Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-07-19 Cont ID  
Sent By hmoser Date 2017-07-19 Time 08:46 Rev Time 0.00
Received By hmoser Date 2017-07-19 Time 08:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-10 Cont ID  
Sent By hmoser Date 2017-07-10 Time 09:45 Rev Time 0.00
Received By hmoser Date 2017-07-10 Time 09:45 Sent To  
Notes
2017-07-10 10:08:24PLAN DENIED
 1) PROVIDE CFM AND GRILL SIZE ON PLANS. PER SECTION 107
 FBC
 2) NEED INCREASE IN VALUE ON THE APPLICATION.
 3) REFER TO SECTION M1602.4 BALANCED RETURN AIR.
  
 PLAN REVIEW BY HAROLD MOSER