Plan Review Details - Permit 17070450
Plan Review Stops For Permit 17070450
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-10-20 Cont ID  
Sent By jgomez Date 2017-10-20 Time 15:14 Rev Time 0.00
Received By jgomez Date 2017-10-20 Time 14:24 Sent To  
Notes
2017-10-20 15:14:06RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 ENGINEER OF RECORD MAY BE CHARGED 4 TIMES THE PLAN
 REVIEW FEE AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B)
 FOR MULTIPLE PLANS REJECTIONS.
  
 1- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
 RESPONSE: REPEAT COMMENT. AFTER PLANS ARE REVISED BY
 THE ENGINEER, BRING THEM TO PALM BEACH COUNTY FOR
 IMPACT FEES ASSESSMENT.
  
 2- PROPOSED EGRESS WINDOW DOESN'T COMPLY WITH THE
 EGRESS REQUIREMENTS OF SEC. R310 FBC-RESIDENTIAL. 5TH
 EDITION (2014). NEED TO COMPLY WITH THE MINIMUM WIDTH
 OPENING, MINIMUM HEIGHT OPENING AND MINIMUM TOTAL CLEAR
 OPENING. SEE SEC. R310 FBC-RESIDENTIAL, 5TH EDITION
 (2014) AND REVISE AS REQUIRED. SH-33 DOESN'T COMPLY.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. NOTE: REVISE
 SIZE OF WINDOW AND CLEARLY SPECIFY SIZE. SEE PRODUCT
 APPROVAL FOR STANDARD SIZES.
  
 3- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 4- PLANS NEED TO PROVIDE INFORMATION SHOWING COMPLIANCE
 WITH THE HEATING REQUIREMENTS OF SEC. R303.9
 FBC-RESIDENTIAL. NOTE: PORTABLE HEATERS ARE NOT
 ALLOWED.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 5- NEW BATHROOM WINDOW TO COMPLY WITH THE SAFETY
 GLAZING REQUIREMENTS OF SEC. R308.4.5 FBC-RESIDENTIAL
 IF THE WINDOW DOESN'T HAVE IMPACT GLASS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. WINDOWS
 PRODUCT APPROVAL WAS NOT SUBMITTED. UNABLE TO VERIFY IF
 WINDOWS ARE GOING TO BE IMPACT RESISTANT OR NOT.
  
 6- PROVIDE DETAILS AND SPECIFICATIONS SHOWING HOW THE
 NEW CONCRETE BLOCK WALL IS ATTACHED TO THE EXISTING
 WOOD BEAM. SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 7- TYPICAL WALL SECTION: SPECIFY FOOTING REINFORCEMENT.
 SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR;
 A) SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 B) WINDOW MULLION AS SPECIFIED ON PLANS. AND, SPECIFY
 MULLION SIZE TO VERIFY COMPLIANCE WITH SEC. R301.1
 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 C) ARCHED FIXED WINDOW AS SPECIFIED ON PLANS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 D) PRECAST LINTELS AS SPECIFIED ON PLANS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 E) HURRICANE SHUTTERS IF THE WINDOWS PRODUCT APPROVALS
 DON'T HAVE HURRICANE IMPACT GLASS. AND, PROVIDE
 COMPLETE INSTALLATION SCHEDULE. SEE CITY SAMPLE.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 10- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT (EVEN FOR OWNER
 BUILDER) AND ALL DESIGN PROFESSIONAL FEES AS REQUIRED
 BY SEC. 1098.3 CITY AMENDMENTS. REVISE VALUATION AS
 REQUIRED.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 *******ENGINER TO PROVIDE RESPONSE LETTER ADDRESING
 EACH COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-09 Cont ID  
Sent By jgomez Date 2017-08-09 Time 10:32 Rev Time 0.00
Received By jgomez Date 2017-08-08 Time 18:16 Sent To  
Notes
2017-08-08 18:22:34RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROPOSED EGRESS WINDOW DOESN'T COMPLY WITH THE
 EGRESS REQUIREMENTS OF SEC. R310 FBC-RESIDENTIAL. 5TH
 EDITION (2014). NEED TO COMPLY WITH THE MINIMUM WIDTH
 OPENING, MINIMUM HEIGHT OPENING AND MINIMUM TOTAL CLEAR
 OPENING. SEE SEC. R310 AND REVISE AS REQUIRED.
  
 3- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 4- PLANS NEED TO PROVIDE INFORMATION SHOWING COMPLIANCE
 WITH THE HEATING REQUIREMENTS OF SEC. R303.9
 FBC-RESIDENTIAL. NOTE: PORTABLE HEATERS ARE NOT
 ALLOWED.
  
 5- NEW BATHROOM WINDOW TO COMPLY WITH THE SAFETY
 GLAZING REQUIREMENTS OF SEC. R308.4.5 FBC-RESIDENTIAL
 IF THE WINDOW DOESN'T HAVE IMPACT GLASS.
  
 6- PROVIDE DETAILS AND SPECIFICATIONS SHOWING HOW THE
 NEW CONCRETE BLOCK WALL IS ATTACHED TO THE EXISTING
 WOOD BEAM. SEC. R301.1 FBC-RESIDENTIAL.
  
 7- WINDOW BUCK DETAIL: ENGINEER OF RECORD NEEDS TO
 SPECIFY ANCHOR TYPE AND SPACING FOR THE BUCK FASTENING.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 8- TYPICAL WALL SECTION: SPECIFY FOOTING REINFORCEMENT.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR;
 A) SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS.
  
 B) WINDOW MULLION AS SPECIFIED ON PLANS. AND, SPECIFY
 MULLION SIZE TO VERIFY COMPLIANCE WITH SEC. R301.1
 FBC-RESIDENTIAL.
  
 C) ARCHED FIXED WINDOW AS SPECIFIED ON PLANS.
  
 D) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 E) HURRICANE SHUTTERS IF THE WINDOWS PRODUCT APPROVALS
 DON'T HAVE HURRICANE IMPACT GLASS. AND, PROVIDE
 COMPLETE INSTALLATION SCHEDULE. SEE CITY SAMPLE.
  
 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 11- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT (EVEN FOR OWNER
 BUILDER) AND ALL DESIGN PROFESSIONAL FEES AS REQUIRED
 BY SEC. 1098.3 CITY AMENDMENTS. REVISE VALUATION AS
 REQUIRED.
  
 *******ENGINER TO PROVIDE RESPONSE LETTER ADDRESING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-10-25 Cont ID  
Sent By jpearson Date 2017-10-25 Time 14:12 Rev Time 0.00
Received By jpearson Date 2017-10-25 Time 14:12 Sent To  
Notes
2017-10-25 14:12:21CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 (COMMENTS NOT ADDRESSED ARE NOTED IN PARANTHESES).
  
 1. PROVIDE FLOOR PLAN FOR ENTIRE RESIDENCE, SHOWING
 LOCATION OF EXISTING SMOKE ALARMS. IF NONE ARE
 EXISTING, OR NOT TO CODE, SHOW AS NEW INSTALLATION.
 PROVIDE SMOKE ALARM IN THE IMMEDIATE VICINITY OUTSIDE
 THE NEW BEDROOM. FBC R314.3, R314.3.1; FBC 107.2.1
 (REPEAT COMMENT: NOT ADDRESSED)
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902 (REPEAT COMMENT: NOT ADDRESSED)
 3. PROVIDE LOAD CALCULATION TO CONFIRM EXISTING SERVICE
 IS ADEQUATE FOR THE ADDITIONAL LOAD. NEC 220; FBC
 RE3602.1 (REPEAT COMMENT: NOT ADDRESSED)
 4. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; FBC 107.2.1 (REPEAT COMMENT: NOT ADDRESSED)
 5. PROVIDE AFCI PROTECTION PER CODE: "ALL 120-VOLT,
 SINGLE PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS
 SUPPLYING OUTLETS IN DWELLING UNIT FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION". NEC 210.12; FBC RE3902.12 (REPEAT COMMENT:
 NOT ADDRESSED)
 6. PROVIDE DEDICATED 20 AMP CIRCUIT FOR BATH GFCI
 OUTLET: "A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT
 SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS".
 NEC 210.11(C)(3) , FBC RE3703.4 (REPEAT COMMENT: NOT
 ADDRESSED)
 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 (REPEAT
 COMMENT: NOT ADDRESSED)
 8. PROVIDE RECEPTACLES PER THE NEC WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. NEC 210.52; FBC RE3901.2.1
 (REPEAT COMMENT: NOT ADDRESSED)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-28 Cont ID  
Sent By jpearson Date 2017-07-28 Time 10:33 Rev Time 0.00
Received By jpearson Date 2017-07-28 Time 10:33 Sent To  
Notes
2017-07-28 10:52:44CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE FLOOR PLAN FOR ENTIRE RESIDENCE, SHOWING
 LOCATION OF EXISTING SMOKE ALARMS. IF NONE ARE
 EXISTING, OR NOT TO CODE, SHOW AS NEW INSTALLATION.
 PROVIDE SMOKE ALARM IN THE IMMEDIATE VICINITY OUTSIDE
 THE NEW BEDROOM. FBC R314.3, R314.3.1; FBC 107.2.1
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
 3. PROVIDE LOAD CALCULATION TO CONFIRM EXISTING SERVICE
 IS ADEQUATE FOR THE ADDITIONAL LOAD. NEC 220; FBC
 RE3602.1
 4. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; FBC 107.2.1
 5. PROVIDE AFCI PROTECTION PER CODE: "ALL 120-VOLT,
 SINGLE PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS
 SUPPLYING OUTLETS IN DWELLING UNIT FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION". NEC 210.12; FBC RE3902.12
 6. PROVIDE DEDICATED 20 AMP CIRCUIT FOR BATH GFCI
 OUTLET: "A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT
 SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS".
 NEC 210.11(C)(3) , FBC RE3703.4
 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
 8. PROVIDE RECEPTACLES PER THE NEC WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. NEC 210.52; FBC RE3901.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-25 Cont ID  
Sent By jpearson Date 2017-10-25 Time 14:12 Rev Time 0.00
Received By jpearson Date 2017-10-03 Time 11:04 Sent To  
Notes
2017-10-04 11:04:33R01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-09 Cont ID  
Sent By jgomez Date 2017-08-09 Time 10:48 Rev Time 0.00
Received By jgomez Date 2017-07-12 Time 13:09 Sent To  
Notes
2017-07-13 13:09:49R18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-10-20 Cont ID  
Sent By jgomez Date 2017-10-20 Time 15:41 Rev Time 0.00
Received By jgomez Date 2017-10-20 Time 15:40 Sent To E
Notes
2017-10-20 15:41:141- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-08-09 Cont ID  
Sent By jgomez Date 2017-08-09 Time 10:48 Rev Time 0.00
Received By jgomez Date 2017-08-09 Time 10:48 Sent To  
Notes
2017-08-09 10:48:521- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-13 Cont ID  
Sent By thunt Date 2017-10-13 Time 15:05 Rev Time 0.00
Received By thunt Date 2017-10-13 Time 13:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-07-25 Cont ID  
Sent By tklarge Date 2017-07-25 Time 06:35 Rev Time 0.00
Received By tklarge Date 2017-07-25 Time 06:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2017-10-11 Time   Rev Time 0.00
Received By   Date 2017-10-11 Time   Sent To  
Notes
2017-10-11 09:26:40*****************************ZONING
 REVIEW*******************************
  
 PLEASE PROVIDE A COPY OF THE SURVEY, HIGHLIGHTING THE
 CONVERTED AREA. IS THE BUILDING FOOTPRINT EXPANDING?
  
 PLEASE LET ME KNOW IF YOU HAVE ANY QUESTIONS.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 [email protected]
 561-822.1449

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2017-08-07 Time   Rev Time 0.00
Received By awooten Date 2017-08-02 Time 16:06 Sent To  
Notes
2017-08-07 15:24:33*****************************ZONING
 REVIEW*******************************
  
 PLEASE PROVIDE A COPY OF THE SURVEY, HIGHLIGHTING THE
 CONVERTED AREA. IS THE BUILDING FOOTPRINT EXPANDING?
  
 PLEASE LET ME KNOW IF YOU HAVE ANY QUESTIONS.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 [email protected]
 561-822.1449