Plan Review Details - Permit 17070522
| Plan Review Stops For Permit 17070522 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2017-07-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-07-17 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-07-17 |
Time |
13:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-07-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-07-17 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-07-17 |
Time |
07:40 |
Sent To |
|
|
| Notes |
| 2017-07-17 10:56:09 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- ACCORDING TO THE APPROVED APPLICATIONS ON PAGE 4 OF | | | 7 OF THE COBRA RIDGE VENT NOA 16-0217.02 SUBMITTED, THE | | | MINIMUM SLOPE IS 3:12. PERMIT APPLICATION SPECIFIES A | | | ROOF SLOPE OF 2:12. THEREFORE, THE RIDGE VENT CAN NOT | | | BE INSTALLED. PROVIDE ANOTHER PRODUCT APPROVAL THAT | | | ALLOWS RIDGE VENT INSTALLATION IN THE 2:12 SLOPE OR | | | ADVICE IF ROOF VENT IS NOT GOING TO BE INSTALLED. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-07-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-07-17 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-07-17 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2017-07-17 13:29:10 | THANK YOU JULIO. | | | | | | | | | I HAVE SPOKEN TO THE INSTALLATION MANAGER FOR THIS | | | PROJECT AND IT WAS DECIDED THAT THE PRODUCT WILL BE | | | CHANGED TO COBRA EXHAUST VENT, WHICH HAS A 2:12 ROOF | | | SLOPE MINIMUM. PLEASE PROCEED PERMITTING USING THE | | | ATTACHED PRODUCT APPROVAL | | | | | | | | | THANK YOU AND PLEASE DON'T HESITATE TO CONTACT ME AT | | | THE NUMBER BELOW IF YOU SHOULD HAVE ANY QUESTIONS. | | | | | | | | | WENDY L. GRIFFIN | | | OFFICE MANAGER/PERMIT COORDINATOR | | | TEAM K5 CONSTRUCTION & DEVELOPMENT COORDINATION, LLC | | | 1499 SW 30TH AVE. SUITE 8 | | | BOYNTON BEACH, FL 33426 | | | | | | | | | PH: 954-380-8672 | | | FAX: 954-271-1414 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-07-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2017-07-17 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2017-07-13 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2017-07-14 16:53:53 | JGOMEZ'S DESK |
|
|
|