Plan Review Details - Permit 17070822
| Plan Review Stops For Permit 17070822 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2018-01-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-01-26 |
Time |
06:30 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-01-26 |
Time |
05:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2017-11-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-11-27 |
Time |
18:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-11-27 |
Time |
18:07 |
Sent To |
|
|
| Notes |
| 2017-11-27 18:11:21 | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17070822 | | | ADD: 124 N. DIXIE HWY. | | | CONT: PAN AMERICAN ENGINEERING | | | TEL: 561-254-4858 | | | E-MAIL: ??????????? PLEASE PROVIDE, WE COMMUNICATE WITH | | | E-MAIL. | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | COMMENTS FROM 2ND REVIEW NOT ADDRESSED | | | DATE: 11/27/17 | | | ACTION: DENIED | | | | | | 1-5) COMPLIED. | | | | | | 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) | | | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. | | | | | | 6) SUBMITTED NOA 16-0421.10 PGT SE-3550 OUTSWING DOOR & | | | NOA 16-0505.04 PGT SS-3500 STOREFRONT SYSTEM, THE | | | CONTRACTOR NOR THE DESIGNER OF RECORD HAS NOT | | | IDENTIFIED ELEMENTS IN THE ASSEMBLY. | | | IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE | | | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF | | | RECORD AND BEFORE SUBMISSION TO THE BUILDING | | | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE | | | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, | | | MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND | | | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B | | | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE | | | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS | | | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE | | | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED | | | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. | | | | | | 7)SEMI ?COMPLIED SEE COMMENT ABOVE. | | | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS | | | | | | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ***NEW COMMENT*** | | | THE PRODUCT APPROVALS SUBMITTED INCLUDE DRAWING SHEETS | | | WHICH DID NOT PRINT PROPERLY. FBC 107, PROVIDE A | | | COMPLETE LEGIBLE FULL SIZE PRODUCT APPROVAL INDICATING | | | METHOD OF INSTALLATION AS WELL AS COMPONENTS SUCH AS | | | IMPACT BAR, ADA THRESHOLD. THE PRODUCT APPROVAL | | | CONTAINS MANY DIFFERENT INSTALLATION OPTIONS. APPLICANT | | | IS TO INDICATE WHICH IS PROPOSED. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-10-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-10-01 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-10-01 |
Time |
15:58 |
Sent To |
|
|
| Notes |
| 2017-10-01 16:21:37 | 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17070822 | | | ADD: 124 N. DIXIE HWY. | | | CONT: PAN AMERICAN ENGINEERING | | | TEL: 561-254-4858 | | | E-MAIL: ??????????? PLEASE PROVIDE, WE COMMUNICATE WITH | | | E-MAIL. | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: SUN. OCT. 01/ 2017 | | | ACTION: DENIED | | | | | | 1-5) COMPLIED. | | | | | | 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) | | | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. | | | | | | 6) SUBMITTED NOA 16-0421.10 PGT SE-3550 OUTSWING DOOR & | | | NOA 16-0505.04 PGT SS-3500 STOREFRONT SYSTEM, THE | | | CONTRACTOR NOR THE DESIGNER OF RECORD HAS NOT | | | IDENTIFIED ELEMENTS IN THE ASSEMBLY. | | | IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE | | | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF | | | RECORD AND BEFORE SUBMISSION TO THE BUILDING | | | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE | | | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, | | | MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND | | | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B | | | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE | | | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS | | | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE | | | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED | | | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. | | | | | | 7)SEMI ?COMPLIED SEE COMMENT ABOVE. | | | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS | | | | | | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-07-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-07-28 |
Time |
07:01 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-07-27 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2017-07-28 07:01:04 | 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17070822 | | | ADD: 124 N. DIXIE HWY. | | | CONT: PAN AMERICAN ENGINEERING | | | TEL: 561-254-4858 | | | E-MAIL: ??????????? PLEASE PROVIDE, WE COMMUNICATE WITH | | | E-MAIL. | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: FRI. JULY 28/ 2017 | | | ACTION: DENIED | | | | | | 1) SHEETS A-1 & A-3 BOTH INDICATE THIS TO BE A | | | MERCANTILE OCCUPANCY. DELI OR FOOD ESTABLISHMENTS WITH | | | OCCUPANT LOADS LESS THAN 50 ARE CLASSIFIED AS A | | | BUSINESS OCCUPANCY. 2014 FBC-B 303.1.1 SMALL BUILDINGS | | | AND TENANT SPACES. A BUILDING OR TENANT SPACE USED FOR | | | ASSEMBLY PURPOSES WITH AN OCCUPANT LOAD OF LESS THAN 50 | | | PERSONS SHALL BE CLASSIFIED AS GROUP B OCCUPANCY. | | | | | | 2)THE COVERSHEET A-1 INDICATES A NEW ADA TOILET AT 50 | | | SQ. FT. SHEET A-2 SHOWS A MEASUREMENT BACK WALL AT 5 | | | FOOT 10 INCHES (EXISTING). IF THE RESTROOM IS NEW THEN | | | THE COMPLIANCE WITH 2014 EXISTING BUILDING CODE LEVEL | | | II 701.3 COMPLIANCE IS REQUIRED. ALL NEW CONSTRUCTION | | | ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY | | | WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, | | | BUILDING. 2014 FBC-ACCESSIBILITY: | | | 604.3.1 SIZE. | | | 604.3.2 OVERLAP. | | | PLEASE NOTE THERE IS EVEN A NOTE FOR THE CLEAR FLOOR | | | SPACE AND REQUIRED OVERLAP? THE PERMIT APPLICATION | | | INDICATES A NEW ADA RESTROOM. IF THE RESTROOM FIXTURES | | | WERE TO BE RECONFIGURED AGAINST THE 8 FOOT WALL AND THE | | | WATER CLOSET WERE INSTALLED FURTHEST FROM THE DOORWAY | | | CLEARANCES COULD BE MET. | | | | | | 3) NEW ADA RESTROOM PLEASE SHOW COMPLIANCE FOR THE | | | STRUCTURAL STRENGTH OF THE GRAB BARS, 2014 | | | ACCESSIBILITY CODE, FBC SECTION 609.8. | | | | | | 4) THE PLANS SHOW ON SHEET A-2 A ORDER AND PICK-UP | | | COUNTER, BUT NO HEIGHTS ARE GIVEN, PLEASE SHOW | | | COMPLIANCE WITH : | | | 904.3.2 COUNTER. THE COUNTER SURFACE HEIGHT SHALL BE 38 | | | INCHES (965 MM) MAXIMUM ABOVE THE FINISH FLOOR OR | | | GROUND. | | | 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND | | | SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2. | | | THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND | | | THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP. | | | | | | 5) SHEET A-2 ALSO SHOWS 10 SEATS FOR DINING, PLEASE | | | SHOW COMPLIANCE WITH: | | | 5) 902.1 .DINING SURFACES AND WORK SURFACES SHALL | | | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. | | | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, | | | TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK | | | SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, | | | STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER | | | TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON | | | COUNTERS, AND WHERE COVERED BY THE ABA SCOPING | | | PROVISIONS, EMPLOYEE WORK STATIONS. | | | | | | 5A)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR | | | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD | | | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | | | | 5B)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND | | | WORK SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND | | | 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR | | | GROUND. | | | | | | ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. | | | MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL | | | COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL | | | EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED | | | LATCH SIDE OR HINGE SIDE CLEARANCE. | | | | | | 6) SUBMITTED NOA 12-0731.06 WINDOW WALL SYSTEM, THE | | | CONTRACTOR HAS NOT IDENTIFIED ELEMENTS IN THE ASSEMBLY. | | | IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE | | | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF | | | RECORD AND BEFORE SUBMISSION TO THE BUILDING | | | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE | | | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, | | | MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND | | | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B | | | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE | | | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S | | | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE | | | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED | | | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. | | | | | | 7) PLEASE NOTE THE NOA 12-0731.06 WINDOW WALL SYSTEM | | | DOES NOT INCLUDE THE DOOR STATED IN THE TECHNICAL | | | SHEETS. 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS | | | | | | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2018-01-23 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-01-23 |
Time |
07:32 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-01-23 |
Time |
07:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2017-11-28 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-11-28 |
Time |
07:42 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-11-28 |
Time |
07:42 |
Sent To |
I |
|
| Notes |
| 2017-11-28 07:42:00 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | 3RD REVIEW. ITEMS NOT ADDRESSED SATISFACTORILY LISTED | | | BELOW WITH ADDITIONAL COMMENTS IN PARENTHESES: | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE OF WORK | | | AND VALUE. IT APPEARS THE VALUE LISTED ON THE PERMIT | | | APPLICATION IS LOW. FBC 109.3 (HAVE NOT COMPLIED. THIS | | | SHOULD INCLUDE VALUE OF ALL EQUIPMENT AND LABOR FOR A | | | COMPLETE JOB.) | | | 2. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE ON | | | BUILDING. PER THE RISER DIAGRAM, THE SERVICE WIRE HAS A | | | CAPACITY OF 400 AMPS. PROVIDE LOAD CALCULATION TO | | | CONFIRM THE CAPACITY IS ADEQUATE. NEC 215.2, 220; FBC | | | 107.2.1 (NOTE ON PLAN STATES THAT THE REVISED RISER IS | | | THE CORRECTION TO THIS COMMENT, WHICH IS NOT ACCURATE. | | | A LOAD CALCULATION IS REQUIRED. PROVIDE AS PREVIOUSLY | | | REQUESTED.) | | | 3. COMPLIED. | | | 4. PROVIDE DETAILS OF THE METHOD OF SHUTDOWN FOR THE | | | ELECTRICAL EQUIPMENT LOCATED UNDER THE HOOD PER NFPA | | | 96. NFPA 96, SECTION 10.4.1, FBC 107.2.1 (HAVE NOT | | | COMPLIED. PROVIDE AS PREVIOUSLY REQUESTED.) | | | 5. COMPLIED. | | | 6. COMPLIED. | | | 7. COMPLIED. | | | 8. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED | | | FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE | | | CORRECTION. NEC 700.12(F) (A NOTE WAS PROVIDED, | | | HOWEVER, THE LIGHTING PLAN STILL SHOWS THE CIRCUITRY | | | INCORRECT. PROVIDE CORRECTION ON PLAN TO MATCH NOTE.) | | | 9. COMPLIED. | | | 10. COMPLIED. | | | 11. COMPLIED. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2017-10-03 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-10-03 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-10-03 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2017-10-03 10:34:15 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | 2ND REVIEW. ITEMS NOT ADDRESSED SATISFACTORILY LISTED | | | BELOW: | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE OF WORK | | | AND VALUE. IT APPEARS THE VALUE LISTED ON THE PERMIT | | | APPLICATION IS LOW. FBC 109.3 | | | 2. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE ON | | | BUILDING. PER THE RISER DIAGRAM, THE SERVICE WIRE HAS A | | | CAPACITY OF 400 AMPS. PROVIDE LOAD CALCULATION TO | | | CONFIRM THE CAPACITY IS ADEQUATE. NEC 215.2, 220; FBC | | | 107.2.1 | | | 3. COMPLIED. | | | 4. PROVIDE DETAILS OF THE METHOD OF SHUTDOWN FOR THE | | | ELECTRICAL EQUIPMENT LOCATED UNDER THE HOOD PER NFPA | | | 96. NFPA 96, SECTION 10.4.1, FBC 107.2.1 | | | 5. PROVIDE GRAPH OF INTERIOR LIGHTING POWER ALLOWANCES | | | PER THE FBC ENERGY CODE IN RELATION TO THE CONNECTED | | | INTERIOR LIGHTING PROPOSED TO COMPLY WITH CODE. FBC | | | C405.5 | | | 6. COMPLIED. | | | 7. COMPLIED. | | | 8. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED | | | FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE | | | CORRECTION. NEC 700.12(F) | | | 9. COMPLIED. | | | 10. PROVIDE SHOW WINDOW OUTLET. NEC 210.62 (SHOW WINDOW | | | IS PROVIDED, BUT IT IS ON THE SAME CIRCUIT AS THE SIGN, | | | WHICH IS A CODE VIOLATION. SIGN MUST BE ON A DEDICATED | | | CIRCUIUT. NEC 600.5(A). ) | | | 11. COMPLIED. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-07-26 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-07-26 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-07-26 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2017-07-26 10:09:20 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE OF WORK | | | AND VALUE. IT APPEARS THE VALUE LISTED ON THE PERMIT | | | APPLICATION IS LOW. FBC 109.3 | | | 2. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE ON | | | BUILDING. PER THE RISER DIAGRAM, THE SERVICE WIRE HAS A | | | CAPACITY OF 400 AMPS. PROVIDE LOAD CALCULATION TO | | | CONFIRM THE CAPACITY IS ADEQUATE. NEC 215.2, 220; FBC | | | 107.2.1 | | | 3. RISER DIAGRAM SHOWS THE WIRE TO UNIT 332 SIZED AS | | | 1/0, WHICH HAS A CAPACITY OF 150 AMPS. THE CURRENT 175 | | | AMP FUSES EXCEED THIS CAPACITY. PROVIDE CORRECTION. NEC | | | 215.2, 310.15(B)(16) | | | 4. PROVIDE DETAILS OF THE METHOD OF SHUTDOWN FOR THE | | | ELECTRICAL EQUIPMENT LOCATED UNDER THE HOOD PER NFPA | | | 96. NFPA 96, SECTION 10.4.1, FBC 107.2.1 | | | 5. PROVIDE GRAPH OF INTERIOR LIGHTING POWER ALLOWANCES | | | PER THE FBC ENERGY CODE IN RELATION TO THE CONNECTED | | | INTERIOR LIGHTING PROPOSED TO COMPLY WITH CODE. FBC | | | C405.5 | | | 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS FOR | | | INTERIOR LIGHTING STIPULATED IN THE FBC ENERGY CODE. | | | FBC C405.2.2, 405.2.2.2 | | | 7. PROVIDE CONTROL FOR THE EXHAUST FAN ON CIRCUIT C-25. | | | CURRENTLY, THIS APPEARS TO BE WIRED FOR CONTINUOUS | | | OPERATION. FBC MECHANICAL 405.1; FBC 107.2.1 | | | 8. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED | | | FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE | | | CORRECTION. NEC 700.12(F) | | | 9. ALL OUTLETS IN KITCHEN ARE REQUIRED TO BE GFCI | | | PROTECTED. PROVIDE CORRECTION. NEC 210.8(B)(2) | | | 10. PROVIDE SHOW WINDOW OUTLET. NEC 210.62 | | | 11. PROVIDE AUTOMATIC CONTROL OF SIGN AND SHOW WINDOW | | | CIRCUITS PER ENERGY CODE. FBC C405.2.4 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2017-11-22 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-11-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-11-22 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2017-11-22 10:33:15 | 3RD REVIEW. | | | | | | PREVIOUS PROVISO COMMENTS ARE RE-POSTED BELOW: | | | | | | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THE DOOR TO THE DRY STORAGE ROOM OPENS INTO THE PATH | | | OF EGRESS. PER NFPA 101, CHAPTER 7, MEANS OF EGRESS, | | | 7.2.1.4.3 - DOOR LEAF ENCROACHMENT | | | 7.2.1.4.3.1 - DURING ITS SWING, ANY DOOR LEAF IN A | | | MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF | | | THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A | | | PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND SHALL NOT | | | PROJECT NOT MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF | | | AN AISLE, A CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN | | | FULLY OPEN, UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE | | | MET: | | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | | EXISTING BUILDING. | | | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS | | | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED | | | WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY | | | OPEN. | | | | | | THOUGH THE STORAGE ROOM IS NOT CONSTANTLY OCCUPIED, AN | | | AUTOMATIC DOOR CLOSER SHALL BE INSTALLED TO ENSURE THIS | | | DOOR REMIANS CLOSED AT ALL TIMES AND WILL NOT BLOCK THE | | | PATH OF TRAVEL TO THE EXIT DOOR. | | | | | | PLEASE ENSURE A DOOR CLOSER IS INSTALLED. | | | | | | | | | 2) THE PROPOSED PROJECT SHALL COMPLY WITH NFPA 101, | | | CHAPTER 36, (NOT CHAPTER 10) | | | | | | | | | | | | 3) THE EXISTING HOOD AND SUPPRESSION SYSTEM SHALL | | | COMPLY WITH NFPA 96 AND HAVE A CURRENT SERVICE TAG. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-09-29 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-09-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-09-29 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2017-09-29 12:39:39 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THE DOOR TO THE DRY STORAGE ROOM OPENS INTO THE PATH | | | OF EGRESS. PER NFPA 101, CHAPTER 7, MEANS OF EGRESS, | | | 7.2.1.4.3 - DOOR LEAF ENCROACHMENT | | | 7.2.1.4.3.1 - DURING ITS SWING, ANY DOOR LEAF IN A | | | MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF | | | THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A | | | PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND SHALL NOT | | | PROJECT NOT MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF | | | AN AISLE, A CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN | | | FULLY OPEN, UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE | | | MET: | | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | | EXISTING BUILDING. | | | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS | | | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED | | | WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY | | | OPEN. | | | | | | THOUGH THE STORAGE ROOM IS NOT CONSTANTLY OCCUPIED, AN | | | AUTOMATIC DOOR CLOSER SHALL BE INSTALLED TO ENSURE THIS | | | DOOR REMIANS CLOSED AT ALL TIMES AND WILL NOT BLOCK THE | | | PATH OF TRAVEL TO THE EXIT DOOR. | | | | | | PLEASE ENSURE A DOOR CLOSER IS INSTALLED. | | | | | | | | | 2) THE PROPOSED PROJECT SHALL COMPLY WITH NFPA 101, | | | CHAPTER 36, (NOT CHAPTER 10) | | | | | | | | | | | | 3) THE EXISTING HOOD AND SUPPRESSION SYSTEM SHALL | | | COMPLY WITH NFPA 96 AND HAVE A CURRENT SERVICE TAG. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2017-07-24 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-07-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-07-24 |
Time |
12:30 |
Sent To |
|
|
| Notes |
| 2017-07-24 13:38:18 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THE DOOR TO THE DRY STORAGE ROOM OPENS INTO THE PATH | | | OF EGRESS. PER NFPA 101, CHAPTER 7, MEANS OF EGRESS, | | | 7.2.1.4.3 - DOOR LEAF ENCROACHMENT | | | 7.2.1.4.3.1 - DURING ITS SWING, ANY DOOR LEAF IN A | | | MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF | | | THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A | | | PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND SHALL NOT | | | PROJECT NOT MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF | | | AN AISLE, A CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN | | | FULLY OPEN, UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE | | | MET: | | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | | EXISTING BUILDING. | | | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS | | | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED | | | WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY | | | OPEN. | | | | | | THOUGH THE STORAGE ROOM IS NOT CONSTANTLY OCCUPIED, AN | | | AUTOMATIC DOOR CLOSER SHALL BE INSTALLED TO ENSURE THIS | | | DOOR REMIANS CLOSED AT ALL TIMES AND WILL NOT BLOCK THE | | | PATH OF TRAVEL TO THE EXIT DOOR. | | | | | | PLEASE ENSURE A DOOR CLOSER IS INSTALLED. | | | | | | | | | 2) THE PROPOSED PROJECT SHALL COMPLY WITH NFPA 101, | | | CHAPTER 36, (NOT CHAPTER 10) | | | | | | | | | | | | 3) THE EXISTING HOOD AND SUPPRESSION SYSTEM SHALL | | | COMPLY WITH NFPA 96 AND HAVE A CURRENT SERVICE TAG. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-12-10 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-12-10 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-12-10 |
Time |
11:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2017-10-03 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-03 |
Time |
17:37 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-03 |
Time |
17:37 |
Sent To |
|
|
| Notes |
| 2017-10-03 17:38:30 | GAS PLAN REVIEW | | | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | | PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT | | | SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE | | | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | | FBC-R, SEC. G2404.3. | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | | GAS SEC. 301.3. | | | | | | A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2018-01-31 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-01-31 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-01-18 |
Time |
17:09 |
Sent To |
|
|
| Notes |
| 2018-01-31 08:48:21 | TO LAURA MERCHANT FOR PROCESSING | | 2018-01-22 17:12:11 | B17 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-12-14 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-12-14 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-11-16 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2017-11-28 09:06:53 | 11/28 TO ANA APONTE DESK | | | | | | | | 2017-11-21 10:38:00 | B19 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-10-03 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-03 |
Time |
17:30 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-09-26 |
Time |
15:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-07-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-07-20 |
Time |
13:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2017-07-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-07-27 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-07-27 |
Time |
16:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2018-01-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-01-25 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-01-25 |
Time |
14:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2017-11-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-11-22 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-11-22 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2017-11-22 15:59:31 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #17070822 | | | 11/22/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE NEW COMBUSTION CALCULATIONS DO NOT APPEAR TO BE | | | IN COMPLIANCE WITH ANY OF THE METHODS SPECIFIED UNDER | | | SECTION 304 FBC-14 FUEL GAS. IF THE INTENT IS PROVIDE | | | THE AIR MECHANICALLY, THE REQUIRED RATE IS CALCULATED | | | AT 0.35 CFM PER 1,000 BTUH PER SECTION 304.9. | | | | | | 2) THE NEW OUTSIDE AIR INLET IS NOT IN COMPLIANCE WITH | | | SECTION 401.4 WHICH REQUIRES A 10' CLEARANCE TO THE | | | ALLEY. | | | | | | 3) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR KITCHEN | | | EXHAUST HOODS AND FIRE SUPPRESSION SYSTEMS- SECTION | | | 107.2.1 WPB AMENDMENTS TO THE FBC. PLEASE PROVIDE AN | | | AIR BALANCE CALCULATION UNDER THIS MAIN PERMIT WHICH | | | TAKES INTO ACCOUNT THE KITCHEN EXHAUST HOOD RATE, | | | | | | 4) ADVISORY: PLEASE SEE SECTION 508.1.1 WHICH REQUIRES | | | THE TEMPERATURE DIFFERENTIAL BETWEEN THE MAKEUP AIR AND | | | THE AIR IN THE CONDITIONED SPACE NOT TO EXCEED 10 | | | DEGREES F. | | | | | | 5) THE ADDRESS ON THE PLANS DOES NOT MATCH THE ADRESS | | | ON THE PERMIT APPLICATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-10-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-10-02 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-10-02 |
Time |
07:33 |
Sent To |
|
|
| Notes |
| 2017-10-02 10:24:29 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17070822 | | | 10/2/2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SUBMITTED CUT SHEET FOR THE GRIDDLE INDICATES | | | 90,000 BTUH FOR THE 36" UNIT, HOWEVER THE SCHEDULE ON | | | SHEET ME-1 INDICATES 30,000 BTUH- PLEASE CORRECT. | | | | | | 2) 2ND REQUEST FOR COMBUSTION AIR CALCULATIONS:1) | | | INDICATE HOW COMBUSTION AIR IS BEING PROVIDED TO THE | | | NEW GAS COOKING APPLIANCES AND PROVIDE CALCULATIONS- | | | SECTION 304 FBC-14 FUEL GAS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-07-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-07-27 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-07-27 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2017-07-27 15:38:23 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17070822 | | | 7/27/17 | | | | | | 1) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED TO THE | | | NEW GAS COOKING APPLIANCES AND PROVIDE CALCULATIONS- | | | SECTION 304 FBC-14 FUEL GAS. | | | | | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS (CUT SHEETS) | | | FOR THE NEW COOKING APPLIANCES- SECTION 623.1 FBC-14 | | | FUEL GAS. | | | | | | 3) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR KITCHEN | | | EXHAUST HOODS AND FIRE SUPPRESSION SYSTEMS- SECTION | | | 107.2.1 WPB AMENDMENTS TO THE FBC. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2018-01-29 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-01-29 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-01-29 |
Time |
11:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2017-10-03 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-03 |
Time |
17:29 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-03 |
Time |
17:29 |
Sent To |
|
|
| Notes |
| 2017-10-03 17:29:57 | PROVISO: | | | 1. NEW MOP SINK SHALL BE CONNECTED TO GREASE | | | INTERCEPTOR | | | PER FBC PL 1003.3.1 | | | 2. PROVIDE A REVISED SIZING CALCULATION FOR GREASE | | | INCEPTOR INCLUDING MOP SINK TO BE APPROVED BY BUILDING | | | DEPT. BEFORE ROUGH INSPECTION. | | | PER WPB AMEND TO FBC 107.2.1 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-07-25 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-07-25 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-07-25 |
Time |
07:23 |
Sent To |
|
|
| Notes |
| 2017-07-25 10:26:46 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHT A-6 DETAIL #1 THE HEIGHT OF THE GRAB BAR SHALL | | | BE MEASURED TO THE TOP OF THE GRIPPING SURFACE. PER FBC | | | ACC 609.4 | | | | | | 2. SHOW COMPLIANCE WITHE FBC ACC 604.7 DISPENSERS. | | | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 | | | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO | | | THE CENTERLINE OF THE DISPENSER. | | | | | | 3. THE NEW ADA BATHROOM-DOES NOT COMPLY WITH THE | | | CLEARANCE FOR THE TOILET, THE MIN OVERALL WIDTH SHOULD | | | BE A MIN OF 7' TO PROVIDE CLEARANCE FOR THE LAVATORY | | | AND THE TOILET. PER FBC ACC 604.3.1 SIZE. | | | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES | | | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE | | | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED | | | PERPENDICULAR FROM THE REAR WALL. | | | 604.3.2 OVERLAP. | | | THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE | | | PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB | | | BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT | | | HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE | | | AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE | | | TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL | | | BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE. | | | | | | 4. SHT. A-2 SHOWS EXWH IN A DIFFERENT LOCATION THAN SHT | | | P-1 PLEASE CLARIFY. WPB AMEND TO FBC 107.2.1 | | | | | | 5. ON SHT A-2 AND P-1 SHOWS EXISTING FIXTURES IN NEW | | | ADA BATHROOM. PLEASE CLARIFY. WPB AMEND TO FBC 107.2.1 | | | | | | 6. ALL FIXTURES IN KIT SHALL CONNECT THROUGH GREASE | | | INTERCEPTOR PLEASE PROVIDE GREASE CALCULATIONS TO | | | INCLUDE 3 COMP SINK HAND SINK FLOOR DRAIN AND MOPSINK. | | | PER FBC PL 1003.3.1 | | | | | | 7. SHOW EXISTING HAND SINK IN KIT ON RISER. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 8. LAVATORY IN BATHROOM SHALL HAVE TEMPERED WATER SHALL | | | BE DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES | | | LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR | | | CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL | | | BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE | | | LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA | | | B125.3. PER FBC PL 416.5 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2019-01-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-01-16 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-01-16 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2019-01-16 16:18:22 | PROVISO: | | | | | | PROVIDE A REVISED SIZING CALCULATION FOR GREASE | | | INCEPTOR INCLUDING MOP SINK 3 SOMP SINK AND FLOOR DRAIN | | | TO BE APPROVED BY BUILDING DEPT. BEFORE ROUGH | | | INSPECTION. | | | PER WPB AMEND TO FBC 107.2.1 | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2018-01-31 |
|
|
Cont ID |
|
| Sent By |
AA |
Date |
2018-01-31 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2018-01-31 08:47:37 | PROVISO: STOREFRONT GLASS SHALL NOT BE DARK TINTED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2017-12-14 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-12-14 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-12-07 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2017-12-07 15:04:37 | 1. STOREFRONT GLASS CANNOT BE TINTED. | | | 2. AWNING REQUIRES A SEPARATE PERMIT. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|
|