Plan Review Details - Permit 17070199
| Plan Review Stops For Permit 17070199 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-08-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-08-03 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-08-03 |
Time |
08:06 |
Sent To |
|
|
| Notes |
| 2017-08-03 13:47:01 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. TWO SETS OF SUBMITTAL DOCUMENTS ARE REQUIRED. PLEASE | | | PROVIDE A SECOND COPY OF THE FOLLOWING DOCUMENTS: SITE | | | PLAN, SURVEY, GEO REPORT, ENERGY SUBMITTAL WITH MANUAL | | | J CALC'S. | | | | | | FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF | | | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL | | | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL | | | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT | | | APPLICATION. | | | | | | 2. DESIGNER TO SELECT MODEL OF DOORS AND WINDOWS TO BE | | | INSTALLED FROM LIST ON PRODUCT APPROVALS. | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-07-26 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-07-26 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-07-26 |
Time |
11:17 |
Sent To |
|
|
| Notes |
| 2017-07-26 11:24:24 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. ELECTRICAL PLAN IS NOT SIGNED AND SEALED BY THE | | | DESIGN PROFESSIONAL. PLAN IS REQUIRED TO BE SIGNED AND | | | SEALED BY A DESIGN PROFESSIONAL OR THE ELECTRICAL | | | CONTRACTOR QUALIFIER. FS 471.003(2)(H); 471.025; FBC | | | 107.2.1 | | | 2. PROVIDE NOTE THAT THE SMOKE/CO ALARMS WILL BE | | | INTERCONNECTED WITH OTHER ALARMS IN RESIDENCE. IF | | | EXISTING ALARMS ARE NOT TO CODE, SHOW AS NEW | | | INSTALLATIONS. FBC R314.3, R314 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-08-06 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2017-08-06 |
Time |
08:33 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2017-07-06 |
Time |
14:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2017-08-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2017-08-03 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2017-08-03 |
Time |
08:07 |
Sent To |
|
|
| Notes |
| 2017-08-03 13:40:25 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT | | | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. | | | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE | | | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN | | | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP | | | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE | | | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN | | | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY | | | IMPACT FEES AT (561) 233-5025. | | | | | | NOTE: I SPOKE WITH MICHELLE AT PALM BEACH COUNTY | | | BUILDING DEPARTMENT. THE OWNER SHALL BRING A COPY OF | | | THE PLANS AND RECEIPT FOR IMPACT FEES PREVIOUSLY PAID | | | WITH THE MU NUMBER ON IT TO THEIR DEPARTMENT FOR REVIEW | | | AND APPROVAL. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-08-06 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2017-08-06 |
Time |
08:33 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2017-08-06 |
Time |
08:18 |
Sent To |
|
|
| Notes |
| 2017-08-06 08:33:37 | PLAN DENIED | | | 1) PAGE 2.1 CALLS FOR A NEW A/C LOCATION. | | | PAGE 7.1 CALLS FOR A NEW WINDOW A/C | | | PLEASE CLARIFY. SECTION 107 FBC | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-07-25 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-07-25 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-07-25 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2017-07-25 15:18:58 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. ONE SET OF PLANS IS MISSING PAGES PLEASE SUBMIT 2 | | | COMPLETE SETS OF PLANS. PERWPB AMEND TO FBC 107.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2017-07-25 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
2017-07-25 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-07-25 13:56:51 | *******************************ZONING | | | NOTE*********************************** | | | | | | THERE WERE ONLY ONE SET OF COMPLETE PLANS THAT WERE | | | STAMPED APPROVED. THE SECOND SET OF PLANS WERE MISSING | | | PAGES. | | | | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | [email protected] | | | 561-822-1449 |
|
|
|