Plan Review Details - Permit 17070091
Plan Review Stops For Permit 17070091
Review Stop G GAS REVIEW
Rev No 5 Status F Date 2018-01-10 Cont ID  
Sent By tklarge Date 2018-01-10 Time 06:48 Rev Time 0.00
Received By tklarge Date 2018-01-10 Time 06:01 Sent To  
Notes
2018-01-10 06:47:551) THE GAS PLAN NOTES THE TOTAL BTU LOAD ON THE SYSTEM
 AS 310,108 BTU'S. PLEASE REFER TO THE MANUFACTURER'S
 SPECIFICATIONS FOR THE APPLIANCES. THE BTU LOAD OF
 310,108 IS INCORRECT.
 EXISTING STOVE: 6 BURNERS AT 18,000 BTU'S PER BURNER =
 108,000 BTU'S
 GAS DRYER: 20,000 BTU'S
 WATER HEATER: 40,000 BTU'S
 POOL HEATER: 250,000 BTU'S
  
 108,000 + 20,000 + 40,000 + 250,000 = 418,0000 BTU'S.
 DO THE MATH.
 2) THE GAS TABLE THAT HAS BEEN SUBMITTED IS NOT
 ACCEPTABLE. THIS TABLE IS NOT FROM A RECOGNIZED
 STANDARD AND DOES NOT LIST THE TYPE OF PIPE. PIPING
 SHALL BE SIZED PER THE 2014 FBC-FUEL GAS CODE.
 3) THE DISTANCE OF THE FURTHEST GAS OUTLET FROM THE GAS
 METER IS SHOWN AS 76 FEET ON THE GAS PLAN. ALL GAS
 PIPING SHALL BE SIZED USING THE 80 FEET DISTANCE COLUMN
 IN THE GAS CODE. BASED ON TABLE 402.4 (2) IN THE GAS
 CODE FOR SCHEDULE 40 METALLIC PIPE, THE MINIMUM SIZE
 PIPE AT THE POUTLET OF THE GAS METER SHALL BE 1 1/4
 INCHES.
 4) THE MINIMUM SIZE PIPE FOR THE CSST TO THE POOL
 HEATER SHALL BE 1 1/4" WITH AN EHD OF 39 IN ACCORDANCE
 WITH THE 2014 FBC-FUEL GAS TABLE 402.4 (15). A 1 INCH
 CSST LINE IS UNDERSIZED AND CANNOT BE USED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2017-12-28 Cont ID  
Sent By tklarge Date 2017-12-28 Time 05:16 Rev Time 0.00
Received By tklarge Date 2017-12-28 Time 04:14 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2017-12-20 Cont ID  
Sent By thunt Date 2017-12-20 Time 14:16 Rev Time 0.00
Received By thunt Date 2017-12-20 Time 13:50 Sent To  
Notes
2017-12-20 13:58:3612/20/2017 3RD GAS REVIEW**DENIED**
  
 COMMENTS FROM LAST REVIEW STILL NOT ADDRESS. NEW
 COMMENTS ADDED FOR NEW CSST REVISION AND DRYER THAT IS
 NEW AND NOT EXISTING. IT IS ADVISED THAT THE GAS
 QUALIFIER CONTACT THIS PLAN EXAMINER TO SET UP A
 MEETING EITHER AT CITY HALL ON ON JOB IN ORDER TO
 EXPEDITE AND ADDRESS THE COMMENTS
  
  
 1) PROVIDE ALL SIZING TABLES BEING USED FOR A MATERIAL
 BOTH NEW AND EXISTING IF ANY LEFT AND IT MUST SHOW
 PRESSURE DROP AND SPECIFIC GRAVITY FGC 402.3. SUBMITTED
 SIZING CHART IS MISSING ALL OF THIS INFORMATION.SUBMIT
 TWO COPIES OF THE APPLICABLE SIZING TABLES USED TO SIZE
 THE GAS SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS
 SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS
 SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS. 401.4,
 401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2014 FBC-RES. SEC. G2412.4, G2412.8, G2413.1,
 G2413.2, & G2413.3
  
 2) NOT ABLE TO READ DRYER INSTALLTION MANUAL AND
 EXHAUST CFM. BUILDING PLAN SHOWS ALL NEW GAS EQUIPMENT.
 SUBMIT MANUFACTURERS SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1
  
 3) RUNNING OF THE CSST IN A PVC SLEEVE UNDER A BUILDING
 IS A LAST RESORT AND THE PLUMBING/ GAS CODE OFFICIAL
 WILL ONLY ALLOW THE THE PROPOSED DRAWING IF NO OTHER
 SAFE MEANS OF RUNNING A NEW LINE EXIST. FROM THIS PLANS
 EXAMINER SITE VISITS P.E PIPING CAN BE RAN ALONG THE
 SIDE OF BUILDING AROUND THE BACK TO THE PROPOSED
 LOCATION OF THE POOL HEATER. FGC 104.1
  
 4) ) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED
 GAS APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. FGC
 SEC.304.9.3 OR FBCR G2407.9.3
  
 5) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1, 614.5 (CLOTHES DRYERS) OR
 2014 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-10-16 Cont ID  
Sent By thunt Date 2017-10-16 Time 14:54 Rev Time 0.00
Received By thunt Date 2017-10-16 Time 14:54 Sent To  
Notes
2017-10-16 15:07:2910/16/17 GAS 2ND REVIEW**DENED***
  
 1) PROVIDE ALL SIZING TABLES BEING USED FOR A MATERIAL
 BOTH NEW AND EXISTING IF ANY LEFT AND IT MUST SHOW
 PRESSURE DROP AND SPECIFIC GRAVITY FGC 402.3. SUBMITTED
 SIZING CHART IS MISSING THIS INFORMATION
  
 2) BUILDING PLAN SHOWS ALL NEW GAS EQUIPMENT. SUBMIT
 MANUFACTURER?S SPECIFICATION SHEETS / INSTALLATION
 MANUAL FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS CODE
 SEC. 402.2, AND 301.3 OR 2014 FBC-RES. SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1
  
 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES TO INCLUDE WATER HEATER AS NOW IT WILL BE IN
 A CONFINED SPACE INSTEAD OF AN OPEN GARAGE. WHERE
 COMBUSTION AIR IS PROVIDED BY THE BUILDING?S MECHANICAL
 VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE
 SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. FGC SEC.304.9.3 OR FBCR
 G2407.9.3.
  
  
 PLEASE BE ADVISED A STOP WORK ORDER WAS ISSUED ON
 08/22/17 FOR A NEW GAS SYSTEM ON THIS HOME. MOST OF IF
 NOT ALL THE PIPING I WAS ABLE TO SEE HAS BEEN REPLACED
 AND WILL BE INSPECTED BASED OFF THE 2014 FLORIDA GAS
 CODE
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-07-11 Cont ID  
Sent By tklarge Date 2017-07-11 Time 09:27 Rev Time 0.00
Received By tklarge Date 2017-07-11 Time 06:48 Sent To  
Notes
2017-07-11 09:27:251.)SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
 2.) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED AND
 ALL PIPE SIZES INCLUDING THE EXISTING GAS SYSTEM., WPB
 AMENDMENTS TO FBC SEC.107.2.1, 107.3.5.3 (12), 2014
 FBC-FUEL GAS SEC. 402.
 3.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
 4) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3.
 5) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE
 ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED,
 THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. FGC SECS. 401.4, 401.8, 402.1, 402.2,
 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2,
 G2413.3.
 6) SUBMIT A SITE PLAN SHOWING THE LOCATION OF THE POOL
 HEATER ON THE PROPERTY.WPB AMEND. TO FBC SEC.
 107.3.5.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-01-10 Cont ID  
Sent By tklarge Date 2018-01-10 Time 06:48 Rev Time 0.00
Received By tklarge Date 2018-01-10 Time 06:01 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-12-28 Cont ID  
Sent By tklarge Date 2017-12-28 Time 05:16 Rev Time 0.00
Received By tklarge Date 2017-12-28 Time 04:14 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-12-20 Cont ID  
Sent By thunt Date 2017-12-20 Time 14:42 Rev Time 0.00
Received By thunt Date 2017-12-08 Time 13:09 Sent To I
Notes
2017-12-11 13:09:49RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-16 Cont ID  
Sent By thunt Date 2017-10-16 Time 15:07 Rev Time 0.00
Received By thunt Date 2017-10-13 Time 10:50 Sent To  
Notes
2017-10-16 10:50:21RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-11 Cont ID  
Sent By tklarge Date 2017-07-11 Time 09:28 Rev Time 0.00
Received By tklarge Date 2017-07-05 Time 10:21 Sent To  
Notes
2017-07-10 10:21:33PLUMB -$5000