Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-15 Cont ID  
Sent By jwitmer Date 2017-08-15 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2017-08-15 Time 06:00 Sent To  
Notes
2017-08-15 07:10:002014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070620
 ADD: 8170 OKEECHOBEE BLVD. SUITE: 7
 CONT: ATLANTIC ENGINEERING SERVICES
 TEL: 561-358-4140
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. AUGUST 15/ 2017
 ACTION: BUILDING PROVISO
  
 1) BEFORE FRAMING INSPECTION COMPLY WITH, SHEET A-1
 DOOR NOTE # 1 INDICATES A NEW EXTERIOR DOOR, 3 FT. X 8
 FT. ALUM. & GLASS STOREFRONT TRULITE GLASS & ALUMINUM
 SOLUTIONS.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
  
 2) IDENTIFY GLAZING. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2014 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 3) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-20 Cont ID  
Sent By jwitmer Date 2017-07-20 Time 09:28 Rev Time  
Received By jwitmer Date 2017-07-20 Time 07:31 Sent To  
Notes
2017-07-20 09:28:412014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070620
 ADD: 8170 OKEECHOBEE BLVD. SUITE: 7
 CONT: ATLANTIC ENGINEERING SERVICES
 TEL: 561-358-4140
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 20/ 2017
 ACTION: DENIED
  
 1) SHEET A-2 IT APPEARS THERE MAY BE A DISCREPANCY IN
 THE PLANS. THE 2 ELEVATION VIEWS OF THE RESTROOM THE
 NORTH AND EAST SHOW TILE ON THE WALLS BUT WHEN YOU GO
 TO THE ROOM FINISH SCHEDULE, SAME PAGE IT APPEARS THE
 WALLS ARE A PAINT FINISH WITH NOTE (4). PLEASE PROVIDE
 COMPLIANCE WITH THE 2014 FBC-B 1210.2.2 WALLS AND
 PARTITIONS. WALLS AND PARTITIONS WITHIN 2 FEET (610 MM)
 OF SERVICE SINKS, URINALS AND WATER CLOSETS SHALL HAVE
 A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT OF
 NOT LESS THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED BY MOISTURE.
  
 2) THE MECHANICAL SHEET M-1 NOTE #9 IS FOR THROUGH THE
 WALL LOUVERS FOR EITHER INTAKE OR EXHAUST AIR.
 SHEET M-3 DETAIL 8 IDENTIFIES THE WALL LOUVER AS A
 MIAMI-DADE NOA 12-0830.08. PLEASE PROVIDE FOR
 COMPLIANCE WITH 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31(C) WALL LOUVERS
  
 3) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-09 Cont ID  
Sent By jpearson Date 2017-08-09 Time 08:20 Rev Time 0.00
Received By jpearson Date 2017-08-09 Time 08:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-24 Cont ID  
Sent By jpearson Date 2017-07-24 Time 10:14 Rev Time 0.00
Received By jpearson Date 2017-07-24 Time 10:14 Sent To  
Notes
2017-07-24 10:43:22CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. SPECS FOR EEMAX SP2412DL RECOMMEND A WIRE SIZE OF
 #10. PROVIDE CORRECTION. NEC 110.3
 2. POWER PLAN SHOWS THE SAME CIRCUIT FOR EWH AND ERV.
 PROVIDE CORRECTION. FBC 107.2.1, NEC 408.4
 3. PLEASE PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT
 NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND DATA,
 WIRELESS SYSTEMS, KITCHEN HOODS ETC. A NOTE WILL
 SUFFICE. FBC 105.1
 4. NOTE 20 ON E-1 STATES THERE IS NO FIRE ALARM, BUT
 NOTES 5 AND 11 ON MECHANICAL DRAWING REFERENCE FIRE
 ALARM WORK. PROVIDE CORRECTION. FBC 107.2.1
 5. PROVIDE SHORT CIRCUIT CALCULATION FOR SERVICE
 FEEDERS AND RATING OF ELECTRICAL PANEL TO CONFIRM
 ADEQUATE RATING. NEC 110.9, 110.10
 6. PROVIDE AUTOMATIC CONTROL OF SHOW WINDOW OUTLETS.
 FBC C405.2.2.1, C405.2.3
 7. ELECTRICAL RISER DIAGRAM APPEARS TO SHOW A JUNCTION
 BOX BELOW SLAB. JUNCTION BOXES ARE REQUIRED TO BE
 ACCESSIBLE. PROVIDE CORRECTION. NEC 314.29
 8. SPECS FOR ERV STATE THAT THE MOCP SHOULD BE 15 AMP.
 PANEL SCHEDULE SHOWS A 20 AMP BREAKER TO THIS UNIT.
 PROVIDE CORRECTION. NEC 110.3, FBC 107.2.1
 9. CIRCUIT 32 AND 34 SHOW A #14 WIRE ON A 20 AMP
 BREAKER. PROVIDE CORRECTION. NEC 310.15(B)(16), 240.4
 10. NOTE 12 ON E-1 STATES MINIMUM WIRE SIZE SHALL BE
 #12, BUT SEVERAL CIRCUITS ARE SHOWN WITH #14 WIRE.
 CLARIFY AND/OR CORRECT. FBC 107.2.1
 11. SEVERAL OUTLETS ON CIRCUIT 10 AND 12 APPEAR TO BE
 WITHIN 6 FEET OF A SINK AND DO NOT SHOW GFCI
 PROTECTION. PROVIDE GFCI PROTECTION REQUIRED PER CODE.
 NEC 210.8
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-16 Cont ID  
Sent By wjolin Date 2017-08-16 Time 13:12 Rev Time 0.00
Received By wjolin Date 2017-08-16 Time 13:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-07-21 Cont ID  
Sent By wjolin Date 2017-07-21 Time 14:00 Rev Time 0.00
Received By wjolin Date 2017-07-21 Time 13:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-17 Cont ID  
Sent By thunt Date 2017-08-17 Time 16:21 Rev Time 0.00
Received By thunt Date 2017-08-07 Time 14:27 Sent To  
Notes
2017-08-08 14:28:12B23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-26 Cont ID  
Sent By eschneid Date 2017-07-26 Time 10:07 Rev Time 0.00
Received By eschneid Date 2017-07-17 Time 15:23 Sent To  
Notes
2017-07-18 15:23:47B03

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-07-20 Cont ID  
Sent By jwitmer Date 2017-07-20 Time 09:28 Rev Time  
Received By jwitmer Date 2017-07-20 Time 07:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-08-14 Cont ID  
Sent By ccole Date 2017-08-14 Time 17:00 Rev Time 0.00
Received By ccole Date 2017-08-14 Time 16:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-24 Cont ID  
Sent By ccole Date 2017-07-24 Time 12:51 Rev Time 0.00
Received By ccole Date 2017-07-24 Time 12:51 Sent To  
Notes
2017-07-24 14:01:311ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070620
 7/24/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ERV EXHAUST OUTLET APPEARS TO BE WITHIN THE
 REQUIRED 10' CLEARANCE DISTANCE TO THE REAR DOOR-
 SECTION 501.3.1(2).
  
 2) SHOW THE ERV CONDENSATE PIPING RUN AND DISCHARGE
 LOCATION.
  
 3) SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE NOA GOT
 THE LOUVERS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2017-07-20 Cont ID  
Sent By jwitmer Date 2017-07-20 Time 09:59 Rev Time 0.00
Received By jwitmer Date 2017-07-20 Time 09:55 Sent To  
Notes
2017-07-20 09:59:39FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION
 IF PERMIT APPLICATION IS ON OR AFTER SEPT. 12/2016.
  
 THIS IS A SHELL BUILDING:
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
  
 (1) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
 W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS
 (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS
 COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR
 ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL
 INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR
 ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING
 JURISDICTION.
  
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-17 Cont ID  
Sent By thunt Date 2017-08-17 Time 16:18 Rev Time 0.00
Received By thunt Date 2017-08-17 Time 15:40 Sent To  
Notes
2017-08-17 16:20:53IF DEVELOPED LENGHT FROM ANY HOT OR TEMPERED WATER
 PIPING EXCEEDS 50" THEN A RECIRCULATION SYSTEM SHALL BE
 REQUIRED. MUST ALSO THEN COMPLY WITH 607.3 AND 607.5
 FPC.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6696
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-20 Cont ID  
Sent By gjohnson Date 2017-07-20 Time 17:22 Rev Time 0.00
Received By gjohnson Date 2017-07-20 Time 13:45 Sent To  
Notes
2017-07-20 17:39:511ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WASHING MACHINE FIXTURE BRANCH DRAIN SHALL BE
 3". PER FBC PL 406.2
  
 2. A LENT TRAP IS REQUIRED FOR WASHING MACHINE. PER FBC
 PL 1003.6
  
 3. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 4. THE SINK AT THE HOSTESS STATION SHALL COMPLY WITH
 FBC ACC 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-08-15 Cont ID  
Sent By eschneid Date 2017-08-15 Time 10:24 Rev Time 0.25
Received By eschneid Date 2017-08-15 Time 10:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-07-26 Cont ID  
Sent By eschneid Date 2017-07-26 Time 09:47 Rev Time 0.50
Received By eschneid Date 2017-07-26 Time 09:47 Sent To  
Notes
2017-07-26 10:04:25FAILED
  
 PROVIDE A WRITTEN RESPONSE.
  
 1) THE PLANS LIST THIS AS BUILD-OUT FOR SUITE #7. THE
 PLANS SHOW AN EXISTING DOOR ON THE NORTH SIDE OF THE
 SUITE. THE PLANS REVIEWED BY ZONING TO DATE FOR THIS
 BUILDING SHOW THIS AS BEING A WINDOW NOT A DOOR. PLEASE
 EXPLAIN. NOTE: ZONING STAFF DOES NOT OBJECT TO THIS
 BEING A DOOR AS OPPOSED TO A WINDOW PROVIDED IT IS A
 GLAZED DOOR, BUT THE PLANS NEED TO SHOW THE CHANGE FROM
 THE WINDOW TO THE DOOR, WITH DOOR SPECIFICATIONS.
  
 2) EXCEPT FOR THE CLARIFICATION REQUIRED BY COMMENT NO.
 1, THE PLANS COMPLY WITH ZONING REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]