| 2017-07-19 17:17:47 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17070554 |
| | ADD: 2500 METROCENTRE BLVD. W. SUITE # 5 |
| | CONT: CHANDLER CONSTRUCTION |
| | TEL: 561-791-6934 |
| | E-MAIL: JOHN@ BUILDCCC.COM |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JULY 20/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET A-0.0 INDICATES IN THE NOTES ON THE |
| | LEFT SIDE OF THE PLANS THE SQUARE FOOTAGE OF 1,787 SQ. |
| | FT. FOR THIS TENANT SPACE AND AN OCCUPANT LOAD OF 17. |
| | PLEASE SEE THE 2012 IBC-B CODE COMMENTARY WE NEVER |
| | ROUND DOWN ON OCCUPANTS NOR FRACTIONS OF OCCUPANTS. |
| | OCCUPANTS ONLY COME IN WHOLE NUMBERS, YOU ALWAYS ROUND |
| | UP. 2012 IBC-B 1004.1.2/ 2014 FBC-B TABLE 1004.1.2 AND |
| | THE BUILDING OFFICIALS ASSOCIATION OF FLORIDA INFORMAL |
| | CODE INTERPRETATION REPORT 5479. PLEASE NOTE ON THE |
| | SAME SHEET JUST RIGHT ON THE FLOOR PLAN THE SAME NOTE |
| | REAPPEARS PLEASE UPDATE PLANS TO THE CORRECT OCCUPANT |
| | LOAD. |
| | |
| | 2A) THE COVERSHEET A-0.0 INDICATES AN OCCUPANCY |
| | SEPARATION WALL BETWEEN A I-4 DAYCARE OCCUPANCY AND |
| | BUSINESS OCCUPANCY WITH A 2 HOUR FIRE RATING PER TABLE |
| | 508.4. THE PLANS DO NOT INDICATE A WALL TYPE OF |
| | CONSTRUCTION FOR WALL REPAIRS FOR WATER PIPES AND |
| | ELECTRICAL CONDUITS THAT WILL BE BEING INSTALLED IN |
| | THIS WALL, SEE SECTION 707.3.9 SEPARATED OF |
| | OCCUPANCIES. WHERE THE PROVISIONS OF SECTION 508.4 ARE |
| | APPLICABLE, THE FIRE BARRIER SEPARATING MIXED |
| | OCCUPANCIES SHALL HAVE A FIRE-RESISTANCE RATING OF NOT |
| | LESS THAN THAT INDICATED IN TABLE 508.4 BASED ON THE |
| | OCCUPANCIES BEING SEPARATED. NEITHER DOES THE PLAN |
| | INDICATE HOW FAR THE LAPS HAVE TO BE FORM ONE LAYER TO |
| | ANOTHER. |
| | |
| | 715.2 INSTALLATION. A FIRE-RESISTANT JOINT SYSTEM SHALL |
| | BE SECURELY INSTALLED IN ACCORDANCE WITH THE LISTING |
| | CRITERIA IN OR ON THE JOINT FOR ITS ENTIRE LENGTH SO AS |
| | NOT TO DISLODGE, LOOSEN OR OTHERWISE IMPAIR ITS ABILITY |
| | TO ACCOMMODATE EXPECTED BUILDING MOVEMENTS AND TO |
| | RESIST THE PASSAGE OF FIRE AND HOT GASES. |
| | |
| | 715.3 FIRE TEST CRITERIA. FIRE-RESISTANT JOINT SYSTEMS |
| | SHALL BE TESTED IN ACCORDANCE WITH THE REQUIREMENTS OF |
| | EITHER ASTM E 1966 OR UL 2079. NONSYMMETRICAL WALL |
| | JOINT SYSTEMS SHALL BE TESTED WITH BOTH FACES EXPOSED |
| | TO THE FURNACE, AND THE ASSIGNED FIRE-RESISTANCE RATING |
| | SHALL BE THE SHORTEST DURATION OBTAINED FROM THE TWO |
| | TESTS. WHEN EVIDENCE IS FURNISHED TO SHOW THAT THE WALL |
| | WAS TESTED WITH THE LEAST FIRE-RESISTANT SIDE EXPOSED |
| | TO THE FURNACE, SUBJECT TO ACCEPTANCE OF THE BUILDING |
| | OFFICIAL, THE WALL NEED NOT BE SUBJECTED TO TESTS FROM |
| | THE OPPOSITE SIDE. |
| | |
| | 2B) THE COVERSHEET A-0.0 INDICATES AN OCCUPANCY |
| | SEPARATION WALL BETWEEN A I-4 DAYCARE OCCUPANCY AND |
| | BUSINESS OCCUPANCY WITH A 2 HOUR FIRE RATING PER TABLE |
| | 508.4. THE PLANS (ARCHITECTURAL NOR M-E-P) DO NOT |
| | INDICATE HOW TO FIRE RATE THE PENETRATIONS IN THE 2HR. |
| | OCCUPANCY SEPARATION WALLS. PLEASE PROVIDE COMPLIANCE |
| | WITH FBC-B SECTION 714 714.3.1 THROUGH PENETRATIONS. |
| | THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS |
| | SHALL COMPLY WITH SECTION 714.3.1.1 OR 714.3.1.2. |
| | 3) SHEET A-1.0 THE FLOOR PLAN IDENTIFIES (3) DOORS R1, |
| | R2 & R3, THE DOOR SCHEDULE ON SHEET A-4.0 THESE ARE |
| | DOORS TO BE RE-USED. PLEASE NOTE THERE ARE NO NOTES IN |
| | THE DOOR SCHEDULE FOR THESE DOORS. CODE COMPLIANCE FOR |
| | THESE DOORS CANNOT BE DETERMINED. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 104.9.1 USED MATERIALS AND EQUIPMENT. |
| | THE USE OF USED, RECYCLED, OR RECLAIMED MATERIALS WHICH |
| | MEET THE REQUIREMENTS OF THIS CODE FOR NEW MATERIALS IS |
| | PERMITTED. USED |
| | EQUIPMENT AND DEVICES SHALL NOT BE REUSED UNLESS |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | THE USED DOORS MUST MEET THE REQUIREMENTS OF 1008.1.1 |
| | SIZE OF DOORS. THE MINIMUM WIDTH OF EACH DOOR OPENING |
| | SHALL BE SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND |
| | SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES . CLEAR |
| | OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE |
| | MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, |
| | WITH THE DOOR OPEN 90 DEGREES, MINIMUM OF A 36 INCH |
| | DOOR. |
| | |
| | 4) SHEET A-3.0 DETAIL # 3 THE BREAK ROOM ELEVATION OF |
| | CABINETS SHOWS A MICROWAVE ON A SHELF, THE SHELF AT THE |
| | HEIGHT OF 54 INCHES, PLEASE SHOW COMPLIANCE WITH; |
| | 4A)2014 FBC-ACCESS. CODE. REACH RANGES 308.2.2 |
| | OBSTRUCTED HIGH REACH OR308.3.2 OBSTRUCTED HIGH REACH, |
| | BOTH THE HIGHEST REACH RANGE IS 48 INCHES FROM FINISH |
| | FLOOR. |
| | |
| | 4B) PLEASE ALSO SHOW HOW CODE COMPLIANCE WITH BE |
| | ACHIEVED FOR ACCESS. CODE 309.2-309.4. |
| | |
| | 5) SHEET A-3.0 DETAILS FOR TOILETS 108 & 109 BOTH SHOW |
| | A MIRROR THE HEIGHT TO THE BOTTOM OF THE MIRROR |
| | INDICATES A HEIGHT OF 40 INCHES BUT DOES NOT INDICATE |
| | WHERE THE 40 INCHES IS MEASURED TO. PLEASE REVIEW |
| | SECTION 603.3 OF THE ACCESSIBILITY CODE THE BOTTOM OF |
| | THE MIRROR IS TO BE MEASURED TO THE BOTTOM EDGE OF THE |
| | REFLECTIVE SURFACE. |
| | |
| | 6) THE ARCHITECTS SEAL IS APPROXIMATELY 1 INCH IN |
| | DIAMETER. THE ARCHITECTS SEAL SHALL COMPLY WITH: |
| | ARCHITECT. 61G1-16.002(1) THE SEAL SHALL BE |
| | APPROXIMATELY 2" IN DIAMETER WITH TWO CIRCULAR LINES |
| | BETWEEN WHICH LINES SHALL APPEAR, AT THE TOP, THE WORDS |
| | ?STATE OF FLORIDA? AND AT THE BOTTOM THE WORDS |
| | ?REGISTERED ARCHITECT. ? |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |