Plan Review Details - Permit 17070631
Plan Review Stops For Permit 17070631
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2017-09-29 Cont ID  
Sent By gjohnson Date 2017-09-29 Time 12:12 Rev Time 0.00
Received By gjohnson Date 2017-09-29 Time 12:12 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-08-16 Cont ID  
Sent By tklarge Date 2017-08-16 Time 10:57 Rev Time 0.00
Received By tklarge Date 2017-08-16 Time 10:23 Sent To  
Notes
2017-08-16 10:56:581) THE OUTDOOR TANKLESS WATER HEATER IS NOT CONSIDERED
 A "DIRECT VENT UNIT" AND MUST COMPLY WITH THE
 MANUFACTURER'S INSTALLATION CLEARANCE REQUIREMENTS
 WHICH IS 48 INCHES FROM AN OPERABLE DOOR OR WINDOW.
 SHOW THIS ON THE COPIES OF THE SUBMITTED HOUSE PLAN
 SHOWING THE LOCATION OF THE TANKLESS WATER HEATER.
 SUBMIT TWO COPIES OF THE PAGE FROM THE MANUFACTURER'S
 INSTALLATION MANUAL THAT SHOWS THE CLEARANCES FOR
 NON-DIRECT VENT UNIT.
 2) ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3. THE SUBMITTED
 SIZING TABLE DOES PROVIDE THE REQUIRED INFORMATION AND
 IS NOTED AS "FOR REFERENCE ONLY."
 3) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413
 4) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 THE ONLY GAS APPLIANCE ON THIS SYSTEM? IF NOT, SUBMIT A
 COMPLETE GAS RISER SHOWING ALL PIPE SIZES, TYPE OF
 PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET,
 THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM,
 THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM.
 THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM.
 6) THE SUBMITTED GAS RISER REFERS TO A RINNAI TANKLESS
 WATER HEATER BUT THE SUBMITTED SPECIFICATIONS ARE FOR A
 NAVIEN UNIT. CLARIFY.
 7) PLEASE CORRECT THE ADDRESS ON THE GAS RISER. IT
 SHOULD READ 2324 EMBASSY DR.
 8) IF A NAVIEN MODEL WATER HEATER IS BEING INSTALLED,
 IDENTIFY THE SPECIFIC MODEL THAT IS BEING INSTALLED AND
 THE BTU VALUE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-07-24 Cont ID  
Sent By tklarge Date 2017-07-24 Time 09:30 Rev Time 0.00
Received By tklarge Date 2017-07-24 Time 09:16 Sent To  
Notes
2017-07-24 09:22:091) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
 2) ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1.
 4) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413
 5) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 THE ONLY GAS APPLIANCE ON THIS SYSTEM? IF NOT, SUBMIT A
 COMPLETE GAS RISER SHOWING ALL PIPE SIZES, TYPE OF
 PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET,
 THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM,
 THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM.
 THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM.
 6) THE SUBMITTED GAS RISER REFERS TO A RINNAI TANKLESS
 WATER HEATER BUT THE SUBMITTED SPECIFICATIONS ARE FOR A
 NAVIEN UNIT. CLARIFY.
 7) SUBMIT TWO COPIES OF THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR THE TANKLESS WATER HEATER. WPB AMEND.
 TO FBC SEC. 107.2.1.
 8) PLEASE CORRECT THE ADDRESS ON THE GAS RISER. IT
 SHOULD READ 2324 EMBASSY DR.
 9) A SEPARATE PERMIT IS REQUIRED FOR THE PLUMBING FOR
 THE TANKLESS WATER HEATER. PLEASE SUBMIT AN ADDITIONAL
 PERMIT APPLICATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-16 Cont ID  
Sent By tklarge Date 2017-08-16 Time 10:57 Rev Time 0.00
Received By tklarge Date 2017-08-10 Time 11:07 Sent To  
Notes
2017-08-11 11:07:29RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-24 Cont ID  
Sent By tklarge Date 2017-07-24 Time 09:30 Rev Time 0.00
Received By tklarge Date 2017-07-17 Time 13:51 Sent To  
Notes
2017-07-18 13:51:29PLUMB <5K