Plan Review Details - Permit 17070680
Plan Review Stops For Permit 17070680
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-09-22 Cont ID  
Sent By shill Date 2017-09-22 Time 17:30 Rev Time 0.00
Received By shill Date 2017-09-22 Time 17:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-08-02 Cont ID  
Sent By shill Date 2017-08-02 Time 11:23 Rev Time 0.00
Received By shill Date 2017-08-02 Time 11:23 Sent To  
Notes
2017-08-02 11:25:50PASSED BY JW ON 7/27/17
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-09-28 Cont ID  
Sent By jleahy Date 2017-09-28 Time 16:37 Rev Time 0.00
Received By jleahy Date 2017-09-28 Time 16:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-07-27 Cont ID  
Sent By jpearson Date 2017-07-27 Time 10:28 Rev Time 0.00
Received By jpearson Date 2017-07-27 Time 10:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-09-20 Cont ID  
Sent By wjolin Date 2017-09-20 Time 09:57 Rev Time 0.00
Received By wjolin Date 2017-09-20 Time 09:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-07-21 Cont ID  
Sent By wjolin Date 2017-07-21 Time 13:46 Rev Time 0.00
Received By wjolin Date 2017-07-21 Time 13:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-03 Cont ID  
Sent By gjohnson Date 2017-10-03 Time 14:43 Rev Time 0.00
Received By gjohnson Date 2017-09-18 Time 13:33 Sent To  
Notes
2017-09-19 13:33:44B02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-02 Cont ID  
Sent By shill Date 2017-08-02 Time 11:25 Rev Time 0.00
Received By shill Date 2017-07-18 Time 16:37 Sent To  
Notes
2017-07-19 16:37:39B10

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-09-28 Cont ID  
Sent By ccole Date 2017-09-28 Time 08:44 Rev Time 0.00
Received By ccole Date 2017-09-28 Time 07:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-10-31 Cont ID  
Sent By ccole Date 2017-07-25 Time 11:51 Rev Time 0.00
Received By ccole Date 2017-07-25 Time 11:51 Sent To  
Notes
2017-07-25 12:01:431ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070680
 7/25/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A MORE COMPREHENSIVE MECHANICAL PLAN
 SHOWING ALL REQUIRED CHANGES TO THE EXISTING SYSTEM(S)
 AS A RESULT OF THE CHANGE FROM ONE TO TWO TENANT
 SPACES, AND THE INSTALLATION OF A DEMISING WALL. IT
 WOULD APPEAR BY THE SCOPE OF THE PROJECT THAT SOME
 DUCTS WOULD HAVED TO TE DEMOLISHED OR RELOCATED BECAUSE
 OF THE DEMISING WALL. SHOW THE LOCATION OF THE AIR
 HANDLER AND INDICATE HOW AIR IS BEING RETURN TO THE
 UNIT FROM BOTH TENANT SPACES- SECTION 107.2.1 WPB
 AMENDMENTS TO THE FBC.
  
 2) PROVIDE THE SIZE OF THE SUPPLY DUCT IN THE OFFICE
 WHERE THE 10" TRANSFER DUCT IS TO BE INSTALLED- SECTION
 601.5 EXCEPTION 1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-03 Cont ID  
Sent By gjohnson Date 2017-10-03 Time 14:42 Rev Time 0.00
Received By gjohnson Date 2017-10-03 Time 14:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-26 Cont ID  
Sent By gjohnson Date 2017-07-26 Time 11:19 Rev Time 0.00
Received By gjohnson Date 2017-07-26 Time 11:19 Sent To  
Notes
2017-07-26 11:46:121ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. NEW BAR SINK SHALL COMPLY WITH FBC ACC 606.2 CLEAR
 FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2. PROVIDE SANITARY AND WATER RISER DIAGRAM. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH