| Plan Review Stops For Permit 17070063 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2018-07-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-27 |
Time |
06:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-27 |
Time |
06:03 |
Sent To |
|
|
| Notes |
| 2018-07-27 06:04:27 | RE: PREVIOUS COMMENT - PROJECT IS NOW COMPLETE, SO NO | | | FURTHER NEED FOR VERSIONING | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2018-03-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-03-17 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-03-17 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2018-03-17 15:41:39 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FROM PREVIOUS LIST: | | | | | | WHEN RESUBMITTING, ALL PLAN REVISIONS ARE TO BE | | | UPLOADED TO THE "DRAWINGS" FOLDER, NOT THE "SUPPORTING | | | DOCS". | | | | | | SEE COMMENT FROM THE SIGNATURE REVIEW: | | | | | | DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS. FS471, 481. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2018-01-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-01-16 |
Time |
07:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-01-16 |
Time |
07:17 |
Sent To |
|
|
| Notes |
| 2018-01-16 07:18:16 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | WHEN RESUBMITTING, ALL PLAN REVISIONS ARE TO BE | | | UPLOADED TO THE "DRAWINGS" FOLDER, NOT THE "SUPPORTING | | | DOCS". | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-01-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-02 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-02 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2018-01-16 07:11:06 | CHANGED REVIEW FROM "P" TO "F" AS 3RD BUILDING REVIEW | | | FAILED. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-07-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-07-20 |
Time |
07:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-07-20 |
Time |
07:10 |
Sent To |
|
|
| Notes |
| 2017-07-21 07:19:19 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. PURPOSE OF SUBMITTAL NOT CLEAR. WAS THIS REQUESTED | | | BY A CITY INSPECTOR? GENERALLY, THIS TYPE OF | | | DOCUMENTATION IS PROVIDED AT INSPECTION. | | | | | | IF THIS WAS REQUESTED TO BE SUBMITTED TO PLAN REVIEW BY | | | ONE OF THE CITY INSPECTORS, PLEASE PROVIDE A | | | TRANSMITTAL LETTER EXPLAINING THE ISSUE AND WHAT IT IS | | | THAT NEEDS CODE RELATED REVIEW. | | | | | | ALSO PROVIDE A LOCATION PLAN. PROVIDE A COPY OF THE | | | PLAN PAGE WHICH INCLUDES THE PROPOSED FIREPLACES. IF | | | THIS WAS NOT ON THE PERMITTED PLANS, HAVE PLANS REVISED | | | AND SUBMIT AS A REVISION. | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-11-28 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2017-11-28 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2017-11-28 |
Time |
11:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-07-26 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2017-07-26 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2017-07-26 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2017-07-26 13:42:21 | 410 DATURA STREET - FIREPLACE APPLIANCES | | | PERMIT #17070063 | | | MASTER #16020194 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FIREPLACE APPLIANCES WERE PREVIOUSLY NOT APPROVED ON | | | THE MASTER BUILDING PERMIT #16020194 ON 03/17/16, | | | 06/23/16 AND 08/31/16. | | | | | | OPEN FLAME OR UNPROTECTED HEAT PRODUCING DEVICES THAT | | | MAY CAUSE BURNS TO OCCUPANTS WILL NOT BE ACCEPTED BY | | | THIS OFFICE. | | | | | | NO PLANS SUBMITTED SHOWING THE PROPOSED LOCATION OF THE | | | APPLIANCES. | | | | | | OUTDOOR FIREPLACE EQUIPMENT SUBMITTAL INDICATES THE | | | APPLIANCE SHALL NOT BE INSTALLED IN A LOCATION | | | SUSCEPTIBLE TO SALTWATER CORROSION OR HIGH WINDS. BOTH | | | THESE CONDITIONS EXIST AT THIS ADDRESS. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2017-12-04 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-12-04 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-12-01 |
Time |
14:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2018-03-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-03-17 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-02-22 |
Time |
16:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-01-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-12-20 |
Time |
09:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-12-04 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-12-04 |
Time |
06:42 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-11-17 |
Time |
07:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-08-17 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-08-17 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-07-25 |
Time |
14:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-07-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-07-14 |
Time |
12:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2018-03-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-03-09 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-03-09 |
Time |
15:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2018-01-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-01-08 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-01-05 |
Time |
17:13 |
Sent To |
I |
|
| Notes |
| 2018-01-08 08:34:06 | 4TH REVIEW FBC-2014 MECHANICAL | | | PERMIT #17070063 | | | 1/8/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE SEE PAGE 8 OF THE SPARK FIRE RIBBON | | | INSTALLATION INSTRUCTIONS WHICH PROVIDES ENCLOSURE | | | DIAGRAMS AND REQUIRED OPENINGS THAT THE ARCHITECTURAL | | | AND STRUCTURAL ENCLOSURE DRAWINGS ARE NOT CONSISTENT | | | WITH. | | | | | | 2) PLEASE NOTE THAT THE RESPONSE LETTER FROM ALLIANCE | | | RESIDENTIAL BUILDERS CERTIFYING THE STRUCTURAL DESIGN | | | FOR THE FIREPLACE INSTALLATION IS NOT ACCEPTABLE | | | BECAUSE THE CONTRACTOR HAS NO AUTHORITY UNDER FLORIDA | | | STATUTES TO CERTIFY SUCH AN INSTALLATION. CERTIFICATION | | | MUST BE PROVIDED BY THE ENGINEER OF RECORD. PLEASE | | | REVIEW AND REVISE THE DRAWINGS TO BE COMPLIANT WITH THE | | | MANUFACTURER'S | | | | | | SPECIFICATIONS, AND PROVIDE A LETTER FROM THE EOR TO | | | CERTIFY THE INSTALLATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2017-11-29 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-11-29 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-11-29 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2017-11-29 14:11:23 | 3RD REVIEW FBC-2014 MECHANICAL , FUEL GAS | | | PERMIT #17070063 | | | 11/29/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) ENGINEERING IS REQUIRED FOR INSTALLATION OF THE | | | ROOFTOP FIREPLACE. REFER TO SECTION 301.10 WIND | | | RESISTANCE FBC-14 FUEL GAS. | | | APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL | | | BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES | | | DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING | | | CODE, BUILDING. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-08-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-08-09 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-08-09 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2017-08-09 10:28:39 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17070063 | | | 8/9/17 | | | | | | PLAN REVIEW RESULTS: DENIED | | | | | | 1) THE 1ST REVIEW COMMENTS STILL EXIST. I AM REPRINTING | | | THEM BELOW: | | | | | | 1ST REVIEW FBC-2014 MECHANICAL/FUEL GAS | | | PERMIT #17070063 | | | 7/21/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE UNVENTED GAS FIREPLACE SHALL NOT BE INSTALLED IN | | | THE CLUBHOUSE PER SECTION 621.4 FBC-14 FUEL GAS. | | | ADDITIONAL INFORMATION FOR BOTH THE INDOOR AND OUTDOOR | | | ROOM HEATERS AND FIREPLACE BOXES IS REQUIRED. SEE | | | BELOW: | | | | | | 621.4 PROHIBITED LOCATIONS. | | | UNVENTED ROOM HEATERS SHALL NOT BE INSTALLED WITHIN | | | OCCUPANCIES IN GROUPS A, E AND I. THE LOCATION OF | | | UNVENTED ROOM HEATERS SHALL ALSO COMPLY WITH SECTION | | | 303.3. | | | | | | 621.5 ROOM OR SPACE VOLUME. | | | THE AGGREGATE INPUT RATING OF ALL UNVENTED APPLIANCES | | | INSTALLED IN A ROOM OR SPACE SHALL NOT EXCEED 20 BTU/H | | | PER CUBIC FOOT (207 W/M3) OF VOLUME OF SUCH ROOM OR | | | SPACE. WHERE THE ROOM OR SPACE IN WHICH THE APPLIANCES | | | ARE INSTALLED IS DIRECTLY CONNECTED TO ANOTHER ROOM OR | | | SPACE BY A DOORWAY, ARCHWAY OR OTHER OPENING OF | | | COMPARABLE SIZE THAT CANNOT BE CLOSED, THE VOLUME OF | | | SUCH ADJACENT ROOM OR SPACE SHALL BE PERMITTED TO BE | | | INCLUDED IN THE CALCULATIONS. | | | | | | 621.6 OXYGEN-DEPLETION SAFETY SYSTEM. | | | UNVENTED ROOM HEATERS SHALL BE EQUIPPED WITH AN | | | OXYGEN-DEPLETION-SENSITIVE SAFETY SHUTOFF SYSTEM. THE | | | SYSTEM SHALL SHUT OFF THE GAS SUPPLY TO THE MAIN AND | | | PILOT BURNERS WHEN THE OXYGEN IN THE SURROUNDING | | | ATMOSPHERE IS DEPLETED TO THE PERCENT CONCENTRATION | | | SPECIFIED BY THE MANUFACTURER, BUT NOT LOWER THAN 18 | | | PERCENT. THE SYSTEM SHALL NOT INCORPORATE FIELD | | | ADJUSTMENT MEANS CAPABLE OF CHANGING THE SET POINT AT | | | WHICH THE SYSTEM ACTS TO SHUT OFF THE GAS SUPPLY TO THE | | | ROOM HEATER. | | | | | | 621.7 UNVENTED DECORATIVE ROOM HEATERS. | | | AN UNVENTED DECORATIVE ROOM HEATER SHALL NOT BE | | | INSTALLED IN A FACTORY-BUILT FIREPLACE UNLESS THE | | | FIREPLACE SYSTEM HAS BEEN SPECIFICALLY TESTED, LISTED | | | AND LABELED FOR SUCH USE IN ACCORDANCE WITH UL 127. | | | | | | 621.7.1 VENTLESS FIREBOX ENCLOSURES. | | | VENTLESS FIREBOX ENCLOSURES USED WITH UNVENTED | | | DECORATIVE ROOM HEATERS SHALL BE LISTED AS COMPLYING | | | WITH ANSI Z21.91. | | | | | | 2) PLEASE NOTE ALL SUBMITTALS FOR MECHANICAL AND FUEL | | | GAS BURNING APPLIANCES SHALL BEAR THE SHOP DRAWING | | | STAMP AND SIGNATURE OF THE ENGINEER OF RECORD | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-07-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-07-21 |
Time |
17:28 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-07-21 |
Time |
17:20 |
Sent To |
|
|
| Notes |
| 2017-07-21 17:32:08 | 1ST REVIEW FBC-2014 MECHANICAL/FUEL GAS | | | PERMIT #17070063 | | | 7/21/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE UNVENTED GAS FIREPLACE SHALL NOT BE INSTALLED IN | | | THE CLUBHOUSE PER SECTION 621.4 FBC-14 FUEL GAS. | | | ADDITIONAL INFORMATION FOR BOTH THE INDOOR AND OUTDOOR | | | ROOM HEATERS AND FIREPLACE BOXES IS REQUIRED. SEE | | | BELOW: | | | | | | 621.4 PROHIBITED LOCATIONS. | | | UNVENTED ROOM HEATERS SHALL NOT BE INSTALLED WITHIN | | | OCCUPANCIES IN GROUPS A, E AND I. THE LOCATION OF | | | UNVENTED ROOM HEATERS SHALL ALSO COMPLY WITH SECTION | | | 303.3. | | | | | | 621.5 ROOM OR SPACE VOLUME. | | | THE AGGREGATE INPUT RATING OF ALL UNVENTED APPLIANCES | | | INSTALLED IN A ROOM OR SPACE SHALL NOT EXCEED 20 BTU/H | | | PER CUBIC FOOT (207 W/M3) OF VOLUME OF SUCH ROOM OR | | | SPACE. WHERE THE ROOM OR SPACE IN WHICH THE APPLIANCES | | | ARE INSTALLED IS DIRECTLY CONNECTED TO ANOTHER ROOM OR | | | SPACE BY A DOORWAY, ARCHWAY OR OTHER OPENING OF | | | COMPARABLE SIZE THAT CANNOT BE CLOSED, THE VOLUME OF | | | SUCH ADJACENT ROOM OR SPACE SHALL BE PERMITTED TO BE | | | INCLUDED IN THE CALCULATIONS. | | | | | | 621.6 OXYGEN-DEPLETION SAFETY SYSTEM. | | | UNVENTED ROOM HEATERS SHALL BE EQUIPPED WITH AN | | | OXYGEN-DEPLETION-SENSITIVE SAFETY SHUTOFF SYSTEM. THE | | | SYSTEM SHALL SHUT OFF THE GAS SUPPLY TO THE MAIN AND | | | PILOT BURNERS WHEN THE OXYGEN IN THE SURROUNDING | | | ATMOSPHERE IS DEPLETED TO THE PERCENT CONCENTRATION | | | SPECIFIED BY THE MANUFACTURER, BUT NOT LOWER THAN 18 | | | PERCENT. THE SYSTEM SHALL NOT INCORPORATE FIELD | | | ADJUSTMENT MEANS CAPABLE OF CHANGING THE SET POINT AT | | | WHICH THE SYSTEM ACTS TO SHUT OFF THE GAS SUPPLY TO THE | | | ROOM HEATER. | | | | | | 621.7 UNVENTED DECORATIVE ROOM HEATERS. | | | AN UNVENTED DECORATIVE ROOM HEATER SHALL NOT BE | | | INSTALLED IN A FACTORY-BUILT FIREPLACE UNLESS THE | | | FIREPLACE SYSTEM HAS BEEN SPECIFICALLY TESTED, LISTED | | | AND LABELED FOR SUCH USE IN ACCORDANCE WITH UL 127. | | | | | | 621.7.1 VENTLESS FIREBOX ENCLOSURES. | | | VENTLESS FIREBOX ENCLOSURES USED WITH UNVENTED | | | DECORATIVE ROOM HEATERS SHALL BE LISTED AS COMPLYING | | | WITH ANSI Z21.91. | | | | | | 2) PLEASE NOTE ALL SUBMITTALS FOR MECHANICAL AND FUEL | | | GAS BURNING APPLIANCES SHALL BEAR THE SHOP DRAWING | | | STAMP AND SIGNATURE OF THE ENGINEER OF RECORD | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2017-12-04 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-12-04 |
Time |
06:42 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-12-01 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2017-12-01 15:03:35 | NO NOTES THIS PERMIT. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-08-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-08-16 |
Time |
17:31 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-08-14 |
Time |
16:30 |
Sent To |
|
|
| Notes |
| 2017-08-16 17:34:00 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | | | | 1) THE UNVENTED GAS FIREPLACE SHALL NOT BE INSTALLED IN | | | THE CLUBHOUSE PER SECTION 621.4 FBC-14 FUEL GAS. | | | ADDITIONAL INFORMATION FOR BOTH THE INDOOR AND OUTDOOR | | | ROOM HEATERS AND FIREPLACE BOXES IS REQUIRED. SEE | | | BELOW: | | | | | | 621.4 PROHIBITED LOCATIONS. | | | UNVENTED ROOM HEATERS SHALL NOT BE INSTALLED WITHIN | | | OCCUPANCIES IN GROUPS A, E AND I. THE LOCATION OF | | | UNVENTED ROOM HEATERS SHALL ALSO COMPLY WITH SECTION | | | 303.3. | | | | | | 621.5 ROOM OR SPACE VOLUME. | | | THE AGGREGATE INPUT RATING OF ALL UNVENTED APPLIANCES | | | INSTALLED IN A ROOM OR SPACE SHALL NOT EXCEED 20 BTU/H | | | PER CUBIC FOOT (207 W/M3) OF VOLUME OF SUCH ROOM OR | | | SPACE. WHERE THE ROOM OR SPACE IN WHICH THE APPLIANCES | | | ARE INSTALLED IS DIRECTLY CONNECTED TO ANOTHER ROOM OR | | | SPACE BY A DOORWAY, ARCHWAY OR OTHER OPENING OF | | | COMPARABLE SIZE THAT CANNOT BE CLOSED, THE VOLUME OF | | | SUCH ADJACENT ROOM OR SPACE SHALL BE PERMITTED TO BE | | | INCLUDED IN THE CALCULATIONS. | | | | | | 621.7 UNVENTED DECORATIVE ROOM HEATERS. | | | AN UNVENTED DECORATIVE ROOM HEATER SHALL NOT BE | | | INSTALLED IN A FACTORY-BUILT FIREPLACE UNLESS THE | | | FIREPLACE SYSTEM HAS BEEN SPECIFICALLY TESTED, LISTED | | | AND LABELED FOR SUCH USE IN ACCORDANCE WITH UL 127. | | | | | | 621.7.1 VENTLESS FIREBOX ENCLOSURES. | | | VENTLESS FIREBOX ENCLOSURES USED WITH UNVENTED | | | DECORATIVE ROOM HEATERS SHALL BE LISTED AS COMPLYING | | | WITH ANSI Z21.91. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2018-03-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-03-17 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-03-17 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2018-03-17 15:43:46 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | ARCHITECTURAL AND STRUCTURAL SHEETS WERE SUBMITTED AS | | | "SUPPORTING DOCS". THEY SHOULD BE IN "DRAWINGS" AND | | | SHOULD BE SIGNED AND SEALED, FS471. | | | | | | | | | MECH ELECTRONIC SEALS AND SIGNATURES NOT REQUIRED. SHOP | | | DRAWINGS STAMPS AND DRAWINGS FOR REFERENCE ONLY. | | | CCOLE- 1/8/18 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2018-01-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-01-16 |
Time |
07:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-01-16 |
Time |
07:19 |
Sent To |
|
|
| Notes |
| 2018-01-16 07:20:37 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | ARCHITECTURAL AND STRUCTURAL SHEETS WERE SUBMITTED AS | | | "SUPPORTING DOCS". THEY SHOULD BE IN "DRAWINGS" AND | | | SHOULD BE SIGNED AND SEALED, FS471. | | | | | | | | 2018-01-08 08:36:25 | MECH ELECTRONIC SEALS AND SIGNATURES NOT REQUIRED. SHOP | | | DRAWINGS STAMPS AND DRAWINGS FOR REFERENCE ONLY. | | | CCOLE- 1/8/18 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2017-12-04 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-12-04 |
Time |
06:45 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-12-04 |
Time |
06:45 |
Sent To |
|
|
| Notes |
| 2017-07-21 17:33:18 | SUBMITTAL DOCUMENTS- NO DIG/SIGS, NO SHOP DRAWING | | | STAMPS/ CCOLE 7/21/17 | | 2017-07-21 07:20:40 | NO SIGNED AND SEALED BUILDING DOCUMENTS SUBMITTED; N | | | STATUS FOR BUILDING S.HILL | | | |
|
|