Plan Review Details - Permit 17070534
Plan Review Stops For Permit 17070534
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2017-09-07 Cont ID  
Sent By lcrespo Date 2017-09-07 Time 15:43 Rev Time 0.00
Received By lcrespo Date 2017-09-07 Time 15:43 Sent To  
Notes
2017-09-07 15:45:10APPORVED LAC/ CALLED CONTRACTOR NO EMAIL FOUND
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-08-21 Cont ID  
Sent By tklarge Date 2017-08-21 Time 06:52 Rev Time 0.00
Received By tklarge Date 2017-08-21 Time 05:51 Sent To  
Notes
2017-08-21 06:18:421) CITY RECORDS SHOW A PREVIOUS GAS PERMIT AT THIS
 ADDRESS. THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST
 BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO
 ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3. 2ND REQUEST.
 2) THE PERMIT APPLICATION IS FOR ONE GENERATOR BUT THE
 SUBMITTTED PLAN SHOWS 2 GENERATORS.PERMIT #17080576
 SHOWS ONLY ONE GENERATOR TO BE INSTALLED BUT THE
 SUBMITTED GAS PLAN SHOWS TWO GENERATORS. CLARIFY. THE
 DESCRIPTION OF WORK ON THE APPLICATION SHALL CORRELATE
 WITH THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1. 2ND
 REQUEST.
 3) THE GAS PLAN APPEARS TO SHOW GALVANIZED PIPING
 UNDERGROUND WHICH IS NOT PERMITTED BY THE 2014 FUEL GAS
 CODE SEC.404.11, 404.11.1. 2ND REQUEST.
 4) SHOW THE BTU LOAD FOR EACH GENERATOR. 2014 FBC-FUEL
 GAS SECS. 401.8 THROUGH 402.2. 2ND REQUEST.
 5) THE SIZING TABLE THAT WAS SUBMITTED IS FROM THE 2009
 INTERNATIONAL FUEL GAS CODE. THE CODE IN EFFECT IS THE
 2014 FBC-FUEL GAS CODE. 2ND REQUEST.
 6) SUBMIT TWO COPIES OF A SURVEY SHOWING THE LOCATION
 OF THE GENERATORS AND THE LOCATION OF THE GAS METERS.
 WPB AMEND. TO FBC SEC. 107.2.1. 2ND REQUEST.
 7) CLARIFY HOW THE GALVANIZED PIPE TO THE 48 KW & 45 KW
 GENERATOR WILL BE INSTALLED. THE PLAN REFERS TO THE
 PIPE BEING MOUNTED ON A WALL BUT THE PLANS DO NOT SHOW
 ANY WALL FOR THIS PIPE TO BE MOUNTED.CLARIFY. SUBMIT
 TWO COPIES OF A SURVEY SHOWING THE LOCATION OF THE
 WALLS.
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1. THE SPECIFICATION
 THAT HAS BEEN SUBMITTED HAS NO INFORMATION AS TO THE
 MANUFACTURER EXCEPT WHAT IS WRITTEN ON IT. SUBMIT
 DOCUMENTATION THAT SHOWS THE MANUFACTURER OF THE
 REGULATOR THAT IS BEING INSTALLED. 2ND REQUEST.
  
 I SUGGEST CONTACTING THIS REVIEWER TO DISCUSS THESE
 PLAN REVIEW COMMENTS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-07-21 Cont ID  
Sent By tklarge Date 2017-07-21 Time 08:52 Rev Time 0.00
Received By tklarge Date 2017-07-21 Time 06:33 Sent To  
Notes
2017-07-21 06:49:071) CITY RECORDS SHOW A PREVIOUS GAS PERMIT AT THIS
 ADDRESS. THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST
 BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO
 ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1.
 3) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR THE GENERATOR(S) TO VERIFY
 COMPLIANCE WITH FBC-2014 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2014 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
 4) SUBMIT A SITE PLAN/SURVEY SHOWING THE LOCATION OF
 THE GENERATORS AND THE DISTANCE OF THE GENERATORS FROM
 THE STRUCTURES.
 5) THE PERMIT APPLICATION IS FOR ONE GENERATOR BUT THE
 SUBMITTTED PLAN SHOWS 2 GENERATORS. CLARIFY. THE
 DESCRIPTION OF WORK ON THE APPLICATION SHALL CORRELATE
 WITH THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
 6) THE GAS PLAN APPEARS TO SHOW GALVANIZED PIPING
 UNDERGROUND WHICH IS NOT PERMITTED BY THE 2014 FUEL GAS
 CODE SEC.404.11, 404.11.1.
 7) SHOW THE BTU LOAD FOR EACH GENERATOR. 2014 FBC-FUEL
 GAS SECS. 401.8 THROUGH 402.2.
 8) THE GENERATORS ARE REQUIRED TO MEET ZONING,
 ELECTRICAL AND BUILDING CODE REQUIREMENTS. COMPLETE
 PLANS SHALL BE SUBMITTED FOR THIS INSTALLATION. THE GAS
 PERMIT CANNOT BE ISSUED JUST FOR THE GAS INSTALLATION
 AS OTHER CODE REQUIREMENTS NEED TO BE MET.
 9) THE SIZING TABLE THAT WAS SUBMITTED IS FROM THE 2009
 INTERNATIONAL FUEL GAS CODE. THE CODE IN EFFECT IS THE
 2014 FBC-FUEL GAS CODE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-09-07 Cont ID  
Sent By lcrespo Date 2017-09-07 Time 15:38 Rev Time 0.00
Received By lcrespo Date 2017-09-07 Time 15:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-21 Cont ID  
Sent By tklarge Date 2017-08-21 Time 06:52 Rev Time 0.00
Received By tklarge Date 2017-08-17 Time 11:11 Sent To  
Notes
2017-08-18 11:11:21RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-21 Cont ID  
Sent By tklarge Date 2017-07-21 Time 08:52 Rev Time 0.00
Received By tklarge Date 2017-07-14 Time 12:44 Sent To  
Notes
2017-07-17 12:45:06PLUMB <5K

Review Stop P PLUMBING
Rev No 1 Status N Date 2017-09-07 Cont ID  
Sent By lcrespo Date 2017-09-07 Time 15:42 Rev Time 0.00
Received By lcrespo Date 2017-09-07 Time 15:42 Sent To  
Notes
***NONE***