Plan Review Details - Permit 17070622
Plan Review Stops For Permit 17070622
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-17 Cont ID  
Sent By rmcdouga Date 2017-08-17 Time 09:28 Rev Time 0.00
Received By rmcdouga Date 2017-08-17 Time 08:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-26 Cont ID  
Sent By rmcdouga Date 2017-07-26 Time 08:09 Rev Time 0.00
Received By rmcdouga Date 2017-07-26 Time 08:09 Sent To  
Notes
2017-07-26 08:11:41PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD AND ANCHORING PLAN IS REQUIRED TO
 HAVE THE FLORIDA ENGINEER'S SEAL AND ORIGINAL
 HANDWRITTEN SIGNATURE, COPIES OR OTHER FACSIMILES ARE
 NOT ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES
 ARE ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED
 PLANS AND DOCUMENTS.
  
 2) THE GENERATOR PAD AND ANCHORING PLAN THAT WAS
 SUBMITTED DOES NOT LIST THE MODEL NUMBER (QT048) OF THE
 48 KW GENERATOR THAT YOU ARE INSTALLING. CHECK THE
 MODELS LISTED ON THE PLANS TO BE SURE THEY MATCH THE
 ONE YOU WILL BE INSTALLING. FBC 107.2.1

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-16 Cont ID  
Sent By jleahy Date 2017-08-16 Time 11:33 Rev Time 0.00
Received By jleahy Date 2017-08-16 Time 11:33 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-07-27 Cont ID  
Sent By jleahy Date 2017-07-27 Time 17:01 Rev Time 0.00
Received By jleahy Date 2017-07-27 Time 17:01 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-08-16 Cont ID  
Sent By lcrespo Date 2017-08-16 Time 15:07 Rev Time 0.00
Received By lcrespo Date 2017-08-16 Time 15:07 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-07-25 Cont ID  
Sent By tklarge Date 2017-07-25 Time 13:56 Rev Time 0.00
Received By tklarge Date 2017-07-25 Time 13:48 Sent To  
Notes
2017-07-25 13:56:001.PLAN SHOW 922,000 BTU BUT MANUFACTURES SPECS QT048 AT
 100% OF LOAD STATES 756 CFU PLEASE CLARIFY ON PLAN TO
 REFLECT CORRECT ONE BEING USED. WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1.
 2.THE PLANS INDICATE AN EXISTING GAS METER.THE BTU LOAD
 OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL
 BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST
 BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
 3.INDICATE ON BOTH GAS DRAWINGS HOW THE PIPING THOUGH
 THE EXTERIOR WALL WILL BE PROTECTED. WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1.
 4.REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED,
 INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE
 AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM
 THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR
 EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5.
 5.THE MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR THE
 GENERATOR SHALL BE ON SITE FOR FINAL GAS INSPECTION.
 THE GENERATOR SHALL BE LISTED AND APPROVED. 2014
 FBC-FUEL GAS SEC. 301.3. THE GENERATOR SHALL MEET THE
 REQUIREMENTS OF UL 2200. THE SUBMITTED SPECIFICATIONS
 DO NOT SHOW THIS. CLARIFY.
  
 PLUMBING PLAN REVIEW
 LUIS A. CRESPO
 PLUMBING INSPECTOR
 561-805-6720
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-17 Cont ID  
Sent By rmcdouga Date 2017-08-17 Time 09:28 Rev Time 0.00
Received By rmcdouga Date 2017-08-10 Time 12:56 Sent To  
Notes
2017-08-11 12:56:41RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-27 Cont ID  
Sent By jleahy Date 2017-07-27 Time 17:01 Rev Time 0.00
Received By jleahy Date 2017-07-17 Time 16:23 Sent To  
Notes
2017-07-18 16:24:05ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2017-08-14 Cont ID  
Sent By njwira Date 2017-08-14 Time 14:42 Rev Time 0.00
Received By njwira Date 2017-08-14 Time 11:18 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-07-21 Cont ID  
Sent By njwira Date 2017-07-21 Time 11:11 Rev Time 0.00
Received By njwira Date 2017-07-19 Time 11:59 Sent To  
Notes
2017-07-21 11:11:537/21/17- FAILED
  
 MUST INDICATE A 3.5FT. SIDE SETBACK
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved