Plan Review Details - Permit 17070579
Plan Review Stops For Permit 17070579
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-09 Cont ID  
Sent By jwitmer Date 2017-08-09 Time 07:38 Rev Time 0.00
Received By shill Date 2017-08-09 Time 07:34 Sent To  
Notes
2017-08-09 07:50:19****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 COMMENTS FROM PREVIOUS LIST, NOT ADDRESS, NOW PROVISO
 ITEMS:
  
 1. ALTHOUGH NOT CLOUDED AS A CHANGE ON A2 AND RELATED
 BUILDING SHEETS, IT APPEARS THAT AN ADDITIONAL ACU WAS
 ADDED, AND THE LOCATION OF THE OTHER ACU CHANGED. THE
 PLAN SHOWS AN ALLEY ON THAT SIDE OF THE BUILDING, BUT
 WITH NO DIMENSIONS.
  
 CLOUD ALL CHANGES, AND REVISE PLAN TO SHOW WIDTH OF
 "ALLEY". REVISE PLAN TO SHOW DIMENSIONS OF ACUS. REVISE
 PLAN TO EITHER SHOW ALL DOORS ON THE ADJACENT BUILDING,
 OR REVISE PLAN TO NOTE THAT THERE ARE NO DOORS ON THE
 WALL OF THE ADJACENT BUILDING, FBC 107, FBC CHAPTER 10.
  
 ***OR***
  
 IF THIS PAGE DOES NOT NEED TO BE CHANGED FOR ANY OTHER
 REASON, THIS ITEM MAY BE ADDRESSED WITH A SIGNED AND
 SEALED LETTER. STATE THAT THIS IS THE ONLY CHANGE, THAT
 THERE ARE NO DOORS ON ADJACENT BUILDING, AND THAT
 EXITING FOR ADJACENT BUILDING IS NOT AFFECTED.
  
 PROVISO, RESPONSE LETTER STATES THAT A NOTE WAS ADDED.
 UNABLE TO LOCATE. PROVISO, NO DOORS ARE EXISTING ON THE
 ADJACENT BUILDING.
  
 2. PROVIDE A VALUE FOR THE ADDITIONAL WORK, FBC 109.
 ADDITIONAL MECHANICAL WORK, ENTRY DOOR ARE INCLUDED IN
 THIS REVISION.
  
 RESPONSE LETTER STATES THERE IS NO ADDITIONAL VALUE,
 THIS IS AN "AS BUILT". $5000 ADDED FOR VALUE AS PLAN
 SHOWS ADDITIONAL WORK.
  
 3. PROVIDE A PRODUCT APPROVAL FOR THE PROPOSED NEW
 DOOR, FBC 1609.
  
 THE PRODUCT APPROVAL PROVIDED IS FOR AN INSWING OPAQUE
 DOOR; THE DOOR ON THE PLAN IS OUTSWING GLAZED.
  
 4. SHEET A4 WAS SUBMITTED, UNABLE TO LOCATE A CHANGE TO
 THE PLAN, FBC 107. CLOUD AND NUMBER OR DIRECT AS TO
 WHERE THE CHANGE(S) IS(ARE).
  
 RESPONSE LETTER STATES NOTHING HAS CHANGED. PROVISO,
 THIS SHEET HAS NOT BEEN REVIEWED AND HAS BEEN VOIDED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-25 Cont ID  
Sent By shill Date 2017-07-25 Time 08:49 Rev Time 0.00
Received By shill Date 2017-07-25 Time 08:36 Sent To  
Notes
2017-07-25 08:49:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. ALTHOUGH NOT CLOUDED AS A CHANGE ON A2 AND RELATED
 BUILDING SHEETS, IT APPEARS THAT AN ADDITIONAL ACU WAS
 ADDED, AND THE LOCATION OF THE OTHER ACU CHANGED. THE
 PLAN SHOWS AN ALLEY ON THAT SIDE OF THE BUILDING, BUT
 WITH NO DIMENSIONS.
  
 CLOUD ALL CHANGES, AND REVISE PLAN TO SHOW WIDTH OF
 "ALLEY". REVISE PLAN TO SHOW DIMENSIONS OF ACUS. REVISE
 PLAN TO EITHER SHOW ALL DOORS ON THE ADJACENT BUILDING,
 OR REVISE PLAN TO NOTE THAT THERE ARE NO DOORS ON THE
 WALL OF THE ADJACENT BUILDING, FBC 107, FBC CHAPTER 10.
  
 ***OR***
  
 IF THIS PAGE DOES NOT NEED TO BE CHANGED FOR ANY OTHER
 REASON, THIS ITEM MAY BE ADDRESSED WITH A SIGNED AND
 SEALED LETTER. STATE THAT THIS IS THE ONLY CHANGE, THAT
 THERE ARE NO DOORS ON ADJACENT BUILDING, AND THAT
 EXITING FOR ADJACENT BUILDING IS NOT AFFECTED.
  
 2. PROVIDE A VALUE FOR THE ADDITIONAL WORK, FBC 109.
 ADDITIONAL MECHANICAL WORK, ENTRY DOOR ARE INCLUDED IN
 THIS REVISION.
  
 3. PROVIDE A PRODUCT APPROVAL FOR THE PROPOSED NEW
 DOOR, FBC 1609.
  
 4. SHEET A4 WAS SUBMITTED, UNABLE TO LOCATE A CHANGE TO
 THE PLAN, FBC 107. CLOUD AND NUMBER OR DIRECT AS TO
 WHERE THE CHANGE(S) IS(ARE).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-09 Cont ID  
Sent By jpearson Date 2017-08-09 Time 09:21 Rev Time 0.00
Received By jpearson Date 2017-08-09 Time 09:21 Sent To  
Notes
2017-08-09 09:20:58APPROVED WITH EXCEPTION:
  
 PROVISO: DESIGN PROFESSIONAL SHALL PROVIDE CALCULATION
 FOR REDUCTION IN NEUTRAL SIZE TO PANEL C PRIOR TO FINAL
 INSPECTION. PROVIDE TO INSPECTOR AT TIME OF INSPECTION.
 NEC 220.61
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-20 Cont ID  
Sent By jleahy Date 2017-07-20 Time 14:01 Rev Time 0.00
Received By jpearson Date 2017-07-20 Time 14:01 Sent To  
Notes
2017-07-20 14:26:09CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. ELECTRICAL PLAN SHOWS 4 ELECTRIC COMPANY METERS, THE
 RISER DIAGRAM SHOWS 2. PROVIDE ACCURATE RISER DIAGRAM
 AND ELECTRICAL PLAN SHOWING THE LOCATION AND NAME OF
 EACH SERVICE AND THE CORRESPONDING SERVICE EQUIPMENT,
 AND THE RATING OF EACH DISCONNECT AND PANEL. NEC 215.5,
 408.30, FBC 107.2.1
 2. RISER DIAGRAM FOR PANEL C SHOWS 3-3/0 CONDUCTORS IN
 A 2 INCH CONDUIT FEEDING THE INTERIOR PANEL. AN
 EQUIPMENT GROUNDING CONDUCTOR IS REQUIRED IN THIS
 CONDUIT. PROVIDE CORRECTION. NEC 250.122, 250.24(A)(5)
 3. RISER DIAGRAM FOR PANEL A SHOWS 3/0 CONDUCTORS,
 WHICH IS RATED FOR 200 AMPS. THE LOAD CALCULATION
 PROVIDED FOR PANEL A AND PANEL B ADDED TOGETHER EQUALS
 206 AMPS, WHICH EXCEEDS THE RATING OF THE WIRE. THE
 LOAD FOR PANEL B IS NOT INCLUDED IN THE PANEL SCHEDULE
 FOR PANEL A, BUT IS SHOWN ON THE RISER AS BEING FED
 FROM PANEL A. PROVIDE ACCURATE LOAD CALCULATION AND
 CIRCUIT DIRECTORY FOR PANEL A, PROVIDE PROPERLY SIZED
 FEEDERS. NEC 215.2, 215.5, 220, 408.4, 310.15(B)(16)
 4. IN ADDITION TO COMMENT #3, PANEL B IS SHOWN AS A
 MAIN LUG ONLY PANEL. IF THIS IS ACCURATE, PROVIDE OVER
 CURRENT PROTECTION DETAILS. NEC 215.2, 240.4, 408.30,
 FBC 107.2.1
 5. IF PANEL B IS FED FROM PANEL A, WHICH IS SHOWN AS A
 200 AMP PANEL, THEN THIS PANEL IS ALSO OVERLOADED.
 PROVIDE CORRECTION. NEC 408.30
 6. THE WIRE FEEDING PANEL B DOES NOT INCLUDE THE
 REQUIRED EQUIPMENT GROUNDING CONDUCTOR. PROVIDE
 CORRECTION. NEC 250.122, 250.24(A)(5)
 7. EMERGENCY AND EXIT LIGHTS MUST BE ON THE SAME
 CIRCUIT AS THE LIGHTS IN THE SAME AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 8. PROVIDE REQUIRED SIGN CIRCUIT, WITH CONTROLS PER THE
 FBC ENERGY CODE. NEC 600.5, FBC C405.2.4
 9. PROVIDE SHOW WINDOW OUTLETS IF APPLICABLE. NEC
 210.62
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-14 Cont ID  
Sent By pleduc Date 2017-08-14 Time   Rev Time 0.00
Received By pleduc Date 2017-08-11 Time 15:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-07-24 Cont ID  
Sent By pleduc Date 2017-07-24 Time   Rev Time 0.00
Received By pleduc Date 2017-07-21 Time 17:08 Sent To  
Notes
2017-07-24 10:12:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) ADDRESS ELECTRICAL COMMENTS PER NFPA 70,
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-22 Cont ID  
Sent By skennedy Date 2017-08-22 Time 13:23 Rev Time 0.00
Received By skennedy Date 2017-08-04 Time 10:19 Sent To  
Notes
2017-08-07 10:19:36C14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-25 Cont ID  
Sent By shill Date 2017-07-25 Time 08:49 Rev Time 0.00
Received By shill Date 2017-07-14 Time 14:10 Sent To  
Notes
2017-07-17 14:10:51C14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-08-09 Cont ID  
Sent By ccole Date 2017-08-09 Time 17:16 Rev Time 0.00
Received By ccole Date 2017-08-09 Time 17:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-24 Cont ID  
Sent By ccole Date 2017-07-24 Time 15:00 Rev Time 0.00
Received By ccole Date 2017-07-24 Time 15:00 Sent To  
Notes
2017-07-24 15:13:441ST REVIEW FBC-2014 MECHANICAL
 REVISION PERMIT #17070579
 MASTER #16110180
 7/24/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: A MINIMUM 10' CLEARANCE BETWEEN THE ERV
 EXHAUST OUTLETS AND AIR INTAKES ARE REQUIRED PER
 SECTION 501.3.1 (3). PLEASE VERIFY COMPLIANCE BY
 PLACING THE CLEARANCE DISTANCE MEASUREMENTS ON THE
 PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-07-21 Cont ID  
Sent By gjohnson Date 2017-07-21 Time 14:28 Rev Time 0.00
Received By gjohnson Date 2017-07-21 Time 11:33 Sent To  
Notes
***NONE***