Plan Review Details - Permit 17070201
Plan Review Stops For Permit 17070201
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-07-27 Cont ID  
Sent By jwitmer Date 2017-07-27 Time 08:07 Rev Time 0.00
Received By jwitmer Date 2017-07-27 Time 07:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-07-13 Cont ID  
Sent By jwitmer Date 2017-07-13 Time 16:32 Rev Time 0.00
Received By jwitmer Date 2017-07-13 Time   Sent To  
Notes
2017-07-13 16:35:442014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070201
 ADD: 3505 POINSETTIA AVENUE
 CONT: PMG GENERAL CONTRACTING
 TEL: 954-607-8721
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. JULY 13/2017
 ACTION: DENIED
  
 WORK DESCRIPTION: ROOF RECOVER
  
 1) 2ND REVIEW. THE CONTRACTOR HAS SUBMITTED ANOTHER
 MANUFACTURERS PRODUCT APPROVAL, A MIAMI-DADE NOA
 16-1206.02 GAF LIBERTY SBS SELF ADHERING MODIFIED
 BITUMEN ROOFING SYSTEM OVER WOOD DECKS.
 THE CONTRACTOR HAS MARKED PAGE 15 WOOD , NON-INSULATED
 DECK SYSTEM E(1) THE SUB-SYSTEM MARKED HAS THE BASE
 SHEET MECHANICALLY ATTACHED AND THE MAXIMUM DESIGN
 PRESSURE OF -45 PSF. WITH GENERAL LIMITATION #7.
  
 SUB-SYSTEMS WITH GENERAL LIMITATION # 7 REQUIRED
 ENHANCED FASTENING . FASTENER DENSITIES SHALL BE
 INCREASED FOR THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER OR REGISTERED
 ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-07 Cont ID  
Sent By jwitmer Date 2017-07-07 Time 09:06 Rev Time  
Received By jwitmer Date 2017-07-07 Time 08:30 Sent To  
Notes
2017-07-07 09:06:272014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070201
 ADD: 3505 POINSETTIA AVENUE
 CONT: PMG GENERAL CONTRACTING
 TEL: 954-607-8721
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JULY 07/2017
 ACTION: DENIED
  
 WORK DESCRIPTION: ROOF RECOVER
  
 1) THE CONTRACTOR HAS NOT IDENTIFIED ON WHICH PAGE OR
 SYSTEM OF THE PRODUCT APPROVAL, PAGE 6 OR 7 IS TO BE
 THE APPLIED APPLICATION. PAGE 6 FOR ALL SYSTEMS HAS A
 MAXIMUM DESIGN PRESSURE OF 45 PSF AND A LIMITATION #9,
 NO ENHANCED FASTENING ALLOWED. PAGE 7 HAS (2)
 SUB-SYSTEMS SYSTEM # 1 THE MAXIMUM DESIGN PRESSURES ARE
 -67.5 PSF AND LIMITATION # 7 ALLOWING ENHANCED
 FASTENING, AND SUB-SYSTEM # 2 WITH A MAXIMUM DESIGN
 PRESSURE OF -52.5 PSF AND LIMITATION NUMBER 7.
  
 FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-07-27 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-21 Time 09:52 Sent To  
Notes
2017-07-24 09:53:05RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-07-13 Time   Rev Time 0.00
Received By cpuell Date 2017-07-12 Time 13:11 Sent To  
Notes
2017-07-13 13:12:02JWITMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-07-07 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-06 Time 16:53 Sent To  
Notes
2017-07-06 16:53:53JWITMER