Plan Review Details - Permit 17070568
Plan Review Stops For Permit 17070568
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-10-24 Cont ID  
Sent By jleahy Date 2017-10-24 Time 12:59 Rev Time 0.00
Received By jleahy Date 2017-10-24 Time 12:52 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-21 Cont ID  
Sent By jleahy Date 2017-07-21 Time 08:04 Rev Time 0.00
Received By jleahy Date 2017-07-21 Time 08:04 Sent To G
Notes
2017-07-21 11:14:11FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 WHAT SIZE GENERATOR ARE YOU INSTALLING?
  
 PLEASE PROVIDE A RISER DIAGRAM, AND FOUNDATION
 INFORMATION FOR THE GENERATOR.
  
 VALUATION IS TO LOW.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-11-03 Cont ID  
Sent By tklarge Date 2017-11-03 Time 13:42 Rev Time 0.00
Received By tklarge Date 2017-11-03 Time 13:14 Sent To  
Notes
2017-11-03 13:42:401) SUBMIT TWO COMPLETE COPIES OF THE GENERATOR
 INSTALLATION MANUAL FOR REVIEW, NOT JUST ONE OR TWO
 PAGES. WPB AMEND. TO FBC SEC. 107.2.1
 2) THE SHEETS PROVIDED FROM THE GENERATOR MANUAL REFER
 TO A 13 KW GENERATOR BUT THE PLAN REVIEW NOTES
 SUBMITTED FOR THE ELECTRICAL PLAN REVIEWER REFER TO THE
 INSTALLATION OF A 25 KW GENERATOR. WHICH IS IT? SUBMIT
 TWO COPIES OF THE CORRECT INSTALLATION MANUAL FOR THE
 UNIT BEING INSTALLED. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHOW ON THE PLANS THE SPECIFIC BTU LOAD OF THE
 TANKLESS WATER HEATER. THE UNIT HAS A RANGE OF 15,000
 BTU'S UP TO 157,000 BTU'S.
 4) SPECIFICATIONS FOR A GAS RANGE HAS BEEN SUBMITTED
 BUT A GAS RANGE IS NOT SHOWN ON THE GAS DRAWING.
 CLARIFY.
 5) THE GAS SIZING TABLE THAT HAS BEEN SUBMITTED IS FOR
 A NORITZ TANKLESS WATER HEATER MODEL NR98-SV BUT THE
 MODEL NOTED ON THE GAS PLAN IS A NORITZ MODEL NRC
 711-OD. CLARIFY.
 6) THE GAS SIZING TABLE THAT HAS BEEN SUBMITTED IS
 UNACCEPTABLE. IT IS FROM THE 1997 UPC WHICH IS AN
 OUTDATED CODE AND THE UPC IS NOT A RECOGNIZED STANDARD
 IN THE 2014 FBC. THIS GAS SYSTEM SHALL BE SIZED
 UTILIZING THE 2014 FBC-FUEL GAS CODE OR NFPA 54.
 7) THE GAS PLAN SHOWS A POOL HEATER. IS IT NEW OR
 EXISTING? INDICATE ON THE PLAN. WPB AMEND. TO FBC SEC.
 107.2.1.
 8) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
 9) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED AND
 ALL PIPE SIZES.WPB AMENDMENTS TO FBC SEC.107.2.1.
 10) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413.
 11) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
 12) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
 13) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
 14) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
 15) SUBMIT TWO COMPLETE SETS OF PLANS COMPLYING WITH
 ALL OF THE ABOVE INFORMATION AND REMOVE ALL OLD SHEETS
 THAT DO NOT APPLY. WPB AMEND. TO FBC SEC. 107.1.
 16) THE GENERATOR SHALL MEET THE REQUIREMENTS OF UL
 2200.2014 FBC-FUEL GAS SEC.616.1. SUBMIT MANUFACTURER'S
 SPECIFICATIONS SHOWING COMPLIANCE.
 17) THE GENERATOR SHALL BE INSTALLED IN ACCORDANCE WITH
 THE MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA
 37. 2014 FBC-FUEL GAS SEC. 616.1.
 18) INDICATE ON THE SPECIFICATIONS WHAT MODEL OF THE
 GENERATOR IS BEING INSTALLED.
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-07-25 Cont ID  
Sent By tklarge Date 2017-07-25 Time 07:01 Rev Time 0.00
Received By tklarge Date 2017-07-25 Time 06:53 Sent To  
Notes
2017-07-25 07:00:541) CITY RECORDS SHOW A PREVIOUS GAS PERMIT FOR A RANGE
 AND TANKLESS WATER HEATER. THE BTU LOAD OF THE EXISTING
 GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE
 SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED.
 IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED. WPB
 AMENDMENTS TO FBC SEC.107.2.1.
 4) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413.
 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
 6) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2.
 7) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
 8) THE GENERATOR SHALL MEET THE REQUIREMENTS OF UL
 2200.2014 FBC-FUEL GAS SEC.616.1. SUBMIT MANUFACTURER'S
 SPECIFICATIONS SHOWING COMPLIANCE.
 9) THE GENERATOR SHALL BE INSTALLED IN ACCORDANCE WITH
 THE MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA
 37. 2014 FBC-FUEL GAS SEC. 616.1.
 10) SHOW THE DISTANCE OF THE GENERATOR FROM THE
 BUILDING WALL.
 11) INDICATE ON THE SPECIFICATIONS WHAT MODEL OF THE
 GENERATOR IS BEING INSTALLED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-03 Cont ID  
Sent By tklarge Date 2017-11-03 Time 13:42 Rev Time 0.00
Received By tklarge Date 2017-10-12 Time 13:10 Sent To  
Notes
2017-10-13 13:10:18RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-25 Cont ID  
Sent By tklarge Date 2017-07-25 Time 07:02 Rev Time 0.00
Received By tklarge Date 2017-07-14 Time 10:14 Sent To  
Notes
2017-07-18 10:14:58ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status F Date 2017-10-20 Cont ID  
Sent By ajones Date 2017-10-20 Time 16:32 Rev Time 0.00
Received By ajones Date 2017-10-20 Time 16:32 Sent To  
Notes
2017-10-20 16:34:1710/20/17- REPEAT COMMENT SEE ZONING COMMENT.
  
 ANGELLA VANN
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2017-07-20 Cont ID  
Sent By njwira Date 2017-07-20 Time 10:43 Rev Time 0.00
Received By jleahy Date 2017-07-21 Time 08:04 Sent To  
Notes
2017-07-20 10:44:147/20/17- FAILED
  
 PLEASE INDICATE HOW FAR THE GENERATOR IS FROM THE
 PROPERTY LINE
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved