Plan Review Details - Permit 17070564
Plan Review Stops For Permit 17070564
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-10 Cont ID  
Sent By jleahy Date 2017-08-10 Time 15:51 Rev Time 0.00
Received By jleahy Date 2017-08-10 Time 15:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-19 Cont ID  
Sent By jleahy Date 2017-07-19 Time 11:25 Rev Time 0.00
Received By jleahy Date 2017-07-19 Time 11:25 Sent To  
Notes
2017-07-19 11:37:00FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 NEED COPY OF THE LISTING REPORT SHOWING THE FIXTURE. I
 HAVE NO IDEA
 WHAT THE FIXTURE LOOKS (YELLOW GOAT) LIKE AND IT WILL
 HAVE TO MATCH
 WHAT IS OUT IN THE FIELD. YOU COULD SHOW ME ANY OLD
 FIXTURE AND CALL IT A YELLOW GOAT!
  
 110.2 APPROVAL
  
 THE CONDUCTORS AND EQUIPMENT REQUIRED OR PERMITTED BY
 THIS
 CODE SHALL BE ACCEPTABLE ONLY IF APPROVED.
  
  
 110.3 EXAMINATION, IDENTIFICATION, INSTALLATION, AND
 USE OF EQUIPMENT
  
 ( B) INSTALLATION AND USE. LISTED OR LABELED EQUIPMENT
 SHALL BE
 INSTALLED AND USED IN ACCORDANCE WITH ANY INSTRUCTIONS
 INCLUDED
 IN THE LISTING OR LABELING.
  
 A FIELD INSTALLED LABEL MAY BE REQUIRED.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-10 Cont ID  
Sent By jleahy Date 2017-08-10 Time 15:51 Rev Time 0.00
Received By jleahy Date 2017-08-04 Time 11:06 Sent To  
Notes
2017-08-07 11:07:06RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-19 Cont ID  
Sent By jleahy Date 2017-07-19 Time 11:37 Rev Time 0.00
Received By jleahy Date 2017-07-14 Time 11:33 Sent To  
Notes
2017-07-18 11:33:46SUBMITTAL ROUTED TO JLEAHY