| 2017-07-26 15:10:36 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE COPY OF CONTRACT WITH SCOPE OF WORK AND |
| | VALUE LISTED. FBC 109.3 |
| | 2. NOTE 1 ON SHEET E-1 REFERENCES THE 2008 NEC. PROVIDE |
| | CORRECTION. FBC PREFACE. |
| | 3. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | 4. PROVIDE LIGHT FIXTURE SCHEDULE AND SYMBOL LEGEND. |
| | FBC 107.2.1, NEC 110.3 |
| | 5. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND |
| | PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE |
| | PERMITTED IN CLOTHES CLOSETS. PROVIDE CORRECTION. NEC |
| | 410.16(B), FBC RE4003.12 |
| | 6. LIGHTING IN BATHTUB OR SHOWER AREAS, AND EXTERIOR |
| | AREAS, SHALL BE SUITABLE FOR DAMP LOCATIONS. PROVIDE |
| | CORRECTION. NEC 410.10(D); FBC RE4003.11 |
| | 7. PROVIDE GFCI PROTECTION FOR OUTLET IN LAUNDRY WITHIN |
| | 6 FEET OF SINK. NEC 210.8; FBC RE3902.7 |
| | 8. PROVIDE GFCI OUTLETS TO CODE IN KITCHEN. NEC 210.8, |
| | 210.52; FBC RE3901.4, FBC 107.2.1 |
| | 9. ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH |
| | CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, |
| | HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI |
| | PROTECTION. PROVIDE COMPLIANCE. NEC 210.12; FBC |
| | RE3902.12 |
| | 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| | 11. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. CURRENTLY, BOTH PANELS SHOW THE SAME AMPERE |
| | LOAD, WHICH IS IMPOSSIBLE SINCE PANEL B IS FED FROM |
| | PANEL A. NEC 220; FBC RE3602.3 |
| | 12. PANEL A IS SHOWN AS A MAIN LUG ONLY PANEL IN THE |
| | PANEL SCHEDULE, AND DOES NOT SHOW A MAIN AHEAD OF THIS |
| | PANEL IN THE RISER DIAGRAM. IF THIS IS ACCURATE, THIS |
| | PANEL WOULD BE LIMITED TO A MAXIMUM OF SIX BREAKERS. |
| | PROVIDE CORRECTION AND/OR CLARIFICATION. FBC 107.2.1; |
| | NEC 230.71 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |