Plan Review Details - Permit 17070063
Plan Review Stops For Permit 17070063
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-07-27 Cont ID  
Sent By shill Date 2018-07-27 Time 06:03 Rev Time 0.00
Received By shill Date 2018-07-27 Time 06:03 Sent To  
Notes
2018-07-27 06:04:27RE: PREVIOUS COMMENT - PROJECT IS NOW COMPLETE, SO NO
 FURTHER NEED FOR VERSIONING
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-03-17 Cont ID  
Sent By shill Date 2018-03-17 Time 15:40 Rev Time 0.00
Received By shill Date 2018-03-17 Time 15:40 Sent To  
Notes
2018-03-17 15:41:39****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 WHEN RESUBMITTING, ALL PLAN REVISIONS ARE TO BE
 UPLOADED TO THE "DRAWINGS" FOLDER, NOT THE "SUPPORTING
 DOCS".
  
 SEE COMMENT FROM THE SIGNATURE REVIEW:
  
 DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. FS471, 481.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-01-16 Cont ID  
Sent By shill Date 2018-01-16 Time 07:17 Rev Time 0.00
Received By shill Date 2018-01-16 Time 07:17 Sent To  
Notes
2018-01-16 07:18:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 WHEN RESUBMITTING, ALL PLAN REVISIONS ARE TO BE
 UPLOADED TO THE "DRAWINGS" FOLDER, NOT THE "SUPPORTING
 DOCS".
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-01-16 Cont ID  
Sent By shill Date 2017-08-02 Time 16:58 Rev Time 0.00
Received By shill Date 2017-08-02 Time 16:58 Sent To  
Notes
2018-01-16 07:11:06CHANGED REVIEW FROM "P" TO "F" AS 3RD BUILDING REVIEW
 FAILED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-21 Cont ID  
Sent By shill Date 2017-07-20 Time 07:10 Rev Time 0.00
Received By shill Date 2017-07-20 Time 07:10 Sent To  
Notes
2017-07-21 07:19:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PURPOSE OF SUBMITTAL NOT CLEAR. WAS THIS REQUESTED
 BY A CITY INSPECTOR? GENERALLY, THIS TYPE OF
 DOCUMENTATION IS PROVIDED AT INSPECTION.
  
 IF THIS WAS REQUESTED TO BE SUBMITTED TO PLAN REVIEW BY
 ONE OF THE CITY INSPECTORS, PLEASE PROVIDE A
 TRANSMITTAL LETTER EXPLAINING THE ISSUE AND WHAT IT IS
 THAT NEEDS CODE RELATED REVIEW.
  
 ALSO PROVIDE A LOCATION PLAN. PROVIDE A COPY OF THE
 PLAN PAGE WHICH INCLUDES THE PROPOSED FIREPLACES. IF
 THIS WAS NOT ON THE PERMITTED PLANS, HAVE PLANS REVISED
 AND SUBMIT AS A REVISION.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-11-28 Cont ID  
Sent By wjolin Date 2017-11-28 Time 11:43 Rev Time 0.00
Received By wjolin Date 2017-11-28 Time 11:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-07-26 Cont ID  
Sent By wjolin Date 2017-07-26 Time 13:42 Rev Time 0.00
Received By wjolin Date 2017-07-26 Time 11:42 Sent To  
Notes
2017-07-26 13:42:21410 DATURA STREET - FIREPLACE APPLIANCES
 PERMIT #17070063
 MASTER #16020194
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIREPLACE APPLIANCES WERE PREVIOUSLY NOT APPROVED ON
 THE MASTER BUILDING PERMIT #16020194 ON 03/17/16,
 06/23/16 AND 08/31/16.
  
 OPEN FLAME OR UNPROTECTED HEAT PRODUCING DEVICES THAT
 MAY CAUSE BURNS TO OCCUPANTS WILL NOT BE ACCEPTED BY
 THIS OFFICE.
  
 NO PLANS SUBMITTED SHOWING THE PROPOSED LOCATION OF THE
 APPLIANCES.
  
 OUTDOOR FIREPLACE EQUIPMENT SUBMITTAL INDICATES THE
 APPLIANCE SHALL NOT BE INSTALLED IN A LOCATION
 SUSCEPTIBLE TO SALTWATER CORROSION OR HIGH WINDS. BOTH
 THESE CONDITIONS EXIST AT THIS ADDRESS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2017-12-04 Cont ID  
Sent By tklarge Date 2017-12-04 Time 14:23 Rev Time 0.00
Received By tklarge Date 2017-12-01 Time 14:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-03-17 Cont ID  
Sent By shill Date 2018-03-17 Time 15:43 Rev Time 0.00
Received By shill Date 2018-02-22 Time 16:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-01-08 Time   Rev Time 0.00
Received By lmarchan Date 2017-12-20 Time 09:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-12-04 Cont ID  
Sent By tklarge Date 2017-12-04 Time 06:42 Rev Time 0.00
Received By tklarge Date 2017-11-17 Time 07:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-17 Cont ID  
Sent By cpuell Date 2017-08-17 Time 09:39 Rev Time 0.00
Received By cpuell Date 2017-07-25 Time 14:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-07-24 Time   Rev Time 0.00
Received By cpuell Date 2017-07-14 Time 12:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2018-03-09 Cont ID  
Sent By ccole Date 2018-03-09 Time 15:55 Rev Time 0.00
Received By ccole Date 2018-03-09 Time 15:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2018-01-08 Cont ID  
Sent By ccole Date 2018-01-08 Time 08:16 Rev Time 0.00
Received By ccole Date 2018-01-05 Time 17:13 Sent To I
Notes
2018-01-08 08:34:064TH REVIEW FBC-2014 MECHANICAL
 PERMIT #17070063
 1/8/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE PAGE 8 OF THE SPARK FIRE RIBBON
 INSTALLATION INSTRUCTIONS WHICH PROVIDES ENCLOSURE
 DIAGRAMS AND REQUIRED OPENINGS THAT THE ARCHITECTURAL
 AND STRUCTURAL ENCLOSURE DRAWINGS ARE NOT CONSISTENT
 WITH.
  
 2) PLEASE NOTE THAT THE RESPONSE LETTER FROM ALLIANCE
 RESIDENTIAL BUILDERS CERTIFYING THE STRUCTURAL DESIGN
 FOR THE FIREPLACE INSTALLATION IS NOT ACCEPTABLE
 BECAUSE THE CONTRACTOR HAS NO AUTHORITY UNDER FLORIDA
 STATUTES TO CERTIFY SUCH AN INSTALLATION. CERTIFICATION
 MUST BE PROVIDED BY THE ENGINEER OF RECORD. PLEASE
 REVIEW AND REVISE THE DRAWINGS TO BE COMPLIANT WITH THE
 MANUFACTURER'S
  
 SPECIFICATIONS, AND PROVIDE A LETTER FROM THE EOR TO
 CERTIFY THE INSTALLATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-11-29 Cont ID  
Sent By ccole Date 2017-11-29 Time 14:06 Rev Time 0.00
Received By ccole Date 2017-11-29 Time 14:06 Sent To  
Notes
2017-11-29 14:11:233RD REVIEW FBC-2014 MECHANICAL , FUEL GAS
 PERMIT #17070063
 11/29/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ENGINEERING IS REQUIRED FOR INSTALLATION OF THE
 ROOFTOP FIREPLACE. REFER TO SECTION 301.10 WIND
 RESISTANCE FBC-14 FUEL GAS.
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-09 Cont ID  
Sent By ccole Date 2017-08-09 Time 10:26 Rev Time 0.00
Received By ccole Date 2017-08-09 Time 10:20 Sent To  
Notes
2017-08-09 10:28:392ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17070063
 8/9/17
  
 PLAN REVIEW RESULTS: DENIED
  
 1) THE 1ST REVIEW COMMENTS STILL EXIST. I AM REPRINTING
 THEM BELOW:
  
 1ST REVIEW FBC-2014 MECHANICAL/FUEL GAS
 PERMIT #17070063
 7/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE UNVENTED GAS FIREPLACE SHALL NOT BE INSTALLED IN
 THE CLUBHOUSE PER SECTION 621.4 FBC-14 FUEL GAS.
 ADDITIONAL INFORMATION FOR BOTH THE INDOOR AND OUTDOOR
 ROOM HEATERS AND FIREPLACE BOXES IS REQUIRED. SEE
 BELOW:
  
 621.4 PROHIBITED LOCATIONS.
 UNVENTED ROOM HEATERS SHALL NOT BE INSTALLED WITHIN
 OCCUPANCIES IN GROUPS A, E AND I. THE LOCATION OF
 UNVENTED ROOM HEATERS SHALL ALSO COMPLY WITH SECTION
 303.3.
  
 621.5 ROOM OR SPACE VOLUME.
 THE AGGREGATE INPUT RATING OF ALL UNVENTED APPLIANCES
 INSTALLED IN A ROOM OR SPACE SHALL NOT EXCEED 20 BTU/H
 PER CUBIC FOOT (207 W/M3) OF VOLUME OF SUCH ROOM OR
 SPACE. WHERE THE ROOM OR SPACE IN WHICH THE APPLIANCES
 ARE INSTALLED IS DIRECTLY CONNECTED TO ANOTHER ROOM OR
 SPACE BY A DOORWAY, ARCHWAY OR OTHER OPENING OF
 COMPARABLE SIZE THAT CANNOT BE CLOSED, THE VOLUME OF
 SUCH ADJACENT ROOM OR SPACE SHALL BE PERMITTED TO BE
 INCLUDED IN THE CALCULATIONS.
  
 621.6 OXYGEN-DEPLETION SAFETY SYSTEM.
 UNVENTED ROOM HEATERS SHALL BE EQUIPPED WITH AN
 OXYGEN-DEPLETION-SENSITIVE SAFETY SHUTOFF SYSTEM. THE
 SYSTEM SHALL SHUT OFF THE GAS SUPPLY TO THE MAIN AND
 PILOT BURNERS WHEN THE OXYGEN IN THE SURROUNDING
 ATMOSPHERE IS DEPLETED TO THE PERCENT CONCENTRATION
 SPECIFIED BY THE MANUFACTURER, BUT NOT LOWER THAN 18
 PERCENT. THE SYSTEM SHALL NOT INCORPORATE FIELD
 ADJUSTMENT MEANS CAPABLE OF CHANGING THE SET POINT AT
 WHICH THE SYSTEM ACTS TO SHUT OFF THE GAS SUPPLY TO THE
 ROOM HEATER.
  
 621.7 UNVENTED DECORATIVE ROOM HEATERS.
 AN UNVENTED DECORATIVE ROOM HEATER SHALL NOT BE
 INSTALLED IN A FACTORY-BUILT FIREPLACE UNLESS THE
 FIREPLACE SYSTEM HAS BEEN SPECIFICALLY TESTED, LISTED
 AND LABELED FOR SUCH USE IN ACCORDANCE WITH UL 127.
  
 621.7.1 VENTLESS FIREBOX ENCLOSURES.
 VENTLESS FIREBOX ENCLOSURES USED WITH UNVENTED
 DECORATIVE ROOM HEATERS SHALL BE LISTED AS COMPLYING
 WITH ANSI Z21.91.
  
 2) PLEASE NOTE ALL SUBMITTALS FOR MECHANICAL AND FUEL
 GAS BURNING APPLIANCES SHALL BEAR THE SHOP DRAWING
 STAMP AND SIGNATURE OF THE ENGINEER OF RECORD
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-21 Cont ID  
Sent By ccole Date 2017-07-21 Time 17:28 Rev Time 0.00
Received By ccole Date 2017-07-21 Time 17:20 Sent To  
Notes
2017-07-21 17:32:081ST REVIEW FBC-2014 MECHANICAL/FUEL GAS
 PERMIT #17070063
 7/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE UNVENTED GAS FIREPLACE SHALL NOT BE INSTALLED IN
 THE CLUBHOUSE PER SECTION 621.4 FBC-14 FUEL GAS.
 ADDITIONAL INFORMATION FOR BOTH THE INDOOR AND OUTDOOR
 ROOM HEATERS AND FIREPLACE BOXES IS REQUIRED. SEE
 BELOW:
  
 621.4 PROHIBITED LOCATIONS.
 UNVENTED ROOM HEATERS SHALL NOT BE INSTALLED WITHIN
 OCCUPANCIES IN GROUPS A, E AND I. THE LOCATION OF
 UNVENTED ROOM HEATERS SHALL ALSO COMPLY WITH SECTION
 303.3.
  
 621.5 ROOM OR SPACE VOLUME.
 THE AGGREGATE INPUT RATING OF ALL UNVENTED APPLIANCES
 INSTALLED IN A ROOM OR SPACE SHALL NOT EXCEED 20 BTU/H
 PER CUBIC FOOT (207 W/M3) OF VOLUME OF SUCH ROOM OR
 SPACE. WHERE THE ROOM OR SPACE IN WHICH THE APPLIANCES
 ARE INSTALLED IS DIRECTLY CONNECTED TO ANOTHER ROOM OR
 SPACE BY A DOORWAY, ARCHWAY OR OTHER OPENING OF
 COMPARABLE SIZE THAT CANNOT BE CLOSED, THE VOLUME OF
 SUCH ADJACENT ROOM OR SPACE SHALL BE PERMITTED TO BE
 INCLUDED IN THE CALCULATIONS.
  
 621.6 OXYGEN-DEPLETION SAFETY SYSTEM.
 UNVENTED ROOM HEATERS SHALL BE EQUIPPED WITH AN
 OXYGEN-DEPLETION-SENSITIVE SAFETY SHUTOFF SYSTEM. THE
 SYSTEM SHALL SHUT OFF THE GAS SUPPLY TO THE MAIN AND
 PILOT BURNERS WHEN THE OXYGEN IN THE SURROUNDING
 ATMOSPHERE IS DEPLETED TO THE PERCENT CONCENTRATION
 SPECIFIED BY THE MANUFACTURER, BUT NOT LOWER THAN 18
 PERCENT. THE SYSTEM SHALL NOT INCORPORATE FIELD
 ADJUSTMENT MEANS CAPABLE OF CHANGING THE SET POINT AT
 WHICH THE SYSTEM ACTS TO SHUT OFF THE GAS SUPPLY TO THE
 ROOM HEATER.
  
 621.7 UNVENTED DECORATIVE ROOM HEATERS.
 AN UNVENTED DECORATIVE ROOM HEATER SHALL NOT BE
 INSTALLED IN A FACTORY-BUILT FIREPLACE UNLESS THE
 FIREPLACE SYSTEM HAS BEEN SPECIFICALLY TESTED, LISTED
 AND LABELED FOR SUCH USE IN ACCORDANCE WITH UL 127.
  
 621.7.1 VENTLESS FIREBOX ENCLOSURES.
 VENTLESS FIREBOX ENCLOSURES USED WITH UNVENTED
 DECORATIVE ROOM HEATERS SHALL BE LISTED AS COMPLYING
 WITH ANSI Z21.91.
  
 2) PLEASE NOTE ALL SUBMITTALS FOR MECHANICAL AND FUEL
 GAS BURNING APPLIANCES SHALL BEAR THE SHOP DRAWING
 STAMP AND SIGNATURE OF THE ENGINEER OF RECORD
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2017-12-04 Cont ID  
Sent By tklarge Date 2017-12-04 Time 06:42 Rev Time 0.00
Received By tklarge Date 2017-12-01 Time 15:02 Sent To  
Notes
2017-12-01 15:03:35NO NOTES THIS PERMIT.

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-16 Cont ID  
Sent By gjohnson Date 2017-08-16 Time 17:31 Rev Time 0.00
Received By gjohnson Date 2017-08-14 Time 16:30 Sent To  
Notes
2017-08-16 17:34:001ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
  
 1) THE UNVENTED GAS FIREPLACE SHALL NOT BE INSTALLED IN
 THE CLUBHOUSE PER SECTION 621.4 FBC-14 FUEL GAS.
 ADDITIONAL INFORMATION FOR BOTH THE INDOOR AND OUTDOOR
 ROOM HEATERS AND FIREPLACE BOXES IS REQUIRED. SEE
 BELOW:
  
 621.4 PROHIBITED LOCATIONS.
 UNVENTED ROOM HEATERS SHALL NOT BE INSTALLED WITHIN
 OCCUPANCIES IN GROUPS A, E AND I. THE LOCATION OF
 UNVENTED ROOM HEATERS SHALL ALSO COMPLY WITH SECTION
 303.3.
  
 621.5 ROOM OR SPACE VOLUME.
 THE AGGREGATE INPUT RATING OF ALL UNVENTED APPLIANCES
 INSTALLED IN A ROOM OR SPACE SHALL NOT EXCEED 20 BTU/H
 PER CUBIC FOOT (207 W/M3) OF VOLUME OF SUCH ROOM OR
 SPACE. WHERE THE ROOM OR SPACE IN WHICH THE APPLIANCES
 ARE INSTALLED IS DIRECTLY CONNECTED TO ANOTHER ROOM OR
 SPACE BY A DOORWAY, ARCHWAY OR OTHER OPENING OF
 COMPARABLE SIZE THAT CANNOT BE CLOSED, THE VOLUME OF
 SUCH ADJACENT ROOM OR SPACE SHALL BE PERMITTED TO BE
 INCLUDED IN THE CALCULATIONS.
  
 621.7 UNVENTED DECORATIVE ROOM HEATERS.
 AN UNVENTED DECORATIVE ROOM HEATER SHALL NOT BE
 INSTALLED IN A FACTORY-BUILT FIREPLACE UNLESS THE
 FIREPLACE SYSTEM HAS BEEN SPECIFICALLY TESTED, LISTED
 AND LABELED FOR SUCH USE IN ACCORDANCE WITH UL 127.
  
 621.7.1 VENTLESS FIREBOX ENCLOSURES.
 VENTLESS FIREBOX ENCLOSURES USED WITH UNVENTED
 DECORATIVE ROOM HEATERS SHALL BE LISTED AS COMPLYING
 WITH ANSI Z21.91.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2018-03-17 Cont ID  
Sent By shill Date 2018-03-17 Time 15:43 Rev Time 0.00
Received By shill Date 2018-03-17 Time 15:43 Sent To  
Notes
2018-03-17 15:43:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ARCHITECTURAL AND STRUCTURAL SHEETS WERE SUBMITTED AS
 "SUPPORTING DOCS". THEY SHOULD BE IN "DRAWINGS" AND
 SHOULD BE SIGNED AND SEALED, FS471.
  
  
 MECH ELECTRONIC SEALS AND SIGNATURES NOT REQUIRED. SHOP
 DRAWINGS STAMPS AND DRAWINGS FOR REFERENCE ONLY.
 CCOLE- 1/8/18

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-01-16 Cont ID  
Sent By shill Date 2018-01-16 Time 07:19 Rev Time 0.00
Received By shill Date 2018-01-16 Time 07:19 Sent To  
Notes
2018-01-16 07:20:37****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ARCHITECTURAL AND STRUCTURAL SHEETS WERE SUBMITTED AS
 "SUPPORTING DOCS". THEY SHOULD BE IN "DRAWINGS" AND
 SHOULD BE SIGNED AND SEALED, FS471.
  
  
2018-01-08 08:36:25MECH ELECTRONIC SEALS AND SIGNATURES NOT REQUIRED. SHOP
 DRAWINGS STAMPS AND DRAWINGS FOR REFERENCE ONLY.
 CCOLE- 1/8/18

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2017-12-04 Cont ID  
Sent By tklarge Date 2017-12-04 Time 06:45 Rev Time 0.00
Received By tklarge Date 2017-12-04 Time 06:45 Sent To  
Notes
2017-07-21 17:33:18SUBMITTAL DOCUMENTS- NO DIG/SIGS, NO SHOP DRAWING
 STAMPS/ CCOLE 7/21/17
2017-07-21 07:20:40NO SIGNED AND SEALED BUILDING DOCUMENTS SUBMITTED; N
 STATUS FOR BUILDING S.HILL
  