Plan Review Details - Permit 17070895
Plan Review Stops For Permit 17070895
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-09-25 Cont ID  
Sent By rmcdouga Date 2017-09-25 Time 18:52 Rev Time 0.00
Received By rmcdouga Date 2017-09-25 Time 11:48 Sent To  
Notes
2017-09-25 18:14:54APPROVED WITH EXCEPTIONS (BUILDING PROVISO)
 THE ROOFING CONTRACTOR IS REQUIRED TO SUBMIT SIGNED AND
 SEALED RAS117 CALCULATIONS FOR THE FLAT ROOF.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-16 Cont ID  
Sent By rmcdouga Date 2017-08-16 Time 14:40 Rev Time 0.00
Received By rmcdouga Date 2017-08-14 Time 18:46 Sent To  
Notes
2017-08-16 09:26:45PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.5.3 - SPECIFY THE WIND DESIGN DATA ON THE
 PLANS. ( I.E. WIND SPEED AND EXPOSURE CATEGORY )
  
 2) FBC-R310.1 THE NEW SINGLE HUNG WINDOWS FOR THE
 BEDROOMS 1 AND 2 DO NOT MEET THE REQUIREMENTS OF FBC
 R310 FOR EMERGENCY AND RESCUE OPENINGS. INDICATE THE
 EXISTING WINDOW'S TYPE AND THE NET CLEAR OPENING SIZE
 OF IT. PROVIDE CALCULATIONS TO SHOW THAT THE NET CLEAR
 OPENING DIMENSIONS OF THE EXISTING WINDOW ARE NOT BEING
 REDUCED BY MORE THAN 5-PERCENT PER FBC EXISTING
 BUILDING SECTION 704.1.
  
 3) SPECIFY THE SIZE OF THE THRU BOLTS THAT ARE SHOWN ON
 TRELLIS DETAIL 6 ON SHEET A4.0. FBC-R 301.1
  
 4) TREATED ROD DOWELS SET IN EPOXY ARE SPECIFIED ON
 TRELLIS DETAIL 6 ON SHEET A4.0 TO ANCHOR THE JOISTS.
 PLEASE PROVIDE ADDITIONAL INFORMATION ON THE RODS AND
 THE EPOXY THAT IS PROPOSED. PROVIDE PRODUCT APPROVALS
 OR CALCULATIONS FOR THIS CONNECTION. FBC 107.2.1.3
  
 5) ON SHEET S1.0, ACI 318 IS REFERENCED WITH VARIOUS
 EDITIONS. CHAPTER 46 OF THE 2014 FBC-R REFERENCES THE
 2011 EDITION OF ACI. PLEASE REVISE TO ACI 318-11. FBC
 107.2.1
  
 6) THE DOOR SCHEDULE ON SHEET A6.0 SPECIFIES PRODUCT
 APPROVAL FL15210.1 AND PART OF PRODUCT APPROVAL FL 4940
 WAS SUBMITTED. THE INSTALLATION INSTRUCTION PORTION OF
 THE PRODUCT APPROVAL IS REQUIRED TO BE SUBMITTED. THE
 PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD PER FBC 107.3.4.1.
  
 7) THE DOOR SCHEDULE ON SHEET A6.0 SPECIFIES PRODUCT
 APPROVAL NOA NO. 17-0130.01 FOR AN EXTERIOR GLAZED
 DOOR. NO PRODUCT APPROVALS WERE SUBMITTED FOR THIS
 DOOR. SUBMIT PRODUCT APPROVALS FOR THIS DOOR THAT HAVE
 BEEN REVIEWED AND APPROVED BY THE DESIGNER OF RECORD.
 FLORIDA STATUTE 553.842 (5)
  
 8) THE WINDOW SCHEDULE ON SHEET A6.0 LISTS THE TYPE AS
 DOUBLE HUNG AND THE COMMENTS SPECIFY SINGLE HUNG.
 PLEASE CLARIFY. FBC 107.2.1
  
 9) NOA NO. 15-0519.08 WHICH IS LISTED IN THE WINDOW
 SCHEDULE HAS BEEN SUPERSEDED BY NOA NO. 16-0714.06.
 PLEASE UPDATE PLANS. THE PRODUCT APPROVALS ARE REQUIRED
 TO BE REVIEWED AND APPROVED BY THE DESIGNER OF RECORD
 PER FBC 107.3.4.1.
  
 10) SPECIFY THE SLOPE OF THE CLAY TILE COVERED PORCH.
 FBC 107.2.1
  
 11) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE CLAY ROOF TILE. FBC-R905.3.6 IF A ROOF
 TILE ADHESIVE IS TO BE USED, SUBMIT THE PRODUCT
 APPROVALS FOR IT. FBC 107.3.4.1
  
 12) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 ENHANCED FASTENING CALCULATIONS AS REQUIRED BY
 LIMITATION NUMBER 7 ON PAGE 5 OF NOA NO. 16-0425.02 FOR
 THE US PLY BUR.
  
 13) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-09-20 Cont ID  
Sent By jpearson Date 2017-09-20 Time 13:32 Rev Time 0.00
Received By jpearson Date 2017-09-20 Time 13:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-08 Cont ID  
Sent By jpearson Date 2017-08-08 Time 13:17 Rev Time 0.00
Received By jpearson Date 2017-08-08 Time 13:17 Sent To  
Notes
2017-08-08 13:17:02CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM STATES THAT WIRES IN THE RISER ARE
 SIZED BY FPL, WHICH IS INCORRECT. SIZE WIRE PER NEC AND
 STATE ON PLAN. NEC 215.2, 220, 310.15: FBC RE3602.1
 2. # 1 WIRE FROM METER TO DISCONNECT AND FROM
 DISCONNECT TO INTERIOR PANEL IS NOT SIZED PROPERLY FOR
 200 AMP SERVICE . PROVIDE CORRECTION. NEC 215.2,
 310.15; FBC RE3602.1
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 4. NOTE #1 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE4002.14
 5. NOTE 13 STATES THAT LIGHTING IN CLOSETS MUST COMPLY
 WITH NEC 410.8. WHICH IS NOT THE CORRECT CODE SECTION
 FOR LIGHTING IN CLOSETS. PROVIDE CORECTION. NEC
 410.16(B), FBC RE4003.12
 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 7. CIRCUITS 13 AND 21 SHOULD BE AFCI PROTECTED BASED ON
 DESCRIPTION. PROVIDE CORRECITON. NEC 210.12; FBC
 RE3902.12
 8. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH
 GRADE LEVEL ACCESS. PROVIDE CORRECTION. NEC
 210.70(A)(2)(B), FBC RE3903.3
 9. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE3901.7
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-08-01 Cont ID  
Sent By destabro Date 2017-08-01 Time 14:36 Rev Time 0.00
Received By destabro Date 2017-08-01 Time 14:36 Sent To B
Notes
2017-08-01 14:38:068/1/2017 - FULL RENOVATION OF CONTRIBUTING PROPERTY TO
 THE NORTHWEST HISTORIC DISTRICT. PRIOR FIRE DAMAGE TO
 BE REPAIRED IN-KIND - PROPOSED REPLACEMENT WINDOWS AND
 DOORS MEET DESIGN GUIDELINES FOR HISTORIC DISTRICT. NEW
 SIDE LOGGIA APPROPRIATE FOR THIS STYLE OF HOUSE. MEETS
 CONDITIONS FOR APPROVAL (HPB CASE NO. 17-33). DLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-25 Cont ID  
Sent By rmcdouga Date 2017-09-25 Time 18:52 Rev Time 0.00
Received By rmcdouga Date 2017-08-28 Time 15:46 Sent To  
Notes
2017-08-29 15:47:05R23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-16 Cont ID  
Sent By rmcdouga Date 2017-08-16 Time 14:40 Rev Time 0.00
Received By rmcdouga Date 2017-07-24 Time 15:50 Sent To  
Notes
2017-07-25 15:51:01R06

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-08-15 Cont ID  
Sent By rmcdouga Date 2017-08-15 Time 07:15 Rev Time 0.00
Received By rmcdouga Date 2017-08-15 Time 06:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-08-14 Cont ID  
Sent By rmcdouga Date 2017-08-14 Time 18:59 Rev Time 0.00
Received By rmcdouga Date 2017-08-14 Time 18:59 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2017-09-25 Cont ID  
Sent By rmcdouga Date 2017-09-25 Time 18:09 Rev Time 0.00
Received By rmcdouga Date 2017-09-25 Time 18:08 Sent To  
Notes
2017-09-25 18:12:53ROOFING
 BORAL ROOFING MISSION CLAY TILE, NOA NO. 12-0605.08
 QUICKRETE ROOF TILE MORTAR FL-15
 US PLY BUILT-UP ROOFING, NOA NO. 16-0425.02 ( THE
 ROOFING CONTRACTOR IS REQUIRED TO SUBMIT SIGNED AND
 SEALED RAS 117 CALCULATIONS. )
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-08-15 Cont ID  
Sent By rmcdouga Date 2017-08-15 Time 08:16 Rev Time 0.00
Received By rmcdouga Date 2017-08-15 Time 07:26 Sent To  
Notes
2017-08-15 07:33:23ROOFING
 BORAL ROOFING MISSION CLAY TILE, NOA NO. 12-0605.08
 US PLY BUILT-UP ROOFING, NOA NO. 16-0425.02
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-09-01 Cont ID  
Sent By destabro Date 2017-09-01 Time 13:35 Rev Time 0.00
Received By destabro Date 2017-09-01 Time 13:35 Sent To B
Notes
2017-09-01 13:35:599/1/2017 - LANDSCAPE PERMIT SUBMITTED (#17081269). DLE

Review Stop Z ZONING
Rev No 1 Status F Date 2017-08-01 Cont ID  
Sent By destabro Date 2017-08-01 Time 14:36 Rev Time 0.00
Received By destabro Date 2017-08-01 Time 15:02 Sent To B
Notes
2017-08-01 14:50:368/1/2017 - VALUE OF IMPROVEMENTS EXCEEDS HALF OF
 EXISTING HOUSE VALUE. SEPARATE LANDSCAPE PERMIT IS
 REQUIRED PER ORDINANCE 4689-16. THIS HOLD WILL BE
 RELEASED ONCE THE LANDSCAPE PERMIT APPLICATION IS
 SUBMITTED. QUESTIONS MAY BE DIRECTED TO RAY CARANCI,
 LANDSCAPE PLANNER AT 561-822-1462.