Plan Review Details - Permit 17070066
Plan Review Stops For Permit 17070066
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-22 Cont ID  
Sent By jwitmer Date 2017-08-22 Time 10:56 Rev Time 0.00
Received By jwitmer Date 2017-08-21 Time 14:40 Sent To  
Notes
2017-08-22 10:56:442014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070066
 ADD: 2310 FLORIDA AVENUE
 CONT: FIVE CONSTRUCTION
 TEL: 561-762-7272
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 11/ 2017
 ACTION: DENIED
  
 1-3) COMPLIED.
  
 4) SHEET A-102:
 4A)(1) 2ND REQUEST. PLEASE SHOW THE ACCESSIBLE ROUTE
 FROM THE PARKING LOT TO THE LIFT PART OF THE LOADING
 DOCK APPROACH PLATFORM. PLEASE NOTE THAT THE LOADING
 DOCK IS PART OF A SERVICE ENTRANCE, AN ENTRANCE
 INTENDED PRIMARILY FOR DELIVERY OF GOODS OR SERVICES.
 PLEASE REVIEW THE DEFINITION FOR PUBLIC ENTRANCE.
 AN ENTRANCE THAT IS NOT A SERVICE ENTRANCE OR A
 RESTRICTED ENTRANCE. SHOW HOW A PERMANENT AND SAFE
 ACCESSIBLE ENTRANCE FOR THE PUBLIC CAN BE MAINTAINED.
  
 4A)(2) BUILDING PROVISO: MANUFACTURERS CUT SHEETS WILL
 BE REQUIRED, THE PLATFORM LIFT THAT WILL NEED TO MEET
 THE REQUIREMENTS OF THE 2014 FBC-ACCESS. CODE 410.
 (1-6) AND ASME A 18.1 OR A LULA LIFT AND REQUIRED TO
 MEET THE REQUIREMENTS IN THE ACCESS. CODE 408. (1-4.8)
 AND ASME A 17.1.
  
 4B-4C) COMPLIED.
  
 4D) SEMI-COMPLIED. DETAIL A IS OF A GUARDRAIL SYSTEM.
 SHEET A-102 SHOWS A GUARDRAIL DETAIL BUT THE NOTES FOR
 HEIGHT AND CODE SECTION PROVIDED ARE FOR HANDRAILS
 FBC-B 1012.2. GUARDRAIL HEIGHT IS LISTED UNDER
 2014 FBC-B 1013.3.
  
 5) SHEET A-301:
 5A) 2ND REQUEST. THE RESPONSE NARRATIVE INDICATES JOIST
 LOADING AND OCCUPANCY FOR ENCLOSED MEZZANINE SEE
 SECTION A/A-301. SHEET A301 DETAIL A INDICATES AN
 ENCLOSED OFFICE 1ST FLOOR, AND AN OPEN MEZZANINE LEVEL
 OCCUPANCY S-2 LOW HAZARD.
 5A)(1)PLEASE PROVIDE THE 2ND FLOOR WALL ENCLOSE IF THE
 MEZZANINE IS TO BE CONSIDERED ENCLOSED. SEE FBC-B
 505.2.3. PLEASE PROVIDE THE SQUARE FOOTAGE OF MEZZANINE
 AND OCCUPANT LOAD? FBC-B TABLE 1004.1.2.
  
 5A)(2) IN NEITHER THE FLOOR PLAN A-101 NOR A-103 IS
 THERE ANY STAIRS TO GAIN ACCESS TO THE MEZZANINE LEVEL.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 5A)(3) SHEET A-103 IT APPEARS TO BE PROVIDING THE LIVE
 AND DEAD LOADS OF THE MEZZANINE FLOOR LOADS BUT IS
 GIVING ROOF LL: 30 PSF AND DL: 20 PSF. IT WOULD APPEAR
 THAT THE DESIGNER OF RECORD IS TAKING VALUES FROM THE
 FBC-B TABLE 2308. 102(2) FOR CEILING JOIST SPANS FOR
 UNINHABITED ATTICS, LIMITED STORAGE 20 PSF. FOR THE
 MEZZANINE LEVEL FOR A STORAGE OCCUPANCY THE DESIGN IS
 EITHER 125 PSF LIGHT STORAGE OR DESIGNED TO 250 PSF
 HEAVY, 2014 FBC-B TABLE 1607.1(31).
  
 5A)(4) PLEASE PROVIDE ENGINEERING CALCULATIONS FOR THE
 MEZZANINE STORAGE, FOR THE SIZE AND SPACING OF FLOOR
 JOIST, BLOCK WALL MOUNTED FLOOR JOIST HANGERS, LEDGER
 AND ANCHORS, AND STRUCTURAL 6 INCH WOOD FRAME (FRT)
 WOOD WALL FOR SPACING, SPECIES AND GRADE OF WOOD. THE
 FLORIDA BUILDING CODE TABLES FOR FLOOR JOIST SPACING,
 AND WEIGHT ARE NOT DESIGNED FOR THE LOADING FOR STORAGE
 OCCUPANCY FLOOR SYSTEMS ABOVE GRADE.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.4.1 GENERAL. WHEN IT IS REQUIRED
 THAT DOCUMENTS BE PREPARED BY A REGISTERED DESIGN
 PROFESSIONAL, THE BUILDING OFFICIAL SHALL BE AUTHORIZED
 TO REQUIRE THE OWNER TO ENGAGE AND DESIGNATE ON THE
 BUILDING PERMIT APPLICATION A REGISTERED DESIGN
 PROFESSIONAL WHO SHALL ACT AS THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE.
  
 5A)(5) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 106.1 LIVE LOADS POSTED. WHERE THE
 LIVE LOADS FOR WHICH EACH FLOOR OR PORTION THEREOF OF A
 COMMERCIAL OR INDUSTRIAL BUILDING IS OR HAS BEEN
 DESIGNED TO EXCEED 50 PSF SUCH
 DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY THE
 OWNER IN THAT PART OF EACH STORY IN WHICH THEY
 APPLY, USING DURABLE SIGNS. IT SHALL BE UNLAWFUL TO
 REMOVE OR DEFACE SUCH NOTICES.
  
 5A)(6) 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A
 CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111
 SHALL NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS,
 REQUIRED BY SECTION 106.1, HAVE BEEN INSTALLED.
  
 5A)(7) THE SHEET A-103 SECTION A SHOWS AN OPEN
 MEZZANINE, IF THIS DETAIL IS CORRECT, THEN PLEASE
 PROVIDE A GUARDRAIL SYSTEM IN COMPLIANCE WITH GUARDRAIL
 HEIGHT IS LISTED UNDER 2014 FBC-B 1013.3.
  
 1ST ROUND OF COMMENTS. THE PLANS INDICATE AN EXISTING
 OFFICE # 1 BUT THE SECTION DOES NOT INDICATE IF THE
 2X10S ARE CEILING JOIST AND LOAD OR IF THEY ARE TO BE
 CONSIDERED AS FLOOR JOIST AND THE LOADING OF THE JOIST?
 ADDITIONAL INFORMATION REQUIRED? PLEASE IDENTIFY IF THE
 AREA ABOVE THE OFFICE IS TO BE AN ENCLOSED A MEZZANINE,
 IF SO THE TYPE OF OCCUPANCY? 107.2.1.3. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 5B) COMPLIED. WALL DETAIL W2/A-501 REMOVED.
  
 5C) SEE COMMENTS 5A COVERED UNDER 5A. PLEASE NOTE THE
 2X10 JOIST ARE SPACED AT 16 INCHES ON CENTER WHEREAS
 THE STEEL STUDS ARE SPACED AT 24 INCHES ON CENTER,
 PLEASE PROVIDE HOW THE LEDGERS ARE GOING TO BE SECURED
 TO A NON-STRUCTURAL STUD. PLEASE ALSO PROVIDE WHAT
 BUCKET WILL BE USED TO ATTACH THE JOIST TO THE
 HORIZONTAL LEDGER AND AT WHAT SPACING THE 2 LEDGERS ARE
 TO BE NAILED TOGETHER. 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 6) COMPLIED.
  
 7) 2ND REQUEST. SUBMITTED A ENGINEERED ALUMINUM WALL
 BRACKET SUPPORT BY FRANK BENNARDO P. E. PLEASE NOTE
 STATED RIGHT ON THE DOCUMENT VALID FOR 1PERMITONLY WITH
 ORIGINAL ENGINEERS SEAL.
 THIS IS NOT A FLORIDA STATE APPROVAL OR MIAMI-DADE NOA.
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 7A) FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE
 DATE 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS
 WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER
 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
  
 7B) 61G15-23.002 SEALS ACCEPTABLE TO THE BOARD. WET
 SEALS, EMBOSSING SEALS AND DIGITALLY CREATED SEALS
 SHALL BE A MINIMUM OF 1-7/8 INCHES IN DIAMETER.
  
 1ST ROUND OF COMMENTS. MECHANICAL SHEET BY COOL WORLD
 SHOWS A NEW CONDENSER MOUNTED ON THE EXTERIOR WALL ON
 WALL BRACKETS, THIS IS NOT SHOWN ON ANY OF THE
 ARCHITECTURAL PLANS. PLEASE INCORPORATE THE DESIGN AND
 PLACEMENT. PLEASE ALSO PROVIDE THE WIND DESIGN CRITERIA
 FOR THE MOUNTING OF THE CONDENSER AND BRACKET.
  
 7C) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THE
 WALL MOUNT BRACKET EITHER ON THE STRUCTURAL
 SPECIFICATION SHEET G-004 AND OR M-3. 2014 FBC-B
 1603.1.4 WIND DESIGN DATA. THE FOLLOWING INFORMATION
 RELATED TO WIND LOADS SHALL BE SHOWN, REGARDLESS OF
 WHETHER WIND LOADS GOVERN THE DESIGN OF THE LATERAL
 FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 7.2. RISK CATEGORY.
 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 7D) ONCE THE KNOWN ELEVATION OF THE WALL MOUNTED A/C
 CONDENSER AND BRACKETS THEN COMPLIANCE WITH THE
 FOLLOWING CODE SECTIONS MAY OR MAY NOT BE REQUIRED.
 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR
 ELEVATED STRUCTURES. ACCESS.
  
 8) SEMI-COMPLIED. SEE 7A & 7B. 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS
  
 9) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-11 Cont ID  
Sent By jwitmer Date 2017-07-11 Time 12:37 Rev Time  
Received By jwitmer Date 2017-07-11 Time 07:45 Sent To  
Notes
2017-07-11 12:33:372014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070066
 ADD: 2310 FLORIDA AVENUE
 CONT: FIVE CONSTRUCTION
 TEL: 561-762-7272
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 11/ 2017
 ACTION: DENIED
  
 1) SHEET G003:
 1A) DETAIL A- SIGNAGE, DEPICTION SHOWS CHARACTERS BUT
 DOES NOT INCLUDE BRAILLE. PLEASE REVIEW THE
 REQUIREMENTS OF THE 2014 FBC-ACCESS. CODE SECTION
 703.4.1 HEIGHT ABOVE FINISH FLOOR OR GROUND.
 TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES
 (1220 MM) MINIMUM ABOVE THE FINISH FLOOR OR GROUND
 SURFACE, MEASURED FROM THE BASELINE OF THE LOWEST
 TACTILE CHARACTER AND 60 INCHES (1525 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE HIGHEST TACTILE CHARACTER.
  
 1B) DETAILS B & C ARE FOR TOILET PAPER DISPENSERS.
 PLEASE PROVIDE COMPLIANCE FOR THE LOCATION OF THE
 DISPENSER BOTH HEIGHT AND THE DISTANCE IN FRONT OF THE
 WATER CLOSET WILL NEED TO SHOW COMPLIANCE WITH
 2014 FBC-ACCESS. CODE 604.9.6 DISPENSERS. TOILET PAPER
 DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 14
 INCHES MINIMUM AND 19 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR. THERE SHALL BE A CLEARANCE OF 11/2 INCHES (38
 MM) MINIMUM BELOW THE GRAB BAR. DISPENSERS SHALL NOT BE
 OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES NOT ALLOW
 CONTINUOUS PAPER FLOW.
  
 2) SHEET G004:
 2A) UNDER THE HEADING OF GENERAL NOTES INTERIOR
 PARTITIONS THE COMMENT REFERENCES R-4403.7.7 THE
 RESIDENTIAL CODE, PLEASE USE THE 2014 FBC-BUILDING CODE
 FOR ALL CODE REFERENCES. 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED, REFERENCING THE WRONG CODE.
  
 2B) UNDER THE HEADING GENERAL NOTES FOR BOTH WOOD AND
 TRUSSES. FOR ANY WOOD THAT IS TO BE USED FOR ANY
 STRUCTURAL ELEMENTS, PLEASE REFER TO FIRE RETARDANT
 TREATED WOOD, THIS BUILDING IS CLASSIFIED AS
 CONSTRUCTION TYPE IIB. PLEASE REVIEW TO FBC-B
 603.1.1.1.3 FIRE-RETARDANT-TREATED WOOD SHALL BE
 PERMITTED IN ROOF CONSTRUCTION, INCLUDING GIRDERS,
 TRUSSES, FRAMING AND DECKING. ALSO REVIEW SHEET A-301
 FOR 2X10 JOIST THAT STATE 2X10 P.T.
  
 3) SHEET A-101 INDICATES A PORTION OF A MEZZANINE BEING
 REMOVED BUT THE PLANS ARE SILENT TO WHERE THERE IS
 STILL APPORTION OF THE MEZZANINE LEFT OVER OFFICE # 1
 AND NONE OF THE PLANS INDICATE HOW TO GAIN ACCESS TO
 THE MEZZANINE AREA THAT IS LEFT. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. THIS REVIEW CYCLE A THOROUGH
 REVIEW COULD NOT BE COMPLETED AND ADDITIONAL AND OR NEW
 COMMENTS MAY OCCUR ON SUBSEQUENT REVIEWS.
  
 4) SHEET A-102:
 4A) THIS SHEET INDICATES THE INSTALLATION OF A NEW
 LIFT. THE PLANS NEED TO MAKE IT CLEAR IF THIS IS A
 PLATFORM LIFT THAT WILL NEED TO MEET THE REQUIREMENTS
 OF THE ACCESS. CODE 410. (1-6) AND ASME A 18.1 OR A
 LULA LIFT AND REQUIRED TO MEET THE REQUIREMENTS IN THE
 ACCESS. CODE 408. (1-4.8) AND ASME A 17.1.
  
 4B) THE LOADING BAY SHOWS NEW STAIRS, PLEASE PROVIDE
 THE DESIGN MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS
 TABLE 1607.1.(30). SHEET A-502 ALSO SHOWS A STAIR
 SECTION BUT NO LOADING INFORMATION. PLEASE ALSO NOTE
 THE STRINGER INDICATES A 2X12. MUST BE FIRE RETARDANT
 TREATED WOOD. FBC-B 603.1.1.1.3
  
 4C) THE PLANS INDICATE THIS IS A LOADING DOCK, PLEASE
 SHOW WHAT SECTIONS WILL BE REMOVALABLE OR WILL THE
 WHOLE LOADING DOCK HAVE GUARDRAILS SURROUNDING THE
 LOADING DOCK. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4D) DETAIL A IS OF A GUARDRAIL SYSTEM. PLEASE CORRECT
 CODE IN AFFECT, WE ARE NO LONGER UNDER THE 2010 CODE
 AND IN ALL 5 NOTES THE CODE REFERENCE AND NUMBERS ARE
 AGAIN THE RESIDENTIAL CODE NOT THE 2014 FBC-B.
  
 5) SHEET A-301:
 5A) THE PLANS INDICATE AN EXISTING OFFICE # 1 BUT THE
 SECTION DOES NOT INDICATE IF THE 2X10S ARE CEILING
 JOIST AND LOAD OR IF THEY ARE TO BE CONSIDERED AS FLOOR
 JOIST AND THE LOADING OF THE JOIST? ADDITIONAL
 INFORMATION REQUIRED? PLEASE IDENTIFY IF THE AREA ABOVE
 THE OFFICE IS TO BE AN ENCLOSED MEZZANINE, IF SO THE
 TYPE OF OCCUPANCY? 107.2.1.3. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 5B) THERE IS A WALL DETAIL W2/A-501 THAT SHOWS THE WALL
 GOING ALL THE WAY TO THE UNDERSIDE OF THE OF THE ROOF
 DECK. THIS WALL IS CLASSIFIED AS UL DESIGN U465 A 1 HR.
 FIRE RATING NON-BEARING WALL. PLEASE NOTE THIS WALL
 SHOWS NOT ONLY DRYWALL CEILING LOADS BUT 2X10 JOIST,
 NOT KNOWN IF ACTING AS FLOOR JOIST OR CEILING JOIST.
 THE LIMITING HEIGHT REQUIREMENT FOR NON-STRUCTURAL
 INTERIOR WALL, 3 ? INCH STEEL STUD, 25 GAUGE, AT 24
 INCHES ON CENTER WITH A 5 PSF AND L/120 IS LIMITED TO
 13 FOOT 9 INCHES.
  
 5C) PLEASE NOTE THE 2X10 JOIST ARE SPACED AT 16 INCHES
 ON CENTER WHEREAS THE STEEL STUDS ARE SPACED AT 24
 INCHES ON CENTER, PLEASE PROVIDE HOW THE LEDGERS ARE
 GOING TO BE SECURED TO A NON-STRUCTURAL STUD. PLEASE
 ALSO PROVIDE WHAT BUCKET WILL BE USED TO ATTACH THE
 JOIST TO THE HORIZONTAL LEDGER AND AT WHAT SPACING THE
 2 LEDGERS ARE TO BE NAILED TOGETHER. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) SHEET A-502 IN THE BOTTOM LEFT SECTION OF THE PAGE
 METHOD OF COMPLIANCE NOTES, FBC 602.1 & 602.1.1 ARE
 BOTH NOTES PULLED FROM THE RESIDENTIAL CODE, NOT
 APPLICABLE UNDER THE 2014 FBC-B. PLEASE CORRECT CODE
 LANGUAGE!!!! 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 7) MECHANICAL SHEET BY COOL WORLD SHOWS A NEW CONDENSER
 MOUNTED ON THE EXTERIOR WALL ON WALL BRACKETS, THIS IS
 NOT SHOWN ON ANY OF THE ARCHITECTURAL PLANS. PLEASE
 INCORPORATE THE DESIGN AND PLACEMENT. PLEASE ALSO
 PROVIDE THE WIND DESIGN CRITERIA FOR THE MOUNTING OF
 THE CONDENSER AND BRACKET.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 7.2. RISK CATEGORY.
  
 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 8) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS
  
 9) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-23 Cont ID  
Sent By jpearson Date 2017-08-23 Time 16:11 Rev Time 0.00
Received By jpearson Date 2017-08-23 Time 16:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-17 Cont ID  
Sent By jpearson Date 2017-07-17 Time 13:40 Rev Time 0.00
Received By jpearson Date 2017-07-17 Time 13:40 Sent To  
Notes
2017-07-17 13:52:31CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. SEVERAL MECHANICAL COMPONENTS DESCRIBED IN
 SUBMITTALS AND THE MECHANICAL PLAN ARE NOT SHOWN ON THE
 ELECTRICAL PLAN. PROVIDE DETAILS OF ALL WIRING ON
 ELECTRICAL PLAN. FBC 107.2.1, 107.3.5
 2. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-30 Cont ID  
Sent By scaldero Date 2017-08-30 Time 14:45 Rev Time 0.00
Received By scaldero Date 2017-08-30 Time 14:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-07-10 Cont ID  
Sent By scaldero Date 2017-07-10 Time 14:00 Rev Time 0.00
Received By scaldero Date 2017-07-10 Time 14:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-13 Cont ID  
Sent By lmarchan Date 2017-09-13 Time 13:21 Rev Time 0.00
Received By lmarchan Date 2017-08-16 Time 14:57 Sent To  
Notes
2017-08-17 14:57:51B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-18 Cont ID  
Sent By gjohnson Date 2017-07-18 Time 08:34 Rev Time 0.00
Received By gjohnson Date 2017-07-05 Time 13:49 Sent To  
Notes
2017-07-07 13:49:17B19

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-07-11 Cont ID  
Sent By jwitmer Date 2017-07-11 Time 08:57 Rev Time 0.00
Received By jwitmer Date 2017-07-11 Time 08:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-29 Cont ID  
Sent By ccole Date 2017-08-29 Time 16:38 Rev Time 0.00
Received By ccole Date 2017-08-29 Time 16:38 Sent To  
Notes
2017-08-29 17:06:412ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17070066
 8/29/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 BASED ON A MEETING WITH THE CONTRACTOR- FIVE
 CONSTRUCTION- AND A REPRESENTATIVE FROM KANTHAN DESIGN
 CORPORATION THAT OCCURRED ON 8/29/17 PRIOR TO THIS
 REVIEW, IT APPEARS THAT THE RESUBMITTED PLANS FOR THE
 PROPOSED PROJECT ARE MISREPRESENTING THE INTENDED USE
 AND OCCUPANCY OF THE SPACE WHICH WAS REVEALED AT THE
 MEETING TO BE A GYMNASIUM OR EXERCISE FACILITY.
 GYMNASIUM
  
 ARE CLASSIFIED AS ASSEMBLY-3 OCCUPANCIES PER SECTION
 303.4 FBC-14 BUILDING, HOWEVER THE PROJECT IS SPECIFIED
 AS F-1 ON SHEET LS-101. THE FOLLOWING REVIEW COMMMENTS
 ARE BASED ON THIS NEW INFORMATION AS IT APPLIES TO THE
 RESUBMITTED PLANS.
  
 1) SHEET M-2: REVISE THE OUTDOOR AIR CALCULATIONS TO
 INCLUDE THE GYMNASIUM OR EXERCISE AREA- SEE TABLE
 403.3. INDICATE HOW VENTILATION WILL BE PROVIDED FOR
 GYMNASIUM OCCUPANTS.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 PROPOSED SYSTEM IN THE OFFICE- SECTION 312.1.
  
 3) THE ASHRAE 90.1-2010- PRESCRIPTIVE COMPLIANCE OPTION
 ENERGY SUBMITTAL FOR THE OFFICE DOES NOT LIST ANY DATA
 FOR THE THERMAL ENVELOPE OF THE SPACE, IN TERMS OF R OR
 U-VALUES FOR THE ROOF, WALLS, FENESTRATION, DOORS, OR
 FLOOR- SEE SECTION 5.5 AND TABLE 5.5-1 ASHRAE
 90.1-2010.
  
 4) REFER TO SECTION 309.1 AND PROVIDE A SPACE HEATING
 SYSTEMS OR SYSTEMS CAPABLE OF MAINTAINING A MINIMUM
 INDOOR TEMPERATURE OF 68 DEGREES FAHRENHEIT.
  
 5) CONCERNING THE AC WALL BRACKET, PLEASE SEE BUILDING
 REVIEW COMMENT #7 DATED 8/22/17.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-14 Cont ID  
Sent By ccole Date 2017-07-14 Time 12:04 Rev Time 0.00
Received By ccole Date 2017-07-14 Time 11:50 Sent To  
Notes
2017-07-14 12:48:011ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070066
 7/14/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED AC PLAN MUST BEAR THE SIGNATURE OF THE
 PERSON WHO PREPARED THE DESIGN- SECTION 107.2.1 WPB
 AMENDMENTS TO THE FBC.
  
 2) THE MODEL NUMBER OF THE AIR HANDLER UNT ON THE
 SUBMITTED AHRI CERTIFICATE DOES NOT MATCH THE MODEL
 NUMBER ON THE AC PLAN- PLEASE CORRECT.
  
 3) WIND LOAD ENGINEERING AND SUBMITTAL OF A FL. PRODUCT
 APPROVAL OR A MIAMI-DADE NOA ARE REQUIRED FOR
 INSTALLATION OF THE CU WALL BRACKET- SECTION 301.5.
  
 4) THE LOCATION OF THE OUTSIDE AIR INTAKE IS NOT IN
 COMPLAINCE WITH SECTION 401.4 (2) WHICH REQUIRES A 10
 FT. CLEARANCE DISTANCE TO THE LOADING/DRIVE AREA.
 ADDITIONALLY PLEASE SEE SECTION 401.5 FOR O/A OPENING
 PROTECTION COMPLIANCE.
  
 5) PROVIDE A MOTORIZED OR GRAVITY DAMPER FOR THE O/A
 INTAKE DUCT- SEE SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION.
  
 6) PROVIDE AIR HANDLER INSTALLATION DETAILS AND CLARIFY
 HOW ACCESS WILL BE PROVIDED TO THE UNIT PER SECTION
 306.1- PLEASE NOTE THE MAIN PLANS SHOW A DRYWALL
 CEILING WHICH MEANS AN ACCESS PANEL WILL HAVE TO BE
 INSTALLED. SHOW THE PANEL LOCATION AND PROVIDE
 CONSTRUCTION DETAILS.
  
 7) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL
 DETAILS- SECTION 307.
  
 8) PROVIDE DUCT HANGING AND CONNECTION DETAILS PER
 SMACNA STANDARDS.
  
 9) PROVIDE EXHAUST FAN EQUIPMENT SCHEDULES.
  
 10) THE ENGINEER OF RECORD WHO PREPARED THE ENERGY
 CALCULATIONS MUST COMPLETE THE MANDATORY REQUIREMENTS
 CHECKLIST ON PAGE 7 OF THE ENERGYGAUGE COMPLIANCE
 SUBMITTAL.
  
 11) THERE IS A SUBMITTAL FOR A GREE DUCTLESS AC SYSTEM.
 PLEASE CLARIFY WHERE THIS SYSTEM WILL BE INSTALLED AND
 PROVIDE A PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-28 Cont ID  
Sent By gjohnson Date 2017-08-28 Time 13:47 Rev Time 0.00
Received By gjohnson Date 2017-08-25 Time 10:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-18 Cont ID  
Sent By gjohnson Date 2017-07-18 Time 08:15 Rev Time 0.00
Received By gjohnson Date 2017-07-17 Time 17:59 Sent To  
Notes
2017-07-18 08:34:051ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. PER FBC ACC 604.7
  
 2. THE GRAB BARS ARE TO BE MEASURED FROM FINISHED FLOOR
 TO THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4
  
 3. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL. PER FBC ACC 604.5.1
  
 4. THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM)
 LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF THE
 WATER CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND
 24 INCHES (610 MM) MINIMUM ON THE OTHER SIDE. PER FBC
 ACC 604.5.2
  
 5. THE CENTERLINE OF THE WATER CLOSET SHALL BE 16
 INCHES (405 MM) MINIMUM TO 18 INCHES (455 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION, PER FBC ACC 604.2
  
 6. SHT. P-101 SANITARY RISER THE WC IN THE MENS
 BATHROOM IS NOT VENTED. PER FBC PL 901.2.1
  
 7. SHT. P-101 ON THE SANITARY RISER THE MOPSINK AND
 WATER COOLER SHALL CONNECT TO THE BUILDING DRAIN DOWN
 STREAM OF THE BATHROOM GROUPS. PER FBC PL 912.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  