Plan Review Details - Permit 17070883
Plan Review Stops For Permit 17070883
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-08-08 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-02 Time 10:56 Sent To  
Notes
2017-08-03 10:57:09RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-01 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-28 Time 14:35 Sent To  
Notes
2017-07-31 14:35:16RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-07-26 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-24 Time 14:09 Sent To  
Notes
2017-07-25 14:10:04ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-08-08 Cont ID  
Sent By ccole Date 2017-08-08 Time 13:11 Rev Time 0.00
Received By ccole Date 2017-08-08 Time 13:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-01 Cont ID  
Sent By ccole Date 2017-08-01 Time 08:35 Rev Time 0.00
Received By ccole Date 2017-08-01 Time 08:35 Sent To  
Notes
2017-08-01 08:46:532ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17070883
 8/1/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENGINEER THOMAS J. TWOMEY P.E. WHOSE TITLE BLOCK
 IS ON THE PLAN MUST PROVIDE HIS SIGNATURE AND SEAL TO
 THE PLAN SHEET IN COMPLIANCE WITH SECTION 61G15-23.002
 FLORIDA ADMINISTRATIVE CODE.
  
 2) THE 6" FLEX DUCTS ARE UNDERSIZED FOR 150 CFMS AT
 STANDARD 0.1" FRICTION LOSS.
  
 3) THE 7" & 8" TRANSFER DUCTS IN THE 2ND FLOOR BEDROOMS
 ARE UNDERSIZED PER SECTION M1602.4 FBC-14 RESIDENTIAL:
 THE TRANSFER DUCTS MUST BE 1-1/2 TIMES THE
 CROSS-SECTIONAL AREA OF THE SUPPLY DUCT ENTERING THE
 ROOM.
  
 4) INDICATE HOW AIR RETURNING TO THE 18X18" GRILL IN
 THE HALLWAY IS BEING TRANSFERED TO THE AIR HANDLER
 WHICH IS LOCATED IN THE MASTER BEDROOM- SECTION
 M1602.4.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-26 Cont ID  
Sent By ccole Date 2017-07-26 Time 11:24 Rev Time 0.00
Received By ccole Date 2017-07-26 Time 11:24 Sent To  
Notes
2017-07-26 11:28:441ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070883
 7/26/16
  
 1) SUBMIT THE CITY OF WEST PALM BEACH AC CHANGEOUT
 FORMS FOR THE REPLACED SYSTEMS. TWO SIGNED COPIES FOR
 EACH SYSTEM REQUIRED- SEE SECTION 107.2.1 WPB
 AMENDMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  