Plan Review Details - Permit 17070040
Plan Review Stops For Permit 17070040
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2017-10-03 Cont ID  
Sent By rmcdouga Date 2017-10-03 Time 13:50 Rev Time 0.00
Received By rmcdouga Date 2017-10-03 Time 13:50 Sent To  
Notes
2017-07-03 13:35:16PLEASE CHECK WITH MIKE ORIO

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-10-03 Cont ID  
Sent By cthroop Date 2017-10-03 Time 15:25 Rev Time 0.00
Received By cthroop Date 2017-10-03 Time 15:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-24 Cont ID  
Sent By cthroop Date 2017-08-24 Time 16:52 Rev Time 0.00
Received By cthroop Date 2017-08-24 Time 14:07 Sent To M
Notes
2017-08-24 16:54:24BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUE ADJUSTED BASED ON ICC BUILDING VALUATION DATA.
 2. SOILS REPORT REQUIRED. 2ND REQUEST.
  
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-21 Cont ID  
Sent By cthroop Date 2017-07-21 Time 15:40 Rev Time 0.00
Received By cthroop Date 2017-07-21 Time 15:16 Sent To  
Notes
2017-07-21 15:42:12BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. STATED VALUE OF $173,615.00 APPEARS LOW. BASED ON
 THE INTERNATIONAL CODE COUNCIL (ICC) BUILDING VALUATION
 TABLE, A TYPE 5-B SFR HAS A PER SQ. FT. VALUE OF 113.85
 FOR UNDER AIR AND $45.09 FOR MISC. (FRONT AND REAR
 PORCH) FOR A TOTAL VALUATION OF $276,657.00.
 2. PROVIDE A SOILS REPORT BY A FLORIDA LICENSED
 GEOTECHNICAL ENGINEER.
 3. PALM BEACH COUNTY IMPACT FEES ARE REQUIRED.
  
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 - VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
  
 DEFINED FIELDS / US C-404 TYPE
 INTERNAL USE ONLY:
  
 US C-404 TYPE ? 101-NEW SFR, DETACHED
  
 CONSTRUCTION TYPE - 14-V-B-5TH ED TYPE V-B
 UNITS - 1
 FLOORS - 1
 BEDROOMS - 4
 ROOMS/TOTAL - 13
 BATHROOMS - 3
 SQ. FT. ? STRUCTURE - 2671
 SQ. FT. ? LIVABLE - 2272
 SQ. FT. ? ROOF - 2671
  
 ZONING ? N/A (USE AS PLACEHOLDER FOR VERTICAL DATUM)
  
 SETBACKS FRONT (ENTER VERTICAL DATA) NGVD29 ? 15.5'
 SETBACKS BACK (ENTER PROPOSED 1ST FLOOR ELEVATION) ?
 SETBACKS LEFT (ENTER PROPOSED 2ND FLOOR ELEVATION) ?
  
 OCC LOAD ? 45
 PROPOSED USE ? SFR
 SPRINKLER SYSTEM INSTALLED ? NO
 SPRINKLER REQUIRED ? NO
  
 BUILDING CODE ? FL 2014
 OCC CLASS ? 5TH ED RESIDENTIAL R3
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-14 Cont ID  
Sent By jpearson Date 2017-08-14 Time 15:49 Rev Time 0.00
Received By jpearson Date 2017-08-14 Time 15:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-12 Cont ID  
Sent By jpearson Date 2017-07-12 Time 11:18 Rev Time 0.00
Received By jpearson Date 2017-07-12 Time 11:18 Sent To  
Notes
2017-07-12 12:24:39CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. ELECTRICAL PLAN REQUIRED TO BE SIGNED AND SEALED BY
 DESIGN PROFESSIONAL OR THE ELECTRICAL CONTRACTOR
 QUALIFIER. FS 471, FAC61G15-23, FBC 107.3.5
 2. SHOW COMPLIANCE WITH ENERGY CODE FOR LIGHTING: "A
 MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS". A NOTE WILL SUFFICE. FBC EC R404.1
 3. PROVIDE CORRECTED PANEL SCHEDULE. CIRCUIT 22 SHOWS
 AS A SMALL APPLIANCE CIRCUIT, BUT IT IS FEEDING OUTDOOR
 OUTLETS. CIRCUITS 24, 26, AND 30 SHOULD BE AFCI
 PROTECTED CIRCUITS. CIRCUIT 9,11 FOR WATER HEATER
 SHOULD BE A 25 AMP BREAKER. NEC 215.5, 408.4, 408.30,
 422.13; FBC 107.2.1, FBC RE3706.1
 4. WIRE FEEDING INTERIOR PANEL FROM OUTSIDE SERVICE IS
 TOO SMALL. 2/0 COPPER CAN ONLY BE USED WHERE IT FEEDS
 100% OF THE LOAD. PROVIDE CORRECTION. NEC 310.15(B)(7);
 FBC RE3602.2
 5. LIGHT IN MASTER CLOSET IS SHOWN AS BEING ON THE SAME
 CIRCUIT AS THE BATHROOM GFCI OUTLETS, WHICH IS NOT
 PERMITTED PER CODE. PROVIDE CORRECTION. NEC
 210.11(C)(3); FBC RE3703.4
 6. KITCHEN COUNTER OUTLETS SHOW ONLY ONE CIRCUIT (#20).
 CODE REQUIRES MINIMUM OF 2 SMALL APPLIANCE CIRCUITS.
 PROVIDE CORRECTION. NEC 210.11(C)(1), 210.52(B)(2); FBC
 RE3703.2
 7. DINING ROOM LIGHT IS SHOWN ON THE SMALL APPLIANCE
 CIRCUIT FOR THE DINING AREA, WHICH IS NOT PERMITTED PER
 CODE. PROVIDE CORRECTION. NEC 210.11(C)(1),
 210.52(B)(2); FBC RE3703.2
 8. BATH 2 LIGHT OVER SHOWER SHOWS A STANDARD LIGHT. PER
 CODE: "LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS". PROVIDE CORRECTION OR
 NOTE TO COMPLY. NEC 410.10(D); FBC RE4003.11
 9. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED
 LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT
 BE PERMITTED IN CLOTHES CLOSETS". LIGHT IN MASTER
 CLOSET IS NOT SPECIFIED. PROVIDE CORRECTION. NEC
 410.16(B), FBC RE4003.12
 10. IN SEVERAL LOCATIONS THE OUTLET SPACING IS NOT
 WITHIN THE LIMITS PER CODE: "RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET". PROVIDE CORRECTION. NEC
 210.52; FBC RE3901.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-10-03 Cont ID  
Sent By cthroop Date 2017-10-03 Time 15:25 Rev Time 0.00
Received By cthroop Date 2017-09-27 Time 15:08 Sent To  
Notes
2017-09-28 15:08:56RESUB ROUTED TO PGREILIC VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-28 Cont ID  
Sent By cpuell Date 2017-08-28 Time 17:29 Rev Time 0.00
Received By cpuell Date 2017-08-10 Time 14:25 Sent To  
Notes
2017-08-11 14:26:07R39

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-11 Cont ID  
Sent By lmarchan Date 2017-08-11 Time 14:22 Rev Time 0.00
Received By lmarchan Date 2017-07-03 Time 14:46 Sent To  
Notes
2017-07-05 14:46:43R09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-10-03 Cont ID  
Sent By cthroop Date 2017-10-03 Time 15:25 Rev Time 0.00
Received By cthroop Date 2017-10-03 Time 15:24 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-07-21 Cont ID  
Sent By cthroop Date 2017-07-21 Time 15:39 Rev Time 0.00
Received By cthroop Date 2017-07-21 Time 15:17 Sent To  
Notes
2017-07-21 15:40:07BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-08-28 Cont ID  
Sent By hmoser Date 2017-08-28 Time 14:20 Rev Time 0.00
Received By hmoser Date 2017-08-28 Time 14:15 Sent To AD
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-07-25 Cont ID  
Sent By hmoser Date 2017-07-25 Time 10:31 Rev Time 0.00
Received By hmoser Date 2017-07-25 Time 09:56 Sent To AD
Notes
2017-07-25 10:31:12PASS PROVISO
 REFER TO SECTION 1602.4 BALANCED RETURN AIR
 2014 FBC RESIDENTIAL. GAME ROOM & MASTERBED ROOM
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-07-13 Cont ID  
Sent By gjohnson Date 2017-07-13 Time 16:10 Rev Time 0.00
Received By gjohnson Date 2017-07-13 Time 15:38 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2017-07-21 Cont ID  
Sent By cthroop Date 2017-07-21 Time 15:39 Rev Time 0.00
Received By cthroop Date 2017-07-21 Time 15:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2017-10-03 Time   Rev Time 0.00
Received By pgreilic Date 2017-10-03 Time 08:49 Sent To B
Notes
2017-10-03 08:49:36 
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]
2017-09-29 11:02:54ROUTED TO PAUL GRELICH

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2017-08-22 Time   Rev Time 0.00
Received By pgreilic Date 2017-08-18 Time 16:40 Sent To  
Notes
2017-08-22 08:43:43PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]
  
 1.) INDICATE ADDRESS OF PROPOSED HOUSE ON PLANS
 2.) LABEL PROPERTY LINE AND PROPOSED FRONT, REAR AND
 SIDE SETBACKS
 3.) PLEASE SUBMIT A LANDSCAPE PERMIT
  

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By pgreilic Date 2017-07-18 Time   Rev Time 0.00
Received By pgreilic Date 2017-07-17 Time 11:15 Sent To  
Notes
2017-07-18 09:11:37PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]
  
 1.) CONTACT MIKE ORIO FOR AN ADDRESS, INDICATE ON PLANS
 2.) INDICATE PROPERTY LINE AND PROPOSED FRONT, REAR,
 AND SIDE SETBACKS
 3.) PLEASE SUBMIT A LANDSCAPE PERMIT