Plan Review Details - Permit 17070343
Plan Review Stops For Permit 17070343
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-08-16 Time   Rev Time 0.00
Received By jwitmer Date 2017-08-16 Time 06:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-16 Cont ID  
Sent By jwitmer Date 2017-08-04 Time 07:58 Rev Time 0.00
Received By jwitmer Date 2017-08-04 Time 07:30 Sent To  
Notes
2017-08-04 07:48:322014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070343
 ADD: 4601 N. CONGRESS AVE.
 CONT: WILSON & COMPANY, INC.
 TEL: 407-365-0906
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. AUG.04/ 2017
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) NEW COMMENT. THE CONTRACTOR SUBMITTED A ROOF TOP A/C
 STAND PRODUCT APPROVAL NOA 16-0601.01. THE ROOF TOP A/C
 STAND PRODUCT APPROVAL A MIAMI-DADE NOA # 16-0601.01
 WAS SUBMITTED, REVIEWED BY THE DESIGNER OF RECORD.
 NEITHER THE CONTRACTOR NOR THE DESIGNER OF RECORD HAVE
 FOLLOWED THE PRODUCT APPROVAL IN CALCULATING THE AREA
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT.
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-17 Cont ID  
Sent By jwitmer Date 2017-07-17 Time 14:48 Rev Time 0.00
Received By jwitmer Date 2017-07-17 Time 12:00 Sent To  
Notes
2017-07-17 14:48:222014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070343
 ADD: 4601 N. CONGRESS AVE.
 CONT: WILSON & COMPANY, INC.
 TEL: 407-365-0906
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 17/ 2017
 ACTION: DENIED
  
 1A) SHEET A1 SHOWS A POINT OF SALE THROUGH WINDOWS A &
 B. SHEET A1.1, DEETAIL # 7 INTERIOR WINDOW SCHEDULE
 SHOWS THE BOTTOM OF THESE WINDOWS AT AN ELEVATION 3 FT.
 2 1/2 INCHES. SHEET A-4 DETAIL 7 & 8 SHOW THE ELEVATION
 VIEW OF THESE WINDOW ON BOTH SIDES OF THE GLASS. DETAIL
 # 7 FROM THE CUSTOMER VIEW AND VIEW # 8 FROM THE
 PHARMISTIST POINT OF VIEW. DETAIL #7 INDICATES THE
 BOTTOM OF THE WINDOW/ COUNTER TOP TO BE AT AN ELEVATION
 OF 3 FOOT 4 INCHES DISCREPANCY IN THE PLANS. DETAIL # 8
 IS NOT DIMENSIONED BUT THE WINDOW APPEARS TO HAVE A
 WINDOW FRAME ON THE BOTTOM OF THE WINDOW, A WINDOW
 SILL, WHEN MEASURED THE GLAZING APPEARS TO BE 42 INCHES
 OR 3 FOOR 6 INCHES FROM THE FINISH FLOOR. DISCREPANCY
 IN PLANS, 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 1B) THE PLANS INDICATE THIS IS THE POINT OF SALE,
 WINDOW/ 10 INCH TRANSACTION COUNTER PLEASE PROVIDE A
 CUT SCTION THROUGH THE WINDOW TO INCLUDE THE HEIGHT OF
 THE TRANS ACTION COUNTER IN COMPLIANCE WITH THE 2014
 FBC-ACCESSIBILITY CODE 904.3.2 COUNTERS. THE COUNTER
 SURFACE HEIGHT SHALL BE 38 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. IF THE POINT OF SALE COUNTER IS
 ALSO TO BE FOR CHECK WRITING THEN A PORTION OF THE
 COUNTER WILL ALSO NEED TO SHOW COMPLIANCE WITH THE
 ACCESS. CODE SECTION 904.3.3 CHECK WRITING SURFACES.
 WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY
 WITH 902.3. 2014 FBC-ACCESSIBILITY CODE 902.3 HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2) SHEETS A1-1 AND A4 INDICATE THE USE OF A NEW FIRE/
 SMOKE CURTAIN, THE PLANS STATE TO THE BUILDING
 STANDARD, WHAT IS THE BUILDING STANDARD THAT IS TO BE
 UPHELD? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-07-19 Cont ID  
Sent By jleahy Date 2017-07-19 Time 10:13 Rev Time 0.00
Received By jleahy Date 2017-07-19 Time 09:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-07-14 Cont ID  
Sent By pleduc Date 2017-07-14 Time   Rev Time 0.00
Received By pleduc Date 2017-07-14 Time 10:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date 2017-08-16 Cont ID  
Sent By jwitmer Date 2017-08-16 Time 06:26 Rev Time 0.00
Received By jwitmer Date 2017-08-11 Time 16:49 Sent To  
Notes
2017-08-14 16:49:45JWITMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-09 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-01 Time 15:05 Sent To  
Notes
2017-08-02 15:06:06B21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2017-07-21 Time   Rev Time 0.00
Received By cpuell Date 2017-07-11 Time 10:44 Sent To  
Notes
2017-07-13 10:45:06B21

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-07-17 Cont ID  
Sent By jwitmer Date 2017-07-17 Time 14:48 Rev Time 0.00
Received By jwitmer Date 2017-07-17 Time 12:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-08-09 Cont ID  
Sent By ccole Date 2017-08-09 Time 09:36 Rev Time 0.00
Received By ccole Date 2017-08-09 Time 09:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-21 Cont ID  
Sent By ccole Date 2017-07-21 Time 16:36 Rev Time 0.00
Received By ccole Date 2017-07-21 Time 16:23 Sent To  
Notes
2017-07-21 16:43:051ST REVIEW FBC-2014 MECHANICAL , EXISTING BUILDING
 CODES
 PERMIT #17070343
 7/21/17
  
 PLAN REVIEW RESULTS: DENIED
  
 1) REFER TO SECTION 809.1 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) AUTOMATIC SHUTOFF DAMPERS, EITHER MOTORIZED OR
 GRAVITY, SHALL BE PROVIDED FOR THE O/A DUCT- SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 3) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE INDOOR
 UNITS IN THE CEILINGS- SECTION 307.
  
 4) PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE ROOFTOP CONDNENSER AND STAND.
 PROVIDE COMPLETE DETAILS FOR ANCHORING INCLUDING HOW
 THE STAND WILL BE ATTACHED TO THE ROOF- SECTION 301.15.
 SUBMIT A MIAMI-DADE NOA OR FLORIDA PRODUCT APPROVAL FOR
 THE STAND WITH REVIEW STAMP BY THE EOR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-07-18 Cont ID  
Sent By gjohnson Date 2017-07-18 Time 08:52 Rev Time 0.00
Received By gjohnson Date 2017-07-18 Time 08:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-08-07 Cont ID  
Sent By eschneid Date 2017-08-07 Time 14:42 Rev Time 0.25
Received By eschneid Date 2017-08-07 Time 14:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-07-18 Cont ID  
Sent By eschneid Date 2017-07-18 Time 12:06 Rev Time 0.25
Received By eschneid Date 2017-07-18 Time 12:06 Sent To  
Notes
2017-07-18 12:09:09FAILED
  
 1) PROVIDE A GRAPHIC WHICH VERIFIES THAT THE PROPOSED
 AC UNIT IS SCREENED BY THE HEIGHT OF THE EXISTING
 PARAPET AND ITS LOCATION ON THE ROOF.
  
 CONTACT ERIC SCHNEIDER@ (561) 822-1446.
 [email protected]