIN 20
 MINUTES AFTER DETERMINING THAT THE AREA IS UNOCCUPIED.
 ALL CONTROLLED RECEPTACLES SHALL BE PERMANENTLY MARKED
 TO VISUALLY DIFFERENTIATE THEM FROM UNCONTROLLED
 RECEPTACLES AND ARE TO BE UNIFORMLY DISTRIBUTED
 THROUGHOUT THE SPACE.
  
 2) PRIMARY OVERCURRENT PROTECTION FOR 45KVA TRANSFORMER
 THAT FEEDS PANEL LA17 EXCEEDS THE VALUE PERMITTED BY
 CODE. PROVIDE CORRECTION. NEC TABLE 450.3(B)
  
 3) ARE THE DISCONNECTS ON THE BUS DUCT CAPABLE OF BEING
 LOCKED IN THE OPEN POSITION, OR WILL THERE BE
 DISCONNECTS PROVIDED AT THE TRANSFORMER LOCATION?
 PROVIDE CLARIFICATION. NEC 450.14, FBC 107.2.1
  
 4) PROVIDE DETAIL ON RISER DIAGRAM FOR ALL FEEDERS,
 SOME ARE MISSING THE SIZE OF CONDUIT AND WIRE. FBC
 107.2.1, NEC 310.15, 240.4, 215.5
  
 5) SPECIFY THE WIRE SIZE FOR THE GROUNDING ELECTRODE
 CONDUCTOR FOR TRANSFORMERS. NEC 250.30(4)
  
 6) PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FBC ENERGY CODE. FBC C405.5
  
 7) PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT PANELS TO CONFIRM STATED AIC RATING OF
 PANELS IS ADEQUATE. NEC 110.10
  
 8) PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT
 NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND DATA,
 WIRELESS SYSTEMS, ETC. FBC 105.1, FBC 107.2.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-09-20 Cont ID  
Sent By pleduc Date 2017-09-20 Time   Rev Time 0.00
Received By pleduc Date 2017-09-19 Time 16:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-07-27 Cont ID  
Sent By pleduc Date 2017-07-27 Time   Rev Time 0.00
Received By pleduc Date 2017-07-26 Time 14:31 Sent To  
Notes
2017-07-26 17:10:56THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET 002 - THERE ARE NO INDICATIONS OF REVIEW
 AND/OR COMPLIANCE WITH ANY FIRE CODE
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
 PROVIDE AN APPLICABLE NOTE
  
  
  
  
 2) SHEET A 121 - IN THEACT& GWB SCHEDULE THERE ARE
 INDICATION OF SPECIFICATION REFERRING TO SHEET A 700.
 THERE IS NO SHEET A 700 AS PART OF THIS SUBMITTAL.
  
 PER NFPA 101, CHAPTER 38, NEW BUSINESS OCCUPNACUES.
  
 38.3.3 INTERIOR FINISH.
 38.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH SECTION 10.2.
 38.3.3.2 INTERIOR WALL AND CEILING FINISH.
 38.3.3.2.1 INTERIOR WALL AND CEILING FINISH MATERIAL
 COMPLYING WITH SECTION 10.2 SHALL BE CLASS A OR CLASS B
 IN EXITS AND IN EXIT ACCESS CORRIDORS.
 38.3.3.2.2 INTERIOR WALL AND CEILING FINISHES SHALL BE
 CLASS A, CLASS B, OR CLASS C IN AREAS OTHER THAN THOSE
 SPECIFIED IN 38.3.3.2.1.
  
 PLEASE PROVIDE THA APPLICABLE MAUNFACTURERS SPEC SHEETS
 OF SHEET A 700 WITH THE APPLICABLE INFORMATION SHOWING
 COMPLIANCE.
  
  
  
 3) SHEET E 0.1 & 2.1 - THERE ARE INDICATIONS OF FIRE
 ALARM EQUIPMENT. ALL WORK ON THE FIRE ALARM SYSTEM OR
 ON ANY EQUIPMENT SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 PLEASE PROVIDE AN APPICABLE NOTE OF COMPLIANCE.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-04 Cont ID  
Sent By gjohnson Date 2017-10-04 Time 18:47 Rev Time 0.00
Received By gjohnson Date 2017-09-14 Time 14:27 Sent To  
Notes
2017-09-18 14:32:17C05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-08-24 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-24 Time 15:54 Sent To  
Notes
2017-07-25 15:54:56C01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-08-24 Cont ID  
Sent By ccole Date 2017-08-24 Time 11:34 Rev Time 0.00
Received By ccole Date 2017-08-24 Time 11:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-08-24 Cont ID  
Sent By ccole Date 2017-08-24 Time 11:30 Rev Time 0.00
Received By ccole Date 2017-08-24 Time 10:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-04 Cont ID  
Sent By gjohnson Date 2017-10-04 Time 18:47 Rev Time 0.00
Received By gjohnson Date 2017-10-04 Time 18:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-22 Cont ID  
Sent By gjohnson Date 2017-08-22 Time 16:46 Rev Time 0.00
Received By gjohnson Date 2017-08-22 Time 15:40 Sent To  
Notes
2017-08-22 17:01:111ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. GRAB BARS SHALL BE MEASURED FROM FINISHED FLOOR TO
 TOP OF GRIPPING SURFACE. PER FBC ACC 609.4
  
 2. WATER-HAMMER ARRESTORS SHALL BE INSTALLED ON ICE
 MACHINES COFFEE MAKERS AND DISHWASHERS AND ANY SENSOR
 FAUCETS. PER FBC PL 604.9
  
 3. A BACKFLOW IS REQUIRED ON THE ICE MAKERS AND COFFEE
 MAKERS. PER FBC PL 608.3, 608.16.10
  
 4. TEMPERED WATER IS REQUIRED AT THE LAVATORY FAUCET.
 PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  