Plan Review Details - Permit 17070500
Plan Review Stops For Permit 17070500
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-08-01 Cont ID  
Sent By tklarge Date 2017-08-01 Time 05:13 Rev Time 0.00
Received By tklarge Date 2017-08-01 Time 04:47 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-07-21 Cont ID  
Sent By tklarge Date 2017-07-21 Time 14:24 Rev Time 0.00
Received By tklarge Date 2017-07-21 Time 13:49 Sent To  
Notes
2017-07-21 14:24:421) TWO SURVEYS HAVE BEEN SUBMITTED. ONE SHOWS 10 FT. OF
 PE PIPE AND ONE SHOWS 8 FEET OF PE PIPE YET YOU HAVE
 SUBMITTED SIZING TABLES FOR COPPER TUBING. I HAVE NO
 IDEA WHAT YOU ARE TRYING TO ACCOMPLISH. CLARIFY.
 2) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 FOR THE TYPE OF GAS PIPE TO BE USED. 2014 FGC
 SEC.401.4, 401.8.
 3) SUBMIT MANUF. SPECIFICATIONS FOR THE REGULATOR. 2014
 FBC-FUEL GAS SEC.410.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-01 Cont ID  
Sent By tklarge Date 2017-08-01 Time 05:13 Rev Time 0.00
Received By tklarge Date 2017-07-24 Time 11:13 Sent To  
Notes
2017-07-25 11:13:39RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-21 Cont ID  
Sent By tklarge Date 2017-07-21 Time 14:24 Rev Time 0.00
Received By tklarge Date 2017-07-13 Time 12:32 Sent To  
Notes
2017-07-17 12:32:24PLUMB <5K