Plan Review Details - Permit 17061394
Plan Review Stops For Permit 17061394
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-07-10 Cont ID  
Sent By jwitmer Date 2017-07-10 Time 07:31 Rev Time  
Received By jwitmer Date 2017-07-10 Time 06:45 Sent To  
Notes
2017-07-10 07:34:502014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17061394
 ADD: 500 S. AUSTRALIAN AVENUE, SUITE: 930
 CONT: DONNELLAN CONSTRUCTION CORP.
 TEL: 954-772-8651
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 10/ 2017
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A-3.0 DETAIL G SHOWS WHAT APPEARS TO BE A
 MICROWAVE IN THE UPPER CABINETS OVER THE BREAK ROOM
 SINK. NO DIMENSION IS GIVEN TO THE BOTTOM SHELF OF THE
 UPPER CABINETS, PLEASE PROVIDE COMPLIANCE WITH THE 2014
 FBC-ACCESS. CODE SECTIONS:
 1A) 2014 ACCESS. CODE 308 REACH RANGES
  
 1B) 309.2 CLEAR FLOOR SPACE. A CLEAR FLOOR OR GROUND
 SPACE COMPLYING WITH 305 SHALL BE PROVIDED.
  
 1C) 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN
 ONE OR MORE OF THE REACH RANGES SPECIFIED IN 308.
  
 1D) 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE
 WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM.
  
 2) SHEET A-3.0 DETAIL G SHOWS WHAT APPEARS TO BE A
 BREAK ROOM SINK, PLEASE PROVIDE COMPLIANCE WITH THE
 2014 FBC-ACCESS. CODE SECTIONS:
 2A) 606.2 CLEAR FLOOR SPACE.
  
 2B) 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 2C) 606.4 FAUCETS. CONTROLS FOR FAUCETS SHALL COMPLY
 WITH 309. HAND-OPERATED METERING FAUCETS SHALL REMAIN
 OPEN FOR 10 SECONDS MINIMUM.
  
 2D) 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY AND
 DRAIN PIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES
 UNDER LAVATORIES AND SINKS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-09 Cont ID  
Sent By jpearson Date 2017-08-09 Time 14:03 Rev Time 0.00
Received By jpearson Date 2017-08-09 Time 14:03 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-12 Cont ID  
Sent By jpearson Date 2017-07-12 Time 13:10 Rev Time 0.00
Received By jpearson Date 2017-07-12 Time 13:10 Sent To  
Notes
2017-07-12 13:14:24CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE LIGHTING CONTROLS FOR CONFERENCE ROOM. FBC
 C405.2.2
 2. PROVIDE DETAIL OF INTERIOR LIGHTING POWER
 REQUIREMENTS IN RELATION TO THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC C405.5
 3. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2
 AND ASHREA 90.1: 8.4.2
 4. LIGHTING CIRCUIT FOR OFFICES 906-911 IS NOT
 INDICATED. PROVIDE CIRCUIT NUMBER FOR LIGHTING. FBC
 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-07-10 Cont ID  
Sent By scaldero Date 2017-07-10 Time 13:05 Rev Time 0.00
Received By scaldero Date 2017-07-10 Time 13:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-10 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-08 Time 13:07 Sent To  
Notes
2017-08-09 13:07:39RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-02 Cont ID  
Sent By cpuell Date 2017-08-02 Time 09:49 Rev Time 0.00
Received By cpuell Date 2017-06-30 Time 10:09 Sent To  
Notes
2017-07-03 10:10:06B27

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-08-10 Cont ID  
Sent By ccole Date 2017-08-10 Time 08:56 Rev Time 0.00
Received By ccole Date 2017-08-10 Time 08:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-14 Cont ID  
Sent By ccole Date 2017-07-14 Time 08:06 Rev Time 0.00
Received By ccole Date 2017-07-14 Time 08:04 Sent To  
Notes
2017-07-14 08:10:561ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17061394
 7/14/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1: REFER TO SECTIONS 809.1 & 809.2 FBC-14
 EXISTING BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES AFFECTED BY THE
 FLOOR PLAN CHANGES- SEE TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) M1.1: PROVIDE THE NEW FLEX DUCT SIZES, AND THE
 SUPPLY AND RETURN CFMS AT THE NEW ROOM LOCATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-08-01 Cont ID  
Sent By kmartin Date 2017-08-01 Time   Rev Time 0.00
Received By kmartin Date 2017-08-01 Time 15:03 Sent To I
Notes
***NONE***