| 2017-07-17 15:50:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET A203 - THERE ARE TWO DOUBLE DOORS LEADING FROM |
| | THE WAREHOUSE TO THE OFFICE AREA. THERE DOES ARE |
| | INDICATING AS SWINGING AGAINST EGRESS. |
| | |
| | PER NFPA 101, CHAPTER 42, STORAGE OCCUPANCIES |
| | |
| | 42.2 MEANS OF EGRESS REQUIREMENTS. |
| | 42.2.1 GENERAL. |
| | 42.2.1.1 EACH REQUIRED MEANS OF EGRESS SHALL BE IN |
| | ACCORDANCE WITH THE APPLICABLE PORTIONS OF CHAPTER 7. |
| | |
| | 42.2.2 MEANS OF EGRESS COMPONENTS. |
| | 42.2.2.2 DOORS. |
| | 42.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | |
| | 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES |
| | REQUIRED TO BE OF THE SIDE-HINGED OR PIVOTED-SWINGING |
| | TYPE SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL |
| | UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD |
| | OF 50 OR MORE, EXCEPT UNDER ANY OF THE FOLLOWING |
| | CONDITIONS: |
| | (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE |
| | REQUIRED TO SWING IN THE DIRECTION OF EGRESS TRAVEL |
| | WHERE PERMITTED BY 7.2.4.3.8.1 OR 7.2.4.3.8.2. |
| | (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED |
| | TO SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING |
| | HEALTH CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19. |
| | (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT |
| | ENCLOSURE, UNLESS THE DOOR OPENING SERVES AN INDIVIDUAL |
| | LIVING UNIT THAT OPENS DIRECTLY INTO AN EXIT ENCLOSURE |
| | (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD |
| | CONTENTS AREA |
| | |
| | PLEASE REVIEW AND CORRECT THE SWING OR JUSTIFY THEY ARE |
| | NOT REQUIRED FOR EXIT AND REMOVE THE EXIT SIGNS. |
| | |
| | |
| | |
| | |
| | 2) SHEET A 203 - PALLET STORAGE IS INDICATED, BUIT NO |
| | DETAIL IS PROVIDED. |
| | |
| | PLEASE PROVIDE DETAILS OF THE PROPOSED PALLET SYSTEM |
| | AND COMMODITY CLASSIFICATION PER NFPA 101. CHAPTER 6, |
| | CLASSIFICATION OF OCCUPANCY AND HAZARD OF CONTENTS |
| | |
| | 6.2 HAZARD OF CONTENTS. |
| | |
| | 6.2.2 CLASSIFICATION OF HAZARD OF CONTENTS. |
| | 6.2.2.1* GENERAL. THE HAZARD OF CONTENTS OF ANY |
| | BUILDING OR STRUCTURE SHALL BE CLASSIFIED AS LOW, |
| | ORDINARY, OR HIGH IN ACCORDANCE WITH 6.2.2.2, 6.2.2.3, |
| | AND 6.2.2.4. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 3) SHEET A 203 - RACK STORAGE IS INDICATED, BUT NO |
| | DETAIL IS PROVIDED. THOUGH A SEPARATE PERMIT IS |
| | INDICATED, RACK INFORMATION SHALL BE SUBMITTED FOR |
| | INFORMATIONAL PURPOSES TO CONDUCT A PLAN REVIEW. |
| | |
| | PLEASE PROVIDE DETAILS ON THE SIZE, HEIGHT, AND TYPE OF |
| | RACKS AND WHAT WILL BE STORED ON THEM. |
| | |
| | |
| | |
| | |
| | 4) SHEET A 203 - A FIRE SPRINKLER SYSTEM IS INDICATED. |
| | IS THIS A NEW SYSTEM OR AN EXISTING ONE. |
| | |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION |
| | ENGINEERING |
| | DOCUMENTS. |
| | (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED |
| | IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE |
| | WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND |
| | DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S), |
| | MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND |
| | UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE |
| | SAFEGUARDING OF LIFE, HEALTH OR PROPERTY. |
| | (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE |
| | ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND |
| | COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES |
| | AND STANDARDS, WHERE AVAILABLE. |
| | (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A |
| | SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION |
| | SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE |
| | PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT |
| | AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE |
| | TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND |
| | ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT |
| | SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED |
| | BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE |
| | FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL |
| | BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS. |
| | (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION |
| | FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT |
| | COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED |
| | ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER |
| | OF RECORD FOR THE FIRE PROTECTION SYSTEM. |
| | (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS, |
| | SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY |
| | RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN |
| | ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS, |
| | UNLESS SHOWN ON OTHER RELATED DOCUMENTS. |
| | (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER |
| | OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION |
| | IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED |
| | PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE |
| | SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR |
| | OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE |
| | SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION |
| | SYSTEM ENGINEERING DOCUMENTS. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| | LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| | HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED |
| | 4-2-2000, 6-26-01 |
| | |
| | 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION |
| | SYSTEMS. |
| | (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT |
| | ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET, |
| | DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE |
| | CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE |
| | WATER MAINS AND DEDICATED FIRE PROTECTION WATER |
| | SOURCES. |
| | (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION |
| | SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL |
| | INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN |
| | APPLICABLE: |
| | (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER |
| | SUPPLY AS DEFINED BY 633.021(18) F.S. |
| | (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE |
| | CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING |
| | STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND |
| | CONCLUSIONS. |
| | (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA. |
| | (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE, |
| | DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR |
| | EACH SEPARATE 42 HAZARD OCCUPANCY. |
| | (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS |
| | MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR |
| | CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE |
| | NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM |
| | DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY |
| | DEMANDING DESIGN AREA. |
| | (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE |
| | FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO |
| | CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION, |
| | STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH |
| | RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND |
| | LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF |
| | SERVICE. |
| | (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE |
| | POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF |
| | WATER. |
| | (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF |
| | RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER |
| | SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION |
| | (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE |
| | LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY |
| | WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY |
| | TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND |
| | THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE |
| | PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE |
| | MEASURES. |
| | (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND |
| | DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS |
| | INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. |
| | (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD |
| | AND INTERIOR FIRE PROTECTION COMPONENTS. |
| | (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE |
| | MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL |
| | DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING |
| | APPROVAL AND DOCUMENTATION. |
| | (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE |
| | INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE |
| | OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL |
| | ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE |
| | CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| | LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| | HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED |
| | 4-2-2000, 6-26-01, 7-12-05 |
| | |
| | |
| | PLEASE PROVIDE THE REQUIRED FIRE SPPRINKLER DOCUMENTS |
| | IN DRAWING OR NARRATIVE FORM FOR THIS MASTER PERMIT. |
| | SHOP DRAWINGS SHALL BE PREPARED OFF OF THESE CRITERIA |
| | AND SUBMITTED AT A LATER DATE. |
| | |
| | |
| | |
| | |
| | 5) SHEET 3.1 - THERE ARE NO INDICATIONS OF EXIT SIGNS |
| | IN THE AISLES OF THE WAREHOUSE AREAS. EXIT SIGNS MAY BE |
| | REQUIRED IF YOU CAN NOT SEE THE ONES BY THE EXIT DOORS. |
| | |
| | 42.2.8 ILLUMINATION OF MEANS OF EGRESS. |
| | |
| | 42.2.8.1 MEANS OF EGRESS SHALL BE ILLUMINATED IN |
| | ACCORDANCE WITH SECTION 7.8. |
| | |
| | 7.8 ILLUMINATION OF MEANS OF EGRESS. |
| | 7.8.1 GENERAL. |
| | 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY |
| | BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11 |
| | THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT |
| | ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING |
| | TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT |
| | DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT |
| | PASSAGEWAYS LEADING TO A PUBLIC WAY. |
| | 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF |
| | OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE |
| | FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2. |
| | |
| | PLEASE REIVEW AND CORRECT. |
| | |
| | |
| | |
| | 6) SHEET E 0.1 - THERE IS NO INDICATIONS OF A FIRE |
| | ALARM SYSTEM. |
| | |
| | 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 9.6.1* GENERAL. |
| | 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY |
| | WHERE SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS |
| | CODE OR WHERE SUPERVISION OF A NEW FIRE SPRINKLER |
| | SYSTEM OR NEW FIRE ALARM SYSTEM IS REQUIRED BY THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 9.7.1.4 AUTOMATIC SPRINKLER SYSTEMS INSTALLED TO MAKE |
| | USE OF AN ALTERNATIVE PERMITTED BY THIS CODE SHALL BE |
| | CONSIDERED REQUIRED SYSTEMS AND SHALL MEET THE |
| | PROVISIONS OF THIS CODE THAT APPLY TO REQUIRED SYSTEMS. |
| | |
| | A FIRE SPRINKLER IS REQUIRED AND SHALL BE MONITORED. |
| | ALL FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE SHOP |
| | DRAWINGS BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE. |
| | |
| | |
| | 7) INFORMATIONAL PURPOSES - SHOULD # 2 ABOVE FIND THE |
| | THE HAZARD CLASSIFICATION AS HIGH HAZARD THEN THE |
| | FOLLOWING SHALL APPLY. |
| | |
| | 42.2.4.3 AREAS WITH HIGH HAZARD CONTENTS SHALL COMPLY |
| | WITH SECTION 7.11. |
| | |
| | 7.11 SPECIAL PROVISIONS FOR OCCUPANCIES WITH HIGH |
| | HAZARD |
| | CONTENTS. SEE SECTION 6.2. |
| | 7.11.1* WHERE THE CONTENTS ARE CLASSIFIED AS HIGH |
| | HAZARD, EXITS SHALL BE PROVIDED AND ARRANGED TO ALLOW |
| | ALL OCCUPANTS TO ESCAPE FROM THE BUILDING OR STRUCTURE, |
| | OR FROM THE HAZARDOUS AREA THEREOF, TO THE OUTSIDE OR |
| | TO A PLACE OF SAFETY WITH A TRAVEL DISTANCE OF NOT MORE |
| | THAN 75 FT (23 M), MEASURED AS REQUIRED IN 7.6.1, |
| | UNLESS OTHERWISE PROVIDED IN 7.11.2 |
| | |
| | PLEASE REVIEW AND PROVIDE FOR CORRECTIONS. |
| | |
| | |
| | |
| | |
| | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |