Plan Review Details - Permit 17070801
Plan Review Stops For Permit 17070801
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-10-25 Cont ID  
Sent By rmcdouga Date 2017-10-25 Time 17:24 Rev Time 0.00
Received By rmcdouga Date 2017-10-25 Time 15:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-09-26 Cont ID  
Sent By rmcdouga Date 2017-09-26 Time 11:33 Rev Time 0.00
Received By rmcdouga Date 2017-09-26 Time 11:19 Sent To  
Notes
2017-09-26 11:34:29PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) (PREVIOUS COMMENT) THE PRODUCT APPROVAL THAT WAS
 SUBMITTED FOR THE BUILT UP ROOF (NOA NO.:14-1030.01)
 WILL REQUIRE ENHANCED FASTENING IN ORDER TO MEET THE
 UPLIFT PRESSURES FOR ROOF ZONES 2 AND 3. THE FASTENING
 OPTION THAT YOU INDICATED ON PAGE 15 OF THE NOA HAS A
 MAXIMUM DESIGN PRESSURE OF -52.5 PSF. THE REQUIRED
 UPLIFT PRESSURES FOR ZONE 2 IS -63.6 PSF AND FOR ZONE 3
 IS -95.7 PER SHEET S.3 OF THE APPROVED PLANS. SEE
 LIMITATION NUMBER 7 ON PAGE 31 AND SUBMIT TWO SETS OF
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING FOR THE PERIMETER AND CORNER AREAS OF THE
 ROOF. FBC - R301.2.1
  
 2) (PREVIOUS COMMENT) THE RAS 117 CALCULATIONS THAT
 WERE SUBMITTED ARE BASED ON NOA NO.13-1022.15 WHICH HAS
 BEEN SUPERCEDED BY NOA NO. 14-1030.01. THE SYSTEM AND
 FASTENING OPTION THAT YOU INDICATED ON THE PRODUCT
 APPROVAL THAT WAS SUBMITTED DOES NOT MATCH THE
 CALCULATIONS. PLEASE SUBMIT MATCHING DOCUMENTS. FBC
 107.2.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-22 Cont ID  
Sent By rmcdouga Date 2017-08-22 Time 16:06 Rev Time 0.00
Received By rmcdouga Date 2017-08-22 Time 15:22 Sent To  
Notes
2017-08-22 15:25:57PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) (PREVIOUS COMMENT) THE PRODUCT APPROVAL THAT WAS
 SUBMITTED FOR THE BUILT UP ROOF (NOA NO.:14-1030.01)
 WILL REQUIRE ENHANCED FASTENING IN ORDER TO MEET THE
 UPLIFT PRESSURES FOR ROOF ZONES 2 AND 3. THE FASTENING
 OPTION THAT YOU INDICATED ON PAGE 15 OF THE NOA HAS A
 MAXIMUM DESIGN PRESSURE OF -52.5 PSF. THE REQUIRED
 UPLIFT PRESSURES FOR ZONE 2 IS -63.6 PSF AND FOR ZONE 3
 IS -95.7 PER SHEET S.3 OF THE APPROVED PLANS. SEE
 LIMITATION NUMBER 7 ON PAGE 31 AND SUBMIT TWO SETS OF
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING FOR THE PERIMETER AND CORNER AREAS OF THE
 ROOF. FBC - R301.2.1
  
 2) (NEW COMMENT) THE RAS 117 CALCULATIONS THAT WERE
 SUBMITTED ARE BASED ON NOA NO.13-1022.15 WHICH HAS BEEN
 SUPERCEDED BY NOA NO. 14-1030.01. THE SYSTEM AND
 FASTENING OPTION THAT YOU INDICATED ON THE PRODUCT
 APPROVAL THAT WAS SUBMITTED DOES NOT MATCH THE
 CALCULATIONS. PLEASE SUBMIT MATCHING DOCUMENTS. FBC
 107.2.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-21 Cont ID  
Sent By rmcdouga Date 2017-07-21 Time 17:44 Rev Time 0.00
Received By rmcdouga Date 2017-07-21 Time 17:44 Sent To  
Notes
2017-07-21 18:03:58PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 BUILT UP ROOF (NOA NO.:14-1030.01) WILL REQUIRE
 ENHANCED FASTENING IN ORDER TO MEET THE UPLIFT
 PRESSURES FOR ROOF ZONES 2 AND 3. THE FASTENING OPTION
 THAT YOU INDICATED ON PAGE 15 OF THE NOA HAS A MAXIMUM
 DESIGN PRESSURE OF -52.5 PSF. THE REQUIRED UPLIFT
 PRESSURES FOR ZONE 2 IS -63.6 PSF AND FOR ZONE 3 IS
 -95.7 PER SHEET S.3 OF THE APPROVED PLANS. SEE
 LIMITATION NUMBER 7 ON PAGE 31 AND SUBMIT TWO SETS OF
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING FOR THE PERIMETER AND CORNER AREAS OF THE
 ROOF. FBC - R301.2.1
  
 NOTE: THE LEDGER FASTENING DETAIL ON THE ROOF FRAMING
 PLAN IS APPROVED.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-10-25 Cont ID  
Sent By rmcdouga Date 2017-10-25 Time 17:25 Rev Time 0.00
Received By rmcdouga Date 2017-10-17 Time 14:44 Sent To  
Notes
2017-10-18 14:44:26RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-09-26 Cont ID  
Sent By rmcdouga Date 2017-09-26 Time 11:33 Rev Time 0.00
Received By rmcdouga Date 2017-09-15 Time 10:37 Sent To  
Notes
2017-09-18 10:37:39RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-22 Cont ID  
Sent By rmcdouga Date 2017-08-22 Time 16:06 Rev Time 0.00
Received By rmcdouga Date 2017-08-18 Time 10:40 Sent To  
Notes
2017-08-22 10:40:59RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-21 Cont ID  
Sent By rmcdouga Date 2017-07-21 Time 17:44 Rev Time 0.00
Received By rmcdouga Date 2017-07-20 Time 11:33 Sent To  
Notes
2017-07-21 11:33:14SUBMITTAL ROUTED TO RMCDOUGAL