Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-01-26 Cont ID  
Sent By jwitmer Date 2018-01-26 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2018-01-26 Time 05:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-11-27 Cont ID  
Sent By shill Date 2017-11-27 Time 18:07 Rev Time 0.00
Received By shill Date 2017-11-27 Time 18:07 Sent To  
Notes
2017-11-27 18:11:21SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 2014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070822
 ADD: 124 N. DIXIE HWY.
 CONT: PAN AMERICAN ENGINEERING
 TEL: 561-254-4858
 E-MAIL: ??????????? PLEASE PROVIDE, WE COMMUNICATE WITH
 E-MAIL.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 COMMENTS FROM 2ND REVIEW NOT ADDRESSED
 DATE: 11/27/17
 ACTION: DENIED
  
 1-5) COMPLIED.
  
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 6) SUBMITTED NOA 16-0421.10 PGT SE-3550 OUTSWING DOOR &
 NOA 16-0505.04 PGT SS-3500 STOREFRONT SYSTEM, THE
 CONTRACTOR NOR THE DESIGNER OF RECORD HAS NOT
 IDENTIFIED ELEMENTS IN THE ASSEMBLY.
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 7)SEMI ?COMPLIED SEE COMMENT ABOVE.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ***NEW COMMENT***
 THE PRODUCT APPROVALS SUBMITTED INCLUDE DRAWING SHEETS
 WHICH DID NOT PRINT PROPERLY. FBC 107, PROVIDE A
 COMPLETE LEGIBLE FULL SIZE PRODUCT APPROVAL INDICATING
 METHOD OF INSTALLATION AS WELL AS COMPONENTS SUCH AS
 IMPACT BAR, ADA THRESHOLD. THE PRODUCT APPROVAL
 CONTAINS MANY DIFFERENT INSTALLATION OPTIONS. APPLICANT
 IS TO INDICATE WHICH IS PROPOSED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-10-01 Cont ID  
Sent By jwitmer Date 2017-10-01 Time 16:30 Rev Time 0.00
Received By jwitmer Date 2017-10-01 Time 15:58 Sent To  
Notes
2017-10-01 16:21:372014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070822
 ADD: 124 N. DIXIE HWY.
 CONT: PAN AMERICAN ENGINEERING
 TEL: 561-254-4858
 E-MAIL: ??????????? PLEASE PROVIDE, WE COMMUNICATE WITH
 E-MAIL.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SUN. OCT. 01/ 2017
 ACTION: DENIED
  
 1-5) COMPLIED.
  
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 6) SUBMITTED NOA 16-0421.10 PGT SE-3550 OUTSWING DOOR &
 NOA 16-0505.04 PGT SS-3500 STOREFRONT SYSTEM, THE
 CONTRACTOR NOR THE DESIGNER OF RECORD HAS NOT
 IDENTIFIED ELEMENTS IN THE ASSEMBLY.
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 7)SEMI ?COMPLIED SEE COMMENT ABOVE.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-28 Cont ID  
Sent By jwitmer Date 2017-07-28 Time 07:01 Rev Time 0.00
Received By jwitmer Date 2017-07-27 Time 16:47 Sent To  
Notes
2017-07-28 07:01:042014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070822
 ADD: 124 N. DIXIE HWY.
 CONT: PAN AMERICAN ENGINEERING
 TEL: 561-254-4858
 E-MAIL: ??????????? PLEASE PROVIDE, WE COMMUNICATE WITH
 E-MAIL.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JULY 28/ 2017
 ACTION: DENIED
  
 1) SHEETS A-1 & A-3 BOTH INDICATE THIS TO BE A
 MERCANTILE OCCUPANCY. DELI OR FOOD ESTABLISHMENTS WITH
 OCCUPANT LOADS LESS THAN 50 ARE CLASSIFIED AS A
 BUSINESS OCCUPANCY. 2014 FBC-B 303.1.1 SMALL BUILDINGS
 AND TENANT SPACES. A BUILDING OR TENANT SPACE USED FOR
 ASSEMBLY PURPOSES WITH AN OCCUPANT LOAD OF LESS THAN 50
 PERSONS SHALL BE CLASSIFIED AS GROUP B OCCUPANCY.
  
 2)THE COVERSHEET A-1 INDICATES A NEW ADA TOILET AT 50
 SQ. FT. SHEET A-2 SHOWS A MEASUREMENT BACK WALL AT 5
 FOOT 10 INCHES (EXISTING). IF THE RESTROOM IS NEW THEN
 THE COMPLIANCE WITH 2014 EXISTING BUILDING CODE LEVEL
 II 701.3 COMPLIANCE IS REQUIRED. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 BUILDING. 2014 FBC-ACCESSIBILITY:
 604.3.1 SIZE.
 604.3.2 OVERLAP.
 PLEASE NOTE THERE IS EVEN A NOTE FOR THE CLEAR FLOOR
 SPACE AND REQUIRED OVERLAP? THE PERMIT APPLICATION
 INDICATES A NEW ADA RESTROOM. IF THE RESTROOM FIXTURES
 WERE TO BE RECONFIGURED AGAINST THE 8 FOOT WALL AND THE
 WATER CLOSET WERE INSTALLED FURTHEST FROM THE DOORWAY
 CLEARANCES COULD BE MET.
  
 3) NEW ADA RESTROOM PLEASE SHOW COMPLIANCE FOR THE
 STRUCTURAL STRENGTH OF THE GRAB BARS, 2014
 ACCESSIBILITY CODE, FBC SECTION 609.8.
  
 4) THE PLANS SHOW ON SHEET A-2 A ORDER AND PICK-UP
 COUNTER, BUT NO HEIGHTS ARE GIVEN, PLEASE SHOW
 COMPLIANCE WITH :
 904.3.2 COUNTER. THE COUNTER SURFACE HEIGHT SHALL BE 38
 INCHES (965 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 5) SHEET A-2 ALSO SHOWS 10 SEATS FOR DINING, PLEASE
 SHOW COMPLIANCE WITH:
 5) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ABA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 5A)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 5B)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND
 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE OR HINGE SIDE CLEARANCE.
  
 6) SUBMITTED NOA 12-0731.06 WINDOW WALL SYSTEM, THE
 CONTRACTOR HAS NOT IDENTIFIED ELEMENTS IN THE ASSEMBLY.
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 7) PLEASE NOTE THE NOA 12-0731.06 WINDOW WALL SYSTEM
 DOES NOT INCLUDE THE DOOR STATED IN THE TECHNICAL
 SHEETS. 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-01-23 Cont ID  
Sent By jpearson Date 2018-01-23 Time 07:32 Rev Time 0.00
Received By jpearson Date 2018-01-23 Time 07:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2017-11-28 Cont ID  
Sent By jpearson Date 2017-11-28 Time 07:42 Rev Time 0.00
Received By jpearson Date 2017-11-28 Time 07:42 Sent To I
Notes
2017-11-28 07:42:00CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 3RD REVIEW. ITEMS NOT ADDRESSED SATISFACTORILY LISTED
 BELOW WITH ADDITIONAL COMMENTS IN PARENTHESES:
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE OF WORK
 AND VALUE. IT APPEARS THE VALUE LISTED ON THE PERMIT
 APPLICATION IS LOW. FBC 109.3 (HAVE NOT COMPLIED. THIS
 SHOULD INCLUDE VALUE OF ALL EQUIPMENT AND LABOR FOR A
 COMPLETE JOB.)
 2. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE ON
 BUILDING. PER THE RISER DIAGRAM, THE SERVICE WIRE HAS A
 CAPACITY OF 400 AMPS. PROVIDE LOAD CALCULATION TO
 CONFIRM THE CAPACITY IS ADEQUATE. NEC 215.2, 220; FBC
 107.2.1 (NOTE ON PLAN STATES THAT THE REVISED RISER IS
 THE CORRECTION TO THIS COMMENT, WHICH IS NOT ACCURATE.
 A LOAD CALCULATION IS REQUIRED. PROVIDE AS PREVIOUSLY
 REQUESTED.)
 3. COMPLIED.
 4. PROVIDE DETAILS OF THE METHOD OF SHUTDOWN FOR THE
 ELECTRICAL EQUIPMENT LOCATED UNDER THE HOOD PER NFPA
 96. NFPA 96, SECTION 10.4.1, FBC 107.2.1 (HAVE NOT
 COMPLIED. PROVIDE AS PREVIOUSLY REQUESTED.)
 5. COMPLIED.
 6. COMPLIED.
 7. COMPLIED.
 8. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F) (A NOTE WAS PROVIDED,
 HOWEVER, THE LIGHTING PLAN STILL SHOWS THE CIRCUITRY
 INCORRECT. PROVIDE CORRECTION ON PLAN TO MATCH NOTE.)
 9. COMPLIED.
 10. COMPLIED.
 11. COMPLIED.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-10-03 Cont ID  
Sent By jpearson Date 2017-10-03 Time 10:34 Rev Time 0.00
Received By jpearson Date 2017-10-03 Time 10:34 Sent To  
Notes
2017-10-03 10:34:15CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 2ND REVIEW. ITEMS NOT ADDRESSED SATISFACTORILY LISTED
 BELOW:
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE OF WORK
 AND VALUE. IT APPEARS THE VALUE LISTED ON THE PERMIT
 APPLICATION IS LOW. FBC 109.3
 2. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE ON
 BUILDING. PER THE RISER DIAGRAM, THE SERVICE WIRE HAS A
 CAPACITY OF 400 AMPS. PROVIDE LOAD CALCULATION TO
 CONFIRM THE CAPACITY IS ADEQUATE. NEC 215.2, 220; FBC
 107.2.1
 3. COMPLIED.
 4. PROVIDE DETAILS OF THE METHOD OF SHUTDOWN FOR THE
 ELECTRICAL EQUIPMENT LOCATED UNDER THE HOOD PER NFPA
 96. NFPA 96, SECTION 10.4.1, FBC 107.2.1
 5. PROVIDE GRAPH OF INTERIOR LIGHTING POWER ALLOWANCES
 PER THE FBC ENERGY CODE IN RELATION TO THE CONNECTED
 INTERIOR LIGHTING PROPOSED TO COMPLY WITH CODE. FBC
 C405.5
 6. COMPLIED.
 7. COMPLIED.
 8. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 9. COMPLIED.
 10. PROVIDE SHOW WINDOW OUTLET. NEC 210.62 (SHOW WINDOW
 IS PROVIDED, BUT IT IS ON THE SAME CIRCUIT AS THE SIGN,
 WHICH IS A CODE VIOLATION. SIGN MUST BE ON A DEDICATED
 CIRCUIUT. NEC 600.5(A). )
 11. COMPLIED.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-26 Cont ID  
Sent By jpearson Date 2017-07-26 Time 09:46 Rev Time 0.00
Received By jpearson Date 2017-07-26 Time 09:46 Sent To  
Notes
2017-07-26 10:09:20CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE OF WORK
 AND VALUE. IT APPEARS THE VALUE LISTED ON THE PERMIT
 APPLICATION IS LOW. FBC 109.3
 2. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE ON
 BUILDING. PER THE RISER DIAGRAM, THE SERVICE WIRE HAS A
 CAPACITY OF 400 AMPS. PROVIDE LOAD CALCULATION TO
 CONFIRM THE CAPACITY IS ADEQUATE. NEC 215.2, 220; FBC
 107.2.1
 3. RISER DIAGRAM SHOWS THE WIRE TO UNIT 332 SIZED AS
 1/0, WHICH HAS A CAPACITY OF 150 AMPS. THE CURRENT 175
 AMP FUSES EXCEED THIS CAPACITY. PROVIDE CORRECTION. NEC
 215.2, 310.15(B)(16)
 4. PROVIDE DETAILS OF THE METHOD OF SHUTDOWN FOR THE
 ELECTRICAL EQUIPMENT LOCATED UNDER THE HOOD PER NFPA
 96. NFPA 96, SECTION 10.4.1, FBC 107.2.1
 5. PROVIDE GRAPH OF INTERIOR LIGHTING POWER ALLOWANCES
 PER THE FBC ENERGY CODE IN RELATION TO THE CONNECTED
 INTERIOR LIGHTING PROPOSED TO COMPLY WITH CODE. FBC
 C405.5
 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS FOR
 INTERIOR LIGHTING STIPULATED IN THE FBC ENERGY CODE.
 FBC C405.2.2, 405.2.2.2
 7. PROVIDE CONTROL FOR THE EXHAUST FAN ON CIRCUIT C-25.
 CURRENTLY, THIS APPEARS TO BE WIRED FOR CONTINUOUS
 OPERATION. FBC MECHANICAL 405.1; FBC 107.2.1
 8. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 9. ALL OUTLETS IN KITCHEN ARE REQUIRED TO BE GFCI
 PROTECTED. PROVIDE CORRECTION. NEC 210.8(B)(2)
 10. PROVIDE SHOW WINDOW OUTLET. NEC 210.62
 11. PROVIDE AUTOMATIC CONTROL OF SIGN AND SHOW WINDOW
 CIRCUITS PER ENERGY CODE. FBC C405.2.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-11-22 Cont ID  
Sent By pleduc Date 2017-11-22 Time   Rev Time 0.00
Received By pleduc Date 2017-11-22 Time 10:27 Sent To  
Notes
2017-11-22 10:33:153RD REVIEW.
  
 PREVIOUS PROVISO COMMENTS ARE RE-POSTED BELOW:
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE DOOR TO THE DRY STORAGE ROOM OPENS INTO THE PATH
 OF EGRESS. PER NFPA 101, CHAPTER 7, MEANS OF EGRESS,
 7.2.1.4.3 - DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 - DURING ITS SWING, ANY DOOR LEAF IN A
 MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF
 THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A
 PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND SHALL NOT
 PROJECT NOT MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN
 FULLY OPEN, UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE
 MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 THOUGH THE STORAGE ROOM IS NOT CONSTANTLY OCCUPIED, AN
 AUTOMATIC DOOR CLOSER SHALL BE INSTALLED TO ENSURE THIS
 DOOR REMIANS CLOSED AT ALL TIMES AND WILL NOT BLOCK THE
 PATH OF TRAVEL TO THE EXIT DOOR.
  
 PLEASE ENSURE A DOOR CLOSER IS INSTALLED.
  
  
 2) THE PROPOSED PROJECT SHALL COMPLY WITH NFPA 101,
 CHAPTER 36, (NOT CHAPTER 10)
  
  
  
 3) THE EXISTING HOOD AND SUPPRESSION SYSTEM SHALL
 COMPLY WITH NFPA 96 AND HAVE A CURRENT SERVICE TAG.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-09-29 Cont ID  
Sent By pleduc Date 2017-09-29 Time   Rev Time 0.00
Received By pleduc Date 2017-09-29 Time 11:42 Sent To  
Notes
2017-09-29 12:39:39THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE DOOR TO THE DRY STORAGE ROOM OPENS INTO THE PATH
 OF EGRESS. PER NFPA 101, CHAPTER 7, MEANS OF EGRESS,
 7.2.1.4.3 - DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 - DURING ITS SWING, ANY DOOR LEAF IN A
 MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF
 THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A
 PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND SHALL NOT
 PROJECT NOT MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN
 FULLY OPEN, UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE
 MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 THOUGH THE STORAGE ROOM IS NOT CONSTANTLY OCCUPIED, AN
 AUTOMATIC DOOR CLOSER SHALL BE INSTALLED TO ENSURE THIS
 DOOR REMIANS CLOSED AT ALL TIMES AND WILL NOT BLOCK THE
 PATH OF TRAVEL TO THE EXIT DOOR.
  
 PLEASE ENSURE A DOOR CLOSER IS INSTALLED.
  
  
 2) THE PROPOSED PROJECT SHALL COMPLY WITH NFPA 101,
 CHAPTER 36, (NOT CHAPTER 10)
  
  
  
 3) THE EXISTING HOOD AND SUPPRESSION SYSTEM SHALL
 COMPLY WITH NFPA 96 AND HAVE A CURRENT SERVICE TAG.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-07-24 Cont ID  
Sent By pleduc Date 2017-07-24 Time   Rev Time 0.00
Received By pleduc Date 2017-07-24 Time 12:30 Sent To  
Notes
2017-07-24 13:38:18THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE DOOR TO THE DRY STORAGE ROOM OPENS INTO THE PATH
 OF EGRESS. PER NFPA 101, CHAPTER 7, MEANS OF EGRESS,
 7.2.1.4.3 - DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 - DURING ITS SWING, ANY DOOR LEAF IN A
 MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF
 THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A
 PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND SHALL NOT
 PROJECT NOT MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN
 FULLY OPEN, UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE
 MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 THOUGH THE STORAGE ROOM IS NOT CONSTANTLY OCCUPIED, AN
 AUTOMATIC DOOR CLOSER SHALL BE INSTALLED TO ENSURE THIS
 DOOR REMIANS CLOSED AT ALL TIMES AND WILL NOT BLOCK THE
 PATH OF TRAVEL TO THE EXIT DOOR.
  
 PLEASE ENSURE A DOOR CLOSER IS INSTALLED.
  
  
 2) THE PROPOSED PROJECT SHALL COMPLY WITH NFPA 101,
 CHAPTER 36, (NOT CHAPTER 10)
  
  
  
 3) THE EXISTING HOOD AND SUPPRESSION SYSTEM SHALL
 COMPLY WITH NFPA 96 AND HAVE A CURRENT SERVICE TAG.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-12-10 Cont ID  
Sent By gjohnson Date 2018-12-10 Time 11:39 Rev Time 0.00
Received By gjohnson Date 2018-12-10 Time 11:39 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2017-10-03 Cont ID  
Sent By gjohnson Date 2017-10-03 Time 17:37 Rev Time 0.00
Received By gjohnson Date 2017-10-03 Time 17:37 Sent To  
Notes
2017-10-03 17:38:30GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-01-31 Cont ID  
Sent By cpuell Date 2018-01-31 Time 09:37 Rev Time 0.00
Received By cpuell Date 2018-01-18 Time 17:09 Sent To  
Notes
2018-01-31 08:48:21TO LAURA MERCHANT FOR PROCESSING
2018-01-22 17:12:11B17

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-12-14 Cont ID  
Sent By jpearson Date 2017-12-14 Time 15:50 Rev Time 0.00
Received By cpuell Date 2017-11-16 Time 10:37 Sent To  
Notes
2017-11-28 09:06:5311/28 TO ANA APONTE DESK
  
  
2017-11-21 10:38:00B19

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-03 Cont ID  
Sent By gjohnson Date 2017-10-03 Time 17:30 Rev Time 0.00
Received By gjohnson Date 2017-09-26 Time 15:24 Sent To  
Notes
2017-09-27 15:25:32B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-07-28 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-20 Time 13:46 Sent To  
Notes
2017-07-21 13:46:29B17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-07-27 Cont ID  
Sent By jwitmer Date 2017-07-27 Time 16:47 Rev Time 0.00
Received By jwitmer Date 2017-07-27 Time 16:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-01-25 Cont ID  
Sent By ccole Date 2018-01-25 Time 14:33 Rev Time 0.00
Received By ccole Date 2018-01-25 Time 14:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-11-22 Cont ID  
Sent By ccole Date 2017-11-22 Time 15:35 Rev Time 0.00
Received By ccole Date 2017-11-22 Time 15:14 Sent To  
Notes
2017-11-22 15:59:313RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17070822
 11/22/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE NEW COMBUSTION CALCULATIONS DO NOT APPEAR TO BE
 IN COMPLIANCE WITH ANY OF THE METHODS SPECIFIED UNDER
 SECTION 304 FBC-14 FUEL GAS. IF THE INTENT IS PROVIDE
 THE AIR MECHANICALLY, THE REQUIRED RATE IS CALCULATED
 AT 0.35 CFM PER 1,000 BTUH PER SECTION 304.9.
  
 2) THE NEW OUTSIDE AIR INLET IS NOT IN COMPLIANCE WITH
 SECTION 401.4 WHICH REQUIRES A 10' CLEARANCE TO THE
 ALLEY.
  
 3) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR KITCHEN
 EXHAUST HOODS AND FIRE SUPPRESSION SYSTEMS- SECTION
 107.2.1 WPB AMENDMENTS TO THE FBC. PLEASE PROVIDE AN
 AIR BALANCE CALCULATION UNDER THIS MAIN PERMIT WHICH
 TAKES INTO ACCOUNT THE KITCHEN EXHAUST HOOD RATE,
  
 4) ADVISORY: PLEASE SEE SECTION 508.1.1 WHICH REQUIRES
 THE TEMPERATURE DIFFERENTIAL BETWEEN THE MAKEUP AIR AND
 THE AIR IN THE CONDITIONED SPACE NOT TO EXCEED 10
 DEGREES F.
  
 5) THE ADDRESS ON THE PLANS DOES NOT MATCH THE ADRESS
 ON THE PERMIT APPLICATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-10-02 Cont ID  
Sent By ccole Date 2017-10-02 Time 09:58 Rev Time 0.00
Received By ccole Date 2017-10-02 Time 07:33 Sent To  
Notes
2017-10-02 10:24:291ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070822
 10/2/2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED CUT SHEET FOR THE GRIDDLE INDICATES
 90,000 BTUH FOR THE 36" UNIT, HOWEVER THE SCHEDULE ON
 SHEET ME-1 INDICATES 30,000 BTUH- PLEASE CORRECT.
  
 2) 2ND REQUEST FOR COMBUSTION AIR CALCULATIONS:1)
 INDICATE HOW COMBUSTION AIR IS BEING PROVIDED TO THE
 NEW GAS COOKING APPLIANCES AND PROVIDE CALCULATIONS-
 SECTION 304 FBC-14 FUEL GAS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-27 Cont ID  
Sent By ccole Date 2017-07-27 Time 15:37 Rev Time 0.00
Received By ccole Date 2017-07-27 Time 15:37 Sent To  
Notes
2017-07-27 15:38:231ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070822
 7/27/17
  
 1) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED TO THE
 NEW GAS COOKING APPLIANCES AND PROVIDE CALCULATIONS-
 SECTION 304 FBC-14 FUEL GAS.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS (CUT SHEETS)
 FOR THE NEW COOKING APPLIANCES- SECTION 623.1 FBC-14
 FUEL GAS.
  
 3) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR KITCHEN
 EXHAUST HOODS AND FIRE SUPPRESSION SYSTEMS- SECTION
 107.2.1 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-01-29 Cont ID  
Sent By gjohnson Date 2018-01-29 Time 11:35 Rev Time 0.00
Received By gjohnson Date 2018-01-29 Time 11:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-03 Cont ID  
Sent By gjohnson Date 2017-10-03 Time 17:29 Rev Time 0.00
Received By gjohnson Date 2017-10-03 Time 17:29 Sent To  
Notes
2017-10-03 17:29:57PROVISO:
 1. NEW MOP SINK SHALL BE CONNECTED TO GREASE
 INTERCEPTOR
 PER FBC PL 1003.3.1
 2. PROVIDE A REVISED SIZING CALCULATION FOR GREASE
 INCEPTOR INCLUDING MOP SINK TO BE APPROVED BY BUILDING
 DEPT. BEFORE ROUGH INSPECTION.
 PER WPB AMEND TO FBC 107.2.1
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-25 Cont ID  
Sent By gjohnson Date 2017-07-25 Time 08:55 Rev Time 0.00
Received By gjohnson Date 2017-07-25 Time 07:23 Sent To  
Notes
2017-07-25 10:26:461ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT A-6 DETAIL #1 THE HEIGHT OF THE GRAB BAR SHALL
 BE MEASURED TO THE TOP OF THE GRIPPING SURFACE. PER FBC
 ACC 609.4
  
 2. SHOW COMPLIANCE WITHE FBC ACC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 3. THE NEW ADA BATHROOM-DOES NOT COMPLY WITH THE
 CLEARANCE FOR THE TOILET, THE MIN OVERALL WIDTH SHOULD
 BE A MIN OF 7' TO PROVIDE CLEARANCE FOR THE LAVATORY
 AND THE TOILET. PER FBC ACC 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
 604.3.2 OVERLAP.
 THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE
 PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB
 BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT
 HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE
 AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE
 TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL
 BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
  
 4. SHT. A-2 SHOWS EXWH IN A DIFFERENT LOCATION THAN SHT
 P-1 PLEASE CLARIFY. WPB AMEND TO FBC 107.2.1
  
 5. ON SHT A-2 AND P-1 SHOWS EXISTING FIXTURES IN NEW
 ADA BATHROOM. PLEASE CLARIFY. WPB AMEND TO FBC 107.2.1
  
 6. ALL FIXTURES IN KIT SHALL CONNECT THROUGH GREASE
 INTERCEPTOR PLEASE PROVIDE GREASE CALCULATIONS TO
 INCLUDE 3 COMP SINK HAND SINK FLOOR DRAIN AND MOPSINK.
 PER FBC PL 1003.3.1
  
 7. SHOW EXISTING HAND SINK IN KIT ON RISER. PER WPB
 AMEND TO FBC 107.2.1
  
 8. LAVATORY IN BATHROOM SHALL HAVE TEMPERED WATER SHALL
 BE DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES
 LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR
 CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL
 BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3. PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2019-01-16 Cont ID  
Sent By gjohnson Date 2019-01-16 Time 16:16 Rev Time 0.00
Received By gjohnson Date 2019-01-16 Time 16:16 Sent To  
Notes
2019-01-16 16:18:22PROVISO:
  
 PROVIDE A REVISED SIZING CALCULATION FOR GREASE
 INCEPTOR INCLUDING MOP SINK 3 SOMP SINK AND FLOOR DRAIN
 TO BE APPROVED BY BUILDING DEPT. BEFORE ROUGH
 INSPECTION.
 PER WPB AMEND TO FBC 107.2.1
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-01-31 Cont ID  
Sent By AA Date 2018-01-31 Time 08:47 Rev Time 0.00
Received By aaponte Date   Time   Sent To  
Notes
2018-01-31 08:47:37PROVISO: STOREFRONT GLASS SHALL NOT BE DARK TINTED.

Review Stop Z ZONING
Rev No 1 Status F Date 2017-12-14 Cont ID  
Sent By cpuell Date 2017-12-14 Time 15:50 Rev Time 0.00
Received By cpuell Date 2017-12-07 Time 15:01 Sent To  
Notes
2017-12-07 15:04:371. STOREFRONT GLASS CANNOT BE TINTED.
 2. AWNING REQUIRES A SEPARATE PERMIT.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.