Plan Review Details - Permit 17070176
| Plan Review Stops For Permit 17070176 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-07-14 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-07-14 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-07-14 |
Time |
08:35 |
Sent To |
|
|
| Notes |
| 2017-07-14 08:36:16 | ADDRESS FD COMMENT FOR AN ELECTRICAL PASS JLEAHY |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-07-12 |
|
|
Cont ID |
|
| Sent By |
GJT |
Date |
2017-07-12 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
2017-07-12 |
Time |
|
Sent To |
E |
|
| Notes |
| 2017-07-12 16:14:04 | FAILED | | | | | | 1. 4 X FEE APPLIED FOR NOT SUBMITTING PLANS AND PERMIT | | | FOLLOWING EMERGENCY INSTALLATION. FACP WAS INSTALLED IN | | | OCTOBER 2016 (PER OWNER). PLANS AND PERMIT NOT | | | SUBMITTED UNTIL UNPERMITTED PANEL WAS DISCOVERED ON AN | | | ANNUAL INSPECTION AND OWNER WAS CITED. | | | | | | 2. SUBMITTED PLANS DO NOT DISPLAY THE REQUIRED | | | INFORMATION FOR PLAN REVIEW OR INSPECTION. - NFPA 72 | | | 4.5.1.1 | | | | | | 3. AS PER NFPA 72 4.5.1.1 - NUMBER AND LOCATIONS OF | | | PULL STATIONS? NUMBER, LOCATIONS, AND CANDELLAS OF | | | NOTIFICATION APPLIANCES? NUMBER AND LOCATIONS OF TAMPER | | | SWITCHES? NUMBER AND LOCATIONS OF WATER FLOW SWITCHES? | | | NUMBER OF FLOORS OF BUILDING TO WHICH THE FIRE ALARM | | | SYSTEM IS INSTALLED? IS THE FIRE ALARM SYSTEM LOCAL OR | | | REMOTELY MONITORED? ETC. | | | | | | 4. REGARDLESS OF ANY EXISTING DEVICES THE ENTIRE SYSTEM | | | MUST NOW COMPY WITH THE CURRENT CODE INCLUDING 75DB AT | | | PILLOW TOP DUE TO THE INSTALL OF A NEW FACP. - FLORIDA | | | ADMINSTRATIVE RULE 69A-48.002 | | | | | | SENT TO ELECTRICAL. GJT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-07-14 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-07-14 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-07-06 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2017-07-07 09:42:13 | ROUTED TO FIRE INBOX |
|
|
|