Plan Review Details - Permit 17070175
| Plan Review Stops For Permit 17070175 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-07-14 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-07-14 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-07-14 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2017-07-14 08:43:30 | ADDRESS FD COMMENTS FOR AN ELECTRICAL PASS JLEAHY |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2017-11-01 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2017-11-01 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2017-11-01 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2017-11-01 16:08:56 | PERMIT # 17070175 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FAILED COMMENTS: | | | | | | PER CONVERSATION WITH JESSICA OF JW FIRE: THE SCOPE WAS | | | BEING CHANGED FROM "REPLACE" TO "REPAIR", WITH AN | | | UNDERSTANDING THAT THE PANEL WAS NOT TO BE PHYSICALLY | | | REMOVED FROM IT'S LOCATION, NOR WERE ANY DEVICES TO BE | | | REMOVED OR ADDED. | | | HOWEVER, AFTER SPEAKING WITH INSPECTOR TELFAIR, IT WAS | | | DETERMINED THAT THIS PERMIT APPLICATION WAS A RESULT OF | | | AN ANNUAL FIRE INSPECTION THAT WAS CONDUCTED IN APRIL | | | 2017. DURING THIS INSPECTION THE INSPECTOR NOTICED THAT | | | THE PANEL AT THIS ADDRESS WAS NEW AND AFTER CONDUCTING | | | SOME RESEARCH IT WAS DETERMINED THAT THE PANEL WAS | | | REPLACED/INSTALLED WITHOUT A PERMIT. | | | | | | AT THIS TIME, THE PERMIT STATUS REMAINS AS A FAIL UNTIL | | | THE MATTER IS RESOLVED. ALL OF THE ORIGINAL COMMENTS | | | UNDER THE PLAN REVIEW CONDUCTED ON 7/12/17 REMAIN AND | | | SHALL BE COMPLIED IN ORDER TO RECEIVE APPROVAL FOR THIS | | | PERMIT. | | | | | | INSPECTOR TELFAIR CAN BE REACHED AT [email protected] / | | | 561-804-4753. | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-07-12 |
|
|
Cont ID |
|
| Sent By |
GJT |
Date |
2017-07-12 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
2017-07-12 |
Time |
|
Sent To |
E |
|
| Notes |
| 2017-07-12 16:24:15 | FAILED | | | | | | 1. SUBMITTED PLANS DO NOT DISPLAY THE REQUIRED | | | INFORMATION FOR PLAN REVIEW OR INSPECTION. - NFPA 72 | | | 4.5.1.1 | | | | | | 2. AS PER NFPA 72 4.5.1.1 - NUMBER AND LOCATIONS OF | | | PULL STATIONS? NUMBER, LOCATIONS, AND CANDELLAS OF | | | NOTIFICATION APPLIANCES? NUMBER AND LOCATIONS OF TAMPER | | | SWITCHES? NUMBER AND LOCATIONS OF WATER FLOW SWITCHES? | | | NUMBER OF FLOORS OF BUILDING TO WHICH THE FIRE ALARM | | | SYSTEM IS INSTALLED? IS THE FIRE ALARM SYSTEM LOCAL OR | | | REMOTELY MONITORED? ETC. | | | | | | 3. REGARDLESS OF ANY EXISTING DEVICES THE ENTIRE SYSTEM | | | MUST NOW COMPY WITH THE CURRENT CODE INCLUDING 75DB AT | | | PILLOW TOP DUE TO THE INSTALL OF A NEW FACP. - FLORIDA | | | ADMINSTRATIVE RULE 69A-48.002 | | | | | | SENT TO ELECTRICAL. GJT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-07-14 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-07-14 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-07-06 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2017-07-07 09:42:52 | ROUTED TO FIRE INBOX |
|
|
|