Plan Review Details - Permit 17070684
Plan Review Stops For Permit 17070684
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-25 Cont ID  
Sent By rmcdouga Date 2017-08-25 Time 13:26 Rev Time 0.00
Received By rmcdouga Date 2017-08-25 Time 10:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-02 Cont ID  
Sent By rmcdouga Date 2017-08-02 Time 14:46 Rev Time 0.00
Received By rmcdouga Date 2017-08-02 Time 13:46 Sent To  
Notes
2017-08-02 14:46:01PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE VALUATION FOR THE WORK THAT IS SHOWN ON THE
 PLANS IS LOW. SUBMIT A COPY OF THE CONTRACT AND
 ITEMIZED SCOPE OF WORK TO VERIFY VALUATION. FBC 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) INDICATE ON THE PLANS THAT THIS IS A LEVEL 3
 ALTERATION. FBC EXISTING BUILDING SECTION 505
  
 3) THIS STRUCTURE IS A SINGLE FAMILY DWELLING AND PER
 FBC SECTION 310.5 IS A GROUP R-3 OCCUPANCY TYPE. PLEASE
 REVISE SHEET A-000.
  
 4) BASED ON FBC TABLE 503, AN R-3 OCCUPANCY OF TYPE V-B
 CONSTRUCTION IS PERMITTED TO BE 3 STORIES IN HEIGHT AND
 UNLIMITED IN AREA. PLEASE REVISE SHEET A-000.
  
 5) SHOW COMPLIANCE WITH R314.3.1 WHEN ALTERATIONS,
 REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN
 ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN
 EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL
 BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR
 NEW DWELLINGS.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-21 Cont ID  
Sent By jpearson Date 2017-08-21 Time 15:40 Rev Time 0.00
Received By jpearson Date 2017-08-21 Time 15:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-26 Cont ID  
Sent By jpearson Date 2017-07-26 Time 14:30 Rev Time 0.00
Received By jpearson Date 2017-07-26 Time 14:30 Sent To  
Notes
2017-07-26 15:10:36CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE COPY OF CONTRACT WITH SCOPE OF WORK AND
 VALUE LISTED. FBC 109.3
 2. NOTE 1 ON SHEET E-1 REFERENCES THE 2008 NEC. PROVIDE
 CORRECTION. FBC PREFACE.
 3. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 4. PROVIDE LIGHT FIXTURE SCHEDULE AND SYMBOL LEGEND.
 FBC 107.2.1, NEC 110.3
 5. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS. PROVIDE CORRECTION. NEC
 410.16(B), FBC RE4003.12
 6. LIGHTING IN BATHTUB OR SHOWER AREAS, AND EXTERIOR
 AREAS, SHALL BE SUITABLE FOR DAMP LOCATIONS. PROVIDE
 CORRECTION. NEC 410.10(D); FBC RE4003.11
 7. PROVIDE GFCI PROTECTION FOR OUTLET IN LAUNDRY WITHIN
 6 FEET OF SINK. NEC 210.8; FBC RE3902.7
 8. PROVIDE GFCI OUTLETS TO CODE IN KITCHEN. NEC 210.8,
 210.52; FBC RE3901.4, FBC 107.2.1
 9. ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION. PROVIDE COMPLIANCE. NEC 210.12; FBC
 RE3902.12
 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
 11. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. CURRENTLY, BOTH PANELS SHOW THE SAME AMPERE
 LOAD, WHICH IS IMPOSSIBLE SINCE PANEL B IS FED FROM
 PANEL A. NEC 220; FBC RE3602.3
 12. PANEL A IS SHOWN AS A MAIN LUG ONLY PANEL IN THE
 PANEL SCHEDULE, AND DOES NOT SHOW A MAIN AHEAD OF THIS
 PANEL IN THE RISER DIAGRAM. IF THIS IS ACCURATE, THIS
 PANEL WOULD BE LIMITED TO A MAXIMUM OF SIX BREAKERS.
 PROVIDE CORRECTION AND/OR CLARIFICATION. FBC 107.2.1;
 NEC 230.71
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-25 Cont ID  
Sent By rmcdouga Date 2017-08-25 Time 13:26 Rev Time 0.00
Received By rmcdouga Date 2017-08-16 Time 09:34 Sent To  
Notes
2017-08-18 09:34:35R13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-02 Cont ID  
Sent By rmcdouga Date 2017-08-02 Time 14:58 Rev Time 0.00
Received By rmcdouga Date 2017-07-18 Time 12:59 Sent To  
Notes
2017-07-19 12:59:29R15

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-08-02 Cont ID  
Sent By rmcdouga Date 2017-08-02 Time 14:58 Rev Time 0.00
Received By rmcdouga Date 2017-08-02 Time 14:58 Sent To  
Notes
2017-08-02 15:00:42NO MECHANICAL WORK IS SHOWN ON THE PLANS. A SEPARATE
 PERMIT, APPLICATION AND REVIEW IS REQUIRED FOR THE
 MECHANICAL WORK.

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-23 Cont ID  
Sent By gjohnson Date 2017-08-23 Time 18:00 Rev Time 0.00
Received By gjohnson Date 2017-08-23 Time 17:05 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-07-26 Cont ID  
Sent By gjohnson Date 2017-07-26 Time 07:04 Rev Time 0.00
Received By gjohnson Date 2017-07-26 Time 06:42 Sent To  
Notes
***NONE***