Plan Review Details - Permit 17070744
Plan Review Stops For Permit 17070744
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-10 Cont ID  
Sent By jleahy Date 2017-08-10 Time 18:10 Rev Time 0.00
Received By jleahy Date 2017-08-10 Time 18:10 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-20 Cont ID  
Sent By jleahy Date 2017-07-20 Time 18:14 Rev Time 0.00
Received By jleahy Date 2017-07-20 Time 18:14 Sent To M
Notes
2017-07-20 18:19:21FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 NEED DISCONNECT AND GROUNDING ELECTRODE SYSTEM
 INSTALLED..
  
 225.30 NUMBER OF SUPPLIES
 A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR
 FEEDER ON THE LOAD SIDE OF A SERVICE DISCONNECTING
 MEANS SHALL BE
 SUPPLIED BY ONLY ONE FEEDER OR BRANCH CIRCUIT UNLESS
 PERMITTED IN
 225.30(A) THROUGH (E). FOR THE PURPOSE OF THIS SECTION,
 A MULTIWIRE
 BRANCH CIRCUIT SHALL BE CONSIDERED A SINGLE CIRCUIT.
 WHERE A BRANCH CIRCUIT OR FEEDER ORIGINATES IN THESE
 ADDITIONAL
 BUILDINGS OR OTHER STRUCTURES, ONLY ONE FEEDER OR
 BRANCH CIRCUIT
 SHALL BE PERMITTED TO SUPPLY POWER BACK TO THE ORIGINAL
 BUILDING
 OR STRUCTURE, UNLESS PERMITTED IN 225.30(A) THROUGH
 (E).
  
 225.31 DISCONNECTING MEANS
 MEANS SHALL BE PROVID ED FOR DISCONNECTING ALL
 UNGROUNDED CONDUCTORS
 THAT SUPPLY OR PASS THROUGH THE BUILDING OR STRUCTURE.
  
 250.32 BUILDINGS OR STRUCTURES SUPPLIED
 BY A FEEDER(S) OR BRANCH CIRCUIT(S)
 (A) GROUNDING ELECTRODE. BUILDING(S) OR STRUCTURE(S)
 SUPPLIED
 BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A
 GROUNDING ELECTRODE
 OR GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE
 WI TH
 PART III OF ARTICLE 250. THE GROUNDING ELECTRODE
 CONDUCTOR(S) SHALL
 BE CON NECTED IN ACCORDANCE WITH 250.32(B) OR (C).
 WHERE THERE
 IS NO EXISTING GROUNDING ELECTRODE, THE GROUNDING
 ELECTRODE(S)
 REQUIRED IN 250.50 SHALL BE INSTALLED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-11 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-08 Time 11:17 Sent To  
Notes
2017-08-09 11:18:01RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-07-25 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-19 Time 15:04 Sent To  
Notes
2017-07-20 15:05:12REVISION ROUTED TO ELEC<5K

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2017-08-29 Cont ID  
Sent By ccole Date 2017-08-29 Time 09:30 Rev Time 0.00
Received By ccole Date 2017-08-29 Time 09:30 Sent To  
Notes
2017-08-29 09:31:16CORRECTED PLANS RESUBMITTED UNDER PERMIT #17081130
 CCOLE- 8/29/17

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-11 Cont ID  
Sent By ccole Date 2017-08-11 Time 14:12 Rev Time 0.00
Received By ccole Date 2017-08-11 Time 14:11 Sent To  
Notes
2017-08-11 14:16:152ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17070744
 8/11/17
  
 COMMENTS FROM THE 1ST REVIEW STILL EXISTS- SEE BELOW.
  
 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17070744
 7/25/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN-
 SECTION 107.2.1 WPB AMENDMENTS TO THE FBC
  
 2) SUBMIT AN AHRI CERTIFICATE FOR THE NEW SYSTEM-
 SECTION R101.4.7 FBC-14 ENERGY CONSERVATION
  
 3) PROVIDE AC COOLING AND HEATING SIZING CALCULATIONS-
 SECTION R403.6.1
  
 4) REFER TO SECTION R101.4.5: CHANGE IN SPACE
 CONDITIONING.
 ANY NONCONDITIONED SPACE THAT IS ALTERED TO BECOME
 CONDITIONED SPACE SHALL BE REQUIRED TO BE BROUGHT INTO
 FULL COMPLIANCE WITH THIS CODE- SEE SECTION R101.5.1
 AND SUBMIT AN ENERGY COMPLIANCE FORM.
  
 5) PROVIDE DETAILS FOR INSTALLATION OF THE NEW AC PAD
 AND TIE DOWN OF THE CONDENSER- SECTIONS M1305.1.4.1 &
 M1401.4 FBC-14 RESIDENTIAL.
  
 6) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION M1411.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-25 Cont ID  
Sent By ccole Date 2017-07-25 Time 15:07 Rev Time 0.00
Received By ccole Date 2017-07-25 Time 15:07 Sent To  
Notes
2017-07-25 15:19:441ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17070744
 7/25/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN-
 SECTION 107.2.1 WPB AMENDMENTS TO THE FBC
  
 2) SUBMIT AN AHRI CERTIFICATE FOR THE NEW SYSTEM-
 SECTION R101.4.7 FBC-14 ENERGY CONSERVATION
  
 3) PROVIDE AC COOLING AND HEATING SIZING CALCULATIONS-
 SECTION R403.6.1
  
 4) REFER TO SECTION R101.4.5: CHANGE IN SPACE
 CONDITIONING.
 ANY NONCONDITIONED SPACE THAT IS ALTERED TO BECOME
 CONDITIONED SPACE SHALL BE REQUIRED TO BE BROUGHT INTO
 FULL COMPLIANCE WITH THIS CODE- SEE SECTION R101.5.1
 AND SUBMIT AN ENERGY COMPLIANCE FORM.
  
 5) PROVIDE DETAILS FOR INSTALLATION OF THE NEW AC PAD
 AND TIE DOWN OF THE CONDENSER- SECTIONS M1305.1.4.1 &
 M1401.4 FBC-14 RESIDENTIAL.
  
 6) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION M1411.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  