Plan Review Details - Permit 17070490
Plan Review Stops For Permit 17070490
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-03-23 Cont ID  
Sent By jwitmer Date 2018-03-23 Time 10:51 Rev Time 0.00
Received By jwitmer Date 2018-03-23 Time 07:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-03-14 Cont ID  
Sent By jwitmer Date 2018-03-14 Time 11:56 Rev Time 0.00
Received By jwitmer Date 2018-03-14 Time 07:44 Sent To  
Notes
2018-03-14 11:57:232014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070490
 ADD: 1111 S. FLAGLER DR.
 CONT: MYRICK GUROSKY & ASSOC.
 TEL: 205-313-3027
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. MARCH 14/ 2018
 ACTION: DENIED
  
 1) COLLATE PLANS INTO (2) COMPLETE SETS OF PLANS. WHEN
 RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS.
  
 2) 3RD REVIEW THERE IS ONLY ONE SET OF PLANS FROM MG+A,
 CONTAINING SHEETS T101, A101,A201, A501& E101, THE DATE
 THE PLANS WERE SEALED WAS 2/22/18.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.1 GENERAL. SUBMITTAL DOCUMENTS
 CONSISTING OF CONSTRUCTION DOCUMENTS, STATEMENT OF
 SPECIAL INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA
 SHALL BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. TWO OLD SETS OF MG+A VOIDED WERE ALSO IN
 THE PACKAGE.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2018-02-02 Time 13:15 Rev Time 0.00
Received By jwitmer Date 2018-02-02 Time 10:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-27 Cont ID  
Sent By jwitmer Date 2017-07-27 Time 14:37 Rev Time 0.00
Received By jwitmer Date 2017-07-27 Time 11:33 Sent To  
Notes
2017-07-27 14:37:222014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070490
 ADD: 1111 S. FLAGLER DR.
 CONT: MYRICK GUROSKY & ASSOC.
 TEL: 205-313-3027
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 27/ 2017
 ACTION: DENIED
  
 1) SHEET A101 INDICATES WINDOW AND DOOR TYPES ON THIS
 SHEET AS WELL AS DOOR SCHEDULE AND NOTES. NOTE # 1
 INDICATES THE EXTERIOR STOREFRONT OPENING IS TO BE
 LARGE MISSILE RATED, AND MUST MEET THE WIND LOAD
 REQUIREMENTS FOR THE LOCAL WIND SPEED. THE DESIGNER OF
 RECORD HAS NOT SPECIFIED THE WIND DESIGN CRITERIA.
 UNKNOWNS TO BASE THE WIND DESIGN, DOES THIS BUILDING
 WHOSE PRIMARY OCCUPANCY IS PUBLIC ASSEMBLY WITH AN
 OCCUPANT LOAD GREATER THAN 300. IF SO, THEN THE
 BUILDINGS RISK CATEGORY IS INCREASED TO III SEE THE
 2014 FBC-B TABLE 1604.5. WITH THE BUILDINGS RISK
 CATEGORY BEING III FIGURE 1609B PUTS THE WIND SPEED AT
 180 VULT.
  
 2) 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2.2. RISK CATEGORY.
  
 2.3HEIGHT AND EXPOSURE. WIND EXPOSURE. APPLICABLE WIND
 DIRECTION IF MORE THAN ONE WIND EXPOSURE IS UTILIZED.
 TABLE 1609.7.2.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
 PLEASE CONVERT ALL WIND PRESSURES INTO VASD SINCE THE
 PRODUCT APPROVALS ARE IN VASD.
  
 3) SHEET A101 INDICATES NEW STOREFRONT WINDOWS AND
 DOORS. PLEASE SUBMIT PRODUCT APPROVAL FOR REVIEW. 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS
  
 4) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 5) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) SHEET A101 IN THE DOOR SCHEDULE NOTE# 4 NOTE A
 INDICATES CYLINDER LOCK AND NOTE B POWER OR MANUAL
 PANIC HARDWARE. PLEASE REFER BACK TO FBC-B 1008.1.9.3
 (2) ONLY ALLOWS THE USE OF KEY OPERATED LOCKING DEVISES
 WHEN THE OCCUPANT LOAD IS LESS THAN 300. PLEASE VERIFY
 THE OCCUPANT LOAD OF THE BUILDING.
  
 7) SHEET A501:
 7A) DETAIL # 1 OF THE INDICATES A BRICK SUPPORT, UNDER
 PERMIT 17010099 THE PLANS INDICATE, PROVIDE AND INSTALL
 NEW GAL/ PAINTED BRICK LINTEL TO EXTEND 8 INCHES PAST
 THE OPENING. NEITHER PLAN TRULY IDENTIFIES THE SIZE OF
 THE BRICK ANGLE LINTEL? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 7B) NEITHER THIS SHEET NOR A101 INDICATE IF THE DOORS
 ARE GOING TO HAVE MANUAL DOORS OR POWER OPERATED,
 ASSIST DOORS. THE NOTE # 2 ON SHEET A101 HAS OR, THE
 PLANS NEED TO BE SPECIFIC. 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.3: W.P.B. ADMINISTRATIVE CODE,
 SUCH INFORMATION SHALL BE SPECIFIC TO THE TECHNICAL
 CODES "SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR
 THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A
 SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 7C) DETAIL 2 INDICATES THE EXISTING FOUNDATION NEW
 BLOCK WORK BENEATH GRADE AND TO FILL THE SPACE BETWEEN
 THE EXISTING FOUNDATION AND BLOCKWORK WITH GROUT. THE
 PLANS DO NOT MENTION THE REQUIREMENT FOR TERMITE
 TREATMENT SEE SECTION 1403.8 EXCEPTION # 4. . IF THE
 PATIO HAS BEEN SOIL TREATED FOR TERMITES, THE FINISH
 ELEVATION MAY MATCH THE BUILDING INTERIOR FINISH FLOOR
 ELEVATIONS ON MASONRY CONSTRUCTION ONLY.
  
 7D) DETAIL # 2 THE SUN SCREEN DOES NOT PROVIDE THE WIND
 DESIGN PARAMETERS FOR THE SUN SHADE TO BE MANUFACTURED
 AND INSTALLED. 105.5.1 LOADS.
 RIGID AWNINGS AND CANOPY SHUTTERS SHALL BE DESIGNED TO
 RESIST THE LOADS SET FORTH IN CHAPTER 16 OF THIS CODE
 (FBC-B).
  
 7E) DETAIL # 2 INDICATES THE USE OF 4 INCH STONE VENEER
 BUT THE PLANS DO NOT STATE HOW THE STONE VENEER IS TO
 BE ANCHORED, FBC-B 1405.7.
  
 7F) DETAIL # 2 THE WINDOW DETAIL INDICATES THE
 INSTALLATION OF A NEW GALVANIZED STEEL LINTEL ANGLE,
 THE PLANS DO NOT PROVIDE THE SIZE OF THE ANGLE NOR HOW
 FAR BEYOND THE WINDOW THE ANGLE NEEDS TO EXTEND?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 7G) THE NOTES INDICATE THE ANCHORING OF THE SUNSHADE
 WITH A ? INCH STEEL PLATE AND (2) ? INCH GALVANIZED
 DEFORMED STEEL PINS INTO THE EXISTING CONCRETE BEAM AND
 EPOXY. THE PLANS DO NOT PROVIDE HOW DEEP OF A HOLE IS
 TO BE CREATED, HOW LONG THE STEEL PINS NEED TO BE
 EMBEDDED, THE TYPE OF WELD TO ATTACH THE GALVANIZED
 PINS TO THE STEEL PLATE. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 7H) OVER THE EXTERIOR DOORS THE PLANS SHOW A NEW
 PREFABBED CANOPY OVER ALUMINUM PURLINS. THERE IS NO
 WIND DESIGN CRITERIA, THIS DETAIL SEEMS TO BE MORE OF A
 CONCEPTUAL DESIGN NO INFORMATION WAS PROVIDED.
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. 2010
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-03-29 Cont ID  
Sent By jpearson Date 2018-03-29 Time 07:54 Rev Time 0.00
Received By jpearson Date 2018-03-29 Time 06:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-02-14 Cont ID  
Sent By jpearson Date 2018-02-14 Time 07:11 Rev Time 0.00
Received By jpearson Date 2018-02-13 Time 07:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-25 Cont ID  
Sent By jpearson Date 2017-07-25 Time 08:29 Rev Time 0.00
Received By jpearson Date 2017-07-25 Time 08:29 Sent To  
Notes
2017-07-25 09:12:47CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE PANEL SCHEDULE FOR PANEL K, INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE. NEC
 215.5, 408.4, 600.5; FBC 107.2.1
 2. PROVIDE BLOCK NOTE THAT A SEPARATE PERMIT IS
 REQUIRED FOR SIGN. FBC 105.1
 3. INDICATE WIE SIZE ON PLAN, INCLUDE ANY NECESSARY
 ACCOMODATIONS FOR VOLTAGE DROP. FBC C405.7.3.2, FBC
 107.2.1
 4. PLAN INDICATES A TIME SWITCH WITH PHOTOCELL FOR
 CONTROL OF THE SIGN, BUT ALSO SHOWS 3 SWITCHES. WHAT IS
 THE PURPOSE OF THE SWITCHES? CLARIFY AND/OR CORRECT.
 FBC 107.2.1, FBC C405.2.4
 5. LOCATION OF ELECTRICAL COMPONENTS IS DIFFICULT TO
 SEE ON PLAN DUE TO THE BACKGROUND BEING FADED
 SUBSTANTIALLY. PROVIDE CLEAR PLAN FOR REVIEW. FBC
 107.2.1, 107.3.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-04-06 Cont ID  
Sent By gjohnson Date 2018-04-06 Time 10:09 Rev Time 0.00
Received By gjohnson Date 2018-03-16 Time 13:23 Sent To  
Notes
2018-03-19 13:24:35C06

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-03-14 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-02 Time 10:03 Sent To  
Notes
2018-03-06 10:04:19RESUB ROUTED TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-16 Cont ID  
Sent By lmarchan Date 2018-02-16 Time 09:35 Rev Time 0.00
Received By lmarchan Date 2018-01-30 Time 13:06 Sent To I
Notes
2018-01-31 13:07:04C32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-07-27 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-13 Time 13:46 Sent To  
Notes
2017-07-18 13:46:45C08

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-04-06 Cont ID  
Sent By gjohnson Date 2018-04-06 Time 10:09 Rev Time 0.00
Received By gjohnson Date 2018-04-06 Time 10:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-03-09 Cont ID  
Sent By thunt Date 2018-03-09 Time 14:03 Rev Time 0.00
Received By thunt Date 2018-03-09 Time 14:03 Sent To B
Notes
2018-03-09 14:06:2403/09/2018 PLUMBING 3RD REVIEW**DENIED**
  
 2 COMPLETE SET OF PLANS ARE REQUIRED FOR A REVIEW CAN
 BE COMPLETED. FBC 107.1
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-02-16 Cont ID  
Sent By thunt Date 2018-02-16 Time 05:34 Rev Time 0.00
Received By thunt Date 2018-02-16 Time 05:34 Sent To  
Notes
2018-02-16 05:37:3202/16/2018 PLUMBING 2ND REVIEW**DENIED**
  
 COMMENTS SAME AS 1ST REVIEW PLEASE ADDRESS
  
 PROVIDE A STORM RISER ISOMETRIC DRAWING SHOWING ALL
 NEW, EXISTING, AND THE TOTAL SQUARE FOOTAGE EACH DRAIN
 WILL HANDLE. WPB AMEND TO THE FBC 107.3.5.1.3 (13)
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-24 Cont ID  
Sent By gjohnson Date 2017-07-24 Time 15:51 Rev Time 0.00
Received By gjohnson Date 2017-07-24 Time 14:46 Sent To  
Notes
2017-07-24 15:55:431ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE STORM RISER DIAGRAM SHOWING SIZING,
 EXISTING A NEW AND THE SQ FT BEING DRAINED. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2018-03-22 Cont ID  
Sent By jroach Date 2018-03-22 Time 15:19 Rev Time 0.00
Received By jroach Date 2018-03-22 Time 14:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2018-03-07 Cont ID  
Sent By jroach Date 2018-03-07 Time 09:32 Rev Time 0.00
Received By jroach Date 2018-03-07 Time 09:32 Sent To P
Notes
2018-03-07 09:50:19ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 03.07.2018
 PERMIT NO.: 17070490
 ADDRESS: 1111 SOUTH FLAGLER DRIVE
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ONLY ONE (1) SET OF THE FOLLOWING REVISED SHEETS WAS
 PROVIDED: T101, A101, A201, A501, E101. TWO (2) SETS
 SHALL BE PROVIDED.
  
 2. SHEET E101 (ELECTRICAL SITE PLAN) STILL SHOWS
 LIGHTING (BOLLARDS) BEING INSTALLED ALONG A PROPOSED
 DROP-OFF AREA; IT WAS MY UNDERSTANDING THAT THE
 MODIFICATION TO THE PARKING AREA WAS REMOVED FROM THE
 SCOPE. IF SO, SHEET E101 SHOULD BE REVISED ACCORDINGLY.
  
 THE FOLLOWING COMMENT IS FOR INFORMATIONAL PURPOSES AND
 DOES NOT AFFECT THE REVIEW STATUS OF THIS PERMIT
 APPLICATION:
  
 A. SIGNAGE SHALL BE SUBMITTED UNDER A SEPARATE PERMIT
 APPLICATION. PLEASE NOTE THAT THE PROPERTY IS SUBJECT
 TO THE SIGNAGE REQUIREMENTS OF SEC. 94-408(F) OF THE
 CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS
 (INCLUDING MAXIMUM # OF SIGNS, MAXIMUM SQUARE FOOTAGE
 OF SIGNS, ETC.).
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-02-09 Cont ID  
Sent By JR Date 2018-02-09 Time 11:34 Rev Time 0.00
Received By jroach Date 2018-02-09 Time 08:20 Sent To  
Notes
2018-02-09 11:34:17ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.19.2017
 PERMIT NO.: 17070490
 ADDRESS: 1111 SOUTH FLAGLER DRIVE
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. SHEET C-4 DOES NOT ACCURATELY REFLECT THE EXISTING
 CONDITIONS.
  
 2. SHEET C-4 INDICATES THAT THERE IS PROPOSED TO BE A
 REDUCTION IN THE NUMBER OF PARKING SPACES. AS PROVIDED
 IN THE APPROVED SITE PLAN FOR THE FIRST BAPTIST CHURCH
 COMMUNITY SERVICE PLANNED DEVELOPMENT (CSPD), THE SITE
 CURRENTLY DOES NOT HAVE ANY EXCESSES PARKING BEYOND
 THAT REQUIRED BY THE ZONING AND LAND DEVELOPMENT
 REGULATIONS. AS SUCH, ANY PARKING PROPOSED TO BE
 REMOVED SHALL BE REPLACED ELSEWHERE ON THE PROPERTY.
  
 3. SHEET C-4 INDICATES THE REMOVAL OF HANDICAP
 ACCESSIBLE PARKING SPACES. AS PROVIDED IN THE APPROVED
 SITE PLAN FOR THE FIRST BAPTIST CHURCH CSPD, THE SITE
 CURRENTLY DOES NOT HAVE ANY EXCESSES ACCESSIBLE PARKING
 BEYOND THAT REQUIRED BY THE ZONING AND LAND DEVELOPMENT
 REGULATIONS. AS SUCH, ANY PARKING PROPOSED TO BE
 REMOVED SHALL BE REPLACED ELSEWHERE ON THE PROPERTY.
  
 4. PLANS INDICATE THAT THERE IS LANDSCAPING PROPOSED TO
 BE REPLACED WITH PAVERS/CONCRETE. AS PROVIDED IN THE
 APPROVED SITE PLAN FOR THE FIRST BAPTIST CHURCH CSPD,
 THE SITE CURRENTLY HAS THE MAXIMUM AMOUNT OF IMPERVIOUS
 SURFACE PERMITTED BY THE ZONING AND LAND DEVELOPMENT
 REGULATIONS. ANY LANDSCAPE MATERIAL THAT IS REMOVED
 SHALL BE REPLACED ELSEWHERE ON THE PROPERTY.
  
 5. SIGNAGE SHALL BE SUBMITTED UNDER A SEPARATE PERMIT
 APPLICATION. PLEASE NOTE THAT THE PROPERTY IS SUBJECT
 TO THE SIGNAGE REQUIREMENTS OF SEC. 94-408(F) OF THE
 CITY?S ZONING AND LAND DEVELOPMENT REGULATIONS
 (INCLUDING MAXIMUM # OF SIGNS, MAXIMUM SQUARE FOOTAGE
 OF SIGNS, ETC.).
  
 6. PURSUANT TO SEC. 94-207(E) OF THE CITY?S ZONING AND
 LAND DEVELOPMENT REGULATIONS, AS THE PROPOSED
 IMPROVEMENTS MODIFY THE PREVIOUSLY-APPROVED SITE AND
 LANDSCAPE PLANS, A MINOR AMENDMENT TO THE FIRST BAPTIST
 CSPD SHALL BE SUBMITTED TO AND APPROVED BY THE PLANNING
 DIVISION PRIOR TO THE ISSUANCE OF A BUILDING PERMIT.
  
 7. ALL LANDSCAPE MODIFICATIONS REQUIRE THE ISSUANCE OF
 A SEPARATE LANDSCAPE PERMIT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-07-19 Cont ID  
Sent By jroach Date 2017-07-19 Time 10:43 Rev Time 0.00
Received By jroach Date 2017-07-18 Time 14:40 Sent To  
Notes
2017-07-19 10:44:00ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.19.2017
 PERMIT NO.: 17070490
 ADDRESS: 1111 SOUTH FLAGLER DRIVE
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. SHEET C-4 DOES NOT ACCURATELY REFLECT THE EXISTING
 CONDITIONS.
  
 2. SHEET C-4 INDICATES THAT THERE IS PROPOSED TO BE A
 REDUCTION IN THE NUMBER OF PARKING SPACES. AS PROVIDED
 IN THE APPROVED SITE PLAN FOR THE FIRST BAPTIST CHURCH
 COMMUNITY SERVICE PLANNED DEVELOPMENT (CSPD), THE SITE
 CURRENTLY DOES NOT HAVE ANY EXCESSES PARKING BEYOND
 THAT REQUIRED BY THE ZONING AND LAND DEVELOPMENT
 REGULATIONS. AS SUCH, ANY PARKING PROPOSED TO BE
 REMOVED SHALL BE REPLACED ELSEWHERE ON THE PROPERTY.
  
 3. SHEET C-4 INDICATES THE REMOVAL OF HANDICAP
 ACCESSIBLE PARKING SPACES. AS PROVIDED IN THE APPROVED
 SITE PLAN FOR THE FIRST BAPTIST CHURCH CSPD, THE SITE
 CURRENTLY DOES NOT HAVE ANY EXCESSES ACCESSIBLE PARKING
 BEYOND THAT REQUIRED BY THE ZONING AND LAND DEVELOPMENT
 REGULATIONS. AS SUCH, ANY PARKING PROPOSED TO BE
 REMOVED SHALL BE REPLACED ELSEWHERE ON THE PROPERTY.
  
 4. PLANS INDICATE THAT THERE IS LANDSCAPING PROPOSED TO
 BE REPLACED WITH PAVERS/CONCRETE. AS PROVIDED IN THE
 APPROVED SITE PLAN FOR THE FIRST BAPTIST CHURCH CSPD,
 THE SITE CURRENTLY HAS THE MAXIMUM AMOUNT OF IMPERVIOUS
 SURFACE PERMITTED BY THE ZONING AND LAND DEVELOPMENT
 REGULATIONS. ANY LANDSCAPE MATERIAL THAT IS REMOVED
 SHALL BE REPLACED ELSEWHERE ON THE PROPERTY.
  
 5. SIGNAGE SHALL BE SUBMITTED UNDER A SEPARATE PERMIT
 APPLICATION. PLEASE NOTE THAT THE PROPERTY IS SUBJECT
 TO THE SIGNAGE REQUIREMENTS OF SEC. 94-408(F) OF THE
 CITY?S ZONING AND LAND DEVELOPMENT REGULATIONS
 (INCLUDING MAXIMUM # OF SIGNS, MAXIMUM SQUARE FOOTAGE
 OF SIGNS, ETC.).
  
 6. PURSUANT TO SEC. 94-207(E) OF THE CITY?S ZONING AND
 LAND DEVELOPMENT REGULATIONS, AS THE PROPOSED
 IMPROVEMENTS MODIFY THE PREVIOUSLY-APPROVED SITE AND
 LANDSCAPE PLANS, A MINOR AMENDMENT TO THE FIRST BAPTIST
 CSPD SHALL BE SUBMITTED TO AND APPROVED BY THE PLANNING
 DIVISION PRIOR TO THE ISSUANCE OF A BUILDING PERMIT.
  
 7. ALL LANDSCAPE MODIFICATIONS REQUIRE THE ISSUANCE OF
 A SEPARATE LANDSCAPE PERMIT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved