Plan Review Details - Permit 17070386
Plan Review Stops For Permit 17070386
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-07-14 Cont ID  
Sent By skennedy Date 2017-07-14 Time 16:05 Rev Time 0.00
Received By skennedy Date 2017-07-14 Time 16:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-07-14 Cont ID  
Sent By shill Date 2017-07-14 Time 12:09 Rev Time 0.00
Received By shill Date 2017-07-14 Time 12:04 Sent To  
Notes
2017-07-14 12:13:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
  
 1. THE PRODUCT APPROVAL SUBMITTED IS EXPIRED; THIS HAS
 BEEN REPLACED BY REVISION 5. PRINT TWO COMPLETE SETS.
  
 2. THE PRODUCT APPROVAL REFERS TO FBC BUILDING
 1507.4.2. BASED ON THE ROOF PITCH PROVIDED VIA EMAIL BY
 APPLICANT (2.5/12), LAP SEALANT IS REQUIRED.
  
 PRIOR TO RESUBMITTING, REVISE THE APPLICATION TO
 INCLUDE THE ROOF PITCH AND MEAN ROOF HEIGHT. MARK THE
 PRODUCT APPROVAL TO INDICATE PROPOSED METHOD OF
 INSTALLATION.
  
 VIA EMAIL, METHOD 1 WAS PROPOSED. PER THE PRODUCT
 APPROVAL, METHOD 2 IS REQUIRED FOR ADHESIVE
 INSTALLATION.
  
 ALTERNATIVELY, APPLICANT CAN SUBMIT A DIFFERENT PRODUCT
 APPROVAL. METHOD OF INSTALLATION IS REQUIRED TO BE
 INDICATED ON THE PRODUCT APPROVAL OR ON THE PERMIT
 APPLICATION.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-12 Cont ID  
Sent By shill Date 2017-07-12 Time 07:51 Rev Time 0.00
Received By shill Date 2017-07-12 Time 07:40 Sent To  
Notes
2017-07-12 07:55:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. NOT ENOUGH INFORMATION TO DETERMINE CODE COMPLIANCE.
 PROVIDE ROOF PITCH, MEAN ROOF HEIGHT. SEE PAGE 5 OF THE
 METAL ROOF PRODUCT APPROVAL; TWO FASTENING OPTIONS ARE
 AVAILABLE. INDICATE WHICH IS PROPOSED (METHOD 1 OR
 METHOD 2).
 FBC 2014 RESIDENTIAL 301.2.
  
 DESIGN PRESSURES REQUIRED CANNOT BE DETERMINED WITHOUT
 PITCH AND ROOF HEIGHT INFORMATION. THIS MAY BE SENT VIA
 EMAIL AND DESIGN PRESSURES WILL BE DETERMINED FOR YOU.
 AFTER DESIGN PRESSURES ARE DETERMINED, APPLICANT CAN
 SELECT FASTENING METHOD. THIS ALSO WILL BE DONE FOR YOU
 UPON REQUEST.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-12 Cont ID  
Sent By shill Date 2017-07-12 Time 07:55 Rev Time 0.00
Received By shill Date 2017-07-11 Time 16:35 Sent To  
Notes
2017-07-11 16:36:00SHILL