| Plan Review Stops For Permit 17070628 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2017-08-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-08-24 |
Time |
18:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-08-24 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2017-08-24 18:59:01 | PROVIDE INSTALLATION INSTRUCTIONS FOR GAS APPLIANCES TO | | | FIELD INSPECTOR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-08-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-08-03 |
Time |
18:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-08-03 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2017-08-03 18:46:55 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PLAN SHEETS A-1, A-2 AND S-1 HAVE THE WRONG ADDRESS | | | IN THE TITLE BLOCK. PLEASE CORRECT. FAC 61G1-16.004 & | | | FBC 107.2.1 | | | | | | 2) PROVIDE A STRUCTURAL FRAMING DETAIL FOR THE ARCH | | | OPENINGS BETWEEN THE COLUMNS. FBC-R301.2.1 & FBC | | | 107.2.1.3 | | | | | | 3) PLAN SHEET A-1 HAS A NOTE TO RELOCATE THE EXISTING | | | BBQ AND THE SCOPE OF WORK FROM THE CONTRACTOR STATES | | | THAT THE BBQ AND EXHAUST HOOD ARE TO BE DISPOSED OF. | | | PLEASE CLARIFY. FBC 107.2.1 | | | | | | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS, LISTINGS AND | | | INSTALLATION INSTRUCTIONS FOR THE NEW SIDE BURNER, NEW | | | BBQ AND NEW EXHAUST HOOD. FBC 107.2.1 & FBC 107.2.1.3 | | | | | | 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC | | | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE | | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH | | | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS | | | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT | | | ROOFING MATERIALS AND ROOF TILE ADHESIVES (IF USED). | | | | | | 6) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED | | | TO INSTALL THE CEMENT ROOF TILES. FBC-R 905.3 & FBC-R | | | 301.1 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-08-25 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-08-25 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-08-25 |
Time |
10:41 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-07-31 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-07-31 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-07-31 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2017-07-31 15:02:29 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE CORRECT ADDRESS OF PROJECT ON PLANS. SHEETS | | | A-1, A-2, AND S-1 SHOW A DIFFERENT ADDRESS THAN THE | | | OTHER SHEETS. "CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL." FBC 107.2.1 | | | 2. NOTE # 11, SHEET C-1, STATES THAT RECEPTACLES SHALL | | | BE TAMPER RESISTANT PER NEC 406.11. THIS CODE SECTION | | | DOES NOT APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE | | | CORRECTION. NEC 406.12; FBC RE4002.14, FBC 107.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2017-08-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-08-03 |
Time |
18:08 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-08-03 |
Time |
18:08 |
Sent To |
|
|
| Notes |
| 2017-08-03 18:17:28 | NO GAS RISER PLANS WERE SUBMITTED. A SEPARATE PERMIT, | | | APPLICATION AND REVIEW IS REQUIRED FOR GAS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-08-25 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-08-25 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-08-10 |
Time |
11:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-08-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-08-03 |
Time |
18:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-07-17 |
Time |
15:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2017-08-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-08-03 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-08-03 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2017-08-03 16:45:47 | NO HABITABLE SPACE IS BEING ADDED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2017-08-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-08-24 |
Time |
18:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-08-24 |
Time |
16:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2017-08-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-08-03 |
Time |
18:08 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-08-03 |
Time |
18:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2017-08-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-08-24 |
Time |
19:13 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-08-24 |
Time |
19:13 |
Sent To |
E |
|
| Notes |
| 2017-08-24 19:13:22 | ROOFING | | | | | | 1) OWENS CORNING UNDERLAYMENT, WEATHERLOCK SPECIALITY | | | TILE & METAL, FL9777-R9 | | | 2) ICP TILE ADHESIVE, AH160, FL6332-R7 | | | 3) EAGLE ROOFING, ROOF TILES, FL7473-R6 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2017-08-24 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2017-08-24 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2017-08-17 |
Time |
16:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2017-08-02 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2017-08-02 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2017-08-01 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2017-08-02 08:25:43 | 8/2/17- PASSED | | | | | | NO TREES MAYBE MOVED WITHOUT A TREE ALTERATION PERMIT | | | | | | | | | PLEASE CONTACT | | | NATHAN WIRA- ZONING TECHNICIAN | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING | | | DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS ST. | | | WEST PALM BEACH, FL 33402 | | | OFFICE HOURS: M-F 8AM - 5PM | | | (561)822-1442 | | | [email protected] | | | |
|
|