Plan Review Details - Permit 17061373
Plan Review Stops For Permit 17061373
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-11-09 Cont ID  
Sent By jgomez Date 2017-11-09 Time 17:46 Rev Time 0.00
Received By jgomez Date 2017-11-09 Time 17:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-18 Cont ID  
Sent By jgomez Date 2017-10-18 Time 15:24 Rev Time 0.00
Received By jgomez Date 2017-10-18 Time 13:13 Sent To  
Notes
2017-10-18 13:34:33 
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-28 Cont ID  
Sent By jgomez Date 2017-07-28 Time 17:22 Rev Time 0.00
Received By jgomez Date 2017-07-28 Time 16:42 Sent To  
Notes
2017-07-28 17:33:44RESIDENTIAL (R3) ADDITION ? ALTERATION ? , BUILDING
 REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- INFORMATION SUBMITTED IS INSUFFICIENT FOR PLAN
 REVIEW. SCOPE OF WORK IS NOT CLEAR. LOCATION OF THE
 BATHROOM ADDITION IS NOT IDENTIFIED. PROVIDE COMPLETE
 DRAWINGS SHOWING THE LOCATION OF THE NEW BATHROOM. IF
 THIS IS AN ADDITION, THEN PROVIDE COMPLETE SET OF
 DRAWINGS (2 COPIES) SHOWING FOUNDATION PLAN, ROOF
 FRAMING PLAN, COMPLETE WALL SECTION DETAIL SHOWING ALL
 STRUCTURAL FRAMING MEMBERS AND CONNECTORS. NOTE:
 CLEARLY IDENTIFY ALL ROOMS ADJACENT TO THE BATHROOM
 ADDITION TO VERIFY THAT NO BEDROOM EGRESS OPENINGS ARE
 BLOCKED. SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.1 FBC
 -RESIDENTIAL, 5TH EDITION (2014).
  
 2- PLANS NEED TO HAVE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN . SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- DRAWING SUBMITTED IS NOT LEGIBLE. THE BACKGROUND OF
 THE GRAPH PAPER IS TOO DARK AND DOESN'T ALLOW READING
 OF THE PROPOSED BATHROOM. PROVIDE PAPER WITH LIGHTER OR
 CLEAR BACKGROUND. SEC. 107.2.1.4 CITY AMENDMENTS.
  
 4- IF THIS IS AN ADDITION, REVISED PLANS NEED TO BE
 TAKEN TO PALM BEACH COUNTY (2300 N. JOG RD.) FOR IMPACT
 FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND
 COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 5- PLANS ARE NO CLEAR. PRODUCT APPROVAL FOR NEW ROOF,
 WINDOWS?, MAY BE REQUIRED. FAC 61G20-3.001.
  
  
 NOTE: ADDITIONAL COMMENTS MAY FOLLOW BASED ON THE
 INFORMATION THAT IS SUBMITTED FOR REVIEW.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW AND PERMIT PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-11-27 Cont ID  
Sent By jpearson Date 2017-11-27 Time 09:09 Rev Time 0.00
Received By jpearson Date 2017-11-27 Time 08:26 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-10-24 Cont ID  
Sent By jpearson Date 2017-10-24 Time 08:00 Rev Time 0.00
Received By jpearson Date 2017-10-24 Time 07:59 Sent To  
Notes
2017-10-24 07:59:52CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 PREVIOUS ELECTRICAL REVIEW COMMENTS NOT ADDRESSED:
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW. INCLUDE PANEL
 SCHEDULE OF EXISTING ELECTRICAL PANEL SHOWING ANY NEW
 OR ALTERED CIRCUITS WITH THE APPROPRIATE AFCI OR GFCI
 PROTECTION PER CODE. SHOW THE REQUIRED 20 AMP CIRCUIT
 TO THE GFCI OUTLET LOCATED WITHIN 3 FEET OF THE SINK.
 PROVIDE FLOOR PLAN OF ENTIRE HOME SHOWING THE LOCATION
 OF ELECTRICAL WORK AND THE EXISTING SMOKE ALARMS. IF
 SMOKE ALARMS ARE NOT PRESENT, OR NOT TO CODE, SHOW AS
 NEW INSTALLATION. FBC 107.2.1, 107.3.5, R314.3,
 RE3902.12, RE3703.4, RE3706.1, RE3902, NEC 210.8,
 210.12, 210.52, 215.5 (PANEL SCHEDULE WAS NOT PROVIDED.
 ALTERED CIRCUITS NOT SHOWN WITH AFCI PROTECTION. GFCI
 OUTLET BY SINK IS SHOWN WITH 14 GUAGE WIRE, WHICH IS
 NOT RATED FOR 20 AMPS. ENTIRE HOME FLOOR PLAN SHOWING
 ALL SMOKE ALARMS NOT PROVIDED.) PROVIDE AS PREVIOUSLY
 REQUESTED.
  
 NEW COMMENT:
  
 2. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-20 Cont ID  
Sent By jpearson Date 2017-07-20 Time 12:08 Rev Time 0.00
Received By jpearson Date 2017-07-20 Time 12:08 Sent To  
Notes
2017-07-20 12:15:20CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW. INCLUDE PANEL
 SCHEDULE OF EXISTING ELECTRICAL PANEL SHOWING ANY NEW
 OR ALTERED CIRCUITS WITH THE APPROPRIATE AFCI OR GFCI
 PROTECTION PER CODE. SHOW THE REQUIRED 20 AMP CIRCUIT
 TO THE GFCI OUTLET LOCATED WITHIN 3 FEET OF THE SINK.
 PROVIDE FLOOR PLAN OF ENTIRE HOME SHOWING THE LOCATION
 OF ELECTRICAL WORK AND THE EXISTING SMOKE ALARMS. IF
 SMOKE ALARMS ARE NOT PRESENT, OR NOT TO CODE, SHOW AS
 NEW INSTALLATION. FBC 107.2.1, 107.3.5, R314.3,
 RE3902.12, RE3703.4, RE3706.1, RE3902, NEC 210.8,
 210.12, 210.52, 215.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-27 Cont ID  
Sent By jpearson Date 2017-11-27 Time 09:10 Rev Time 0.00
Received By jpearson Date 2017-11-01 Time 11:07 Sent To  
Notes
2017-11-02 11:07:24R02

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-24 Cont ID  
Sent By jpearson Date 2017-10-24 Time 08:00 Rev Time 0.00
Received By jpearson Date 2017-10-02 Time 12:41 Sent To  
Notes
2017-10-03 12:42:05R31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-28 Cont ID  
Sent By jgomez Date 2017-07-28 Time 18:23 Rev Time 0.00
Received By jgomez Date 2017-06-30 Time 10:00 Sent To  
Notes
2017-07-03 10:01:06R10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2017-10-18 Cont ID  
Sent By jgomez Date 2017-10-18 Time 15:29 Rev Time 0.00
Received By jgomez Date 2017-10-18 Time 15:29 Sent To  
Notes
2017-10-18 15:30:44NO ADDITION. BATHROOM IS LOCATED IN EXISTING SECOND
 FLOOR.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-07-28 Cont ID  
Sent By jgomez Date 2017-07-28 Time 18:04 Rev Time 0.00
Received By jgomez Date 2017-07-28 Time 17:55 Sent To  
Notes
2017-07-28 18:06:00PLANS ARE NO CLEAR IF NEW BATHROOM IS ADDITION OR NOT.
 IMPACT FEES ASSESSMENT MAY BE REQUIRED DEPENDING ON THE
 RESUBMITTAL PACKAGE. JG.

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-11-15 Cont ID  
Sent By gjohnson Date 2017-11-15 Time 17:47 Rev Time 0.00
Received By gjohnson Date 2017-11-15 Time 16:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-13 Cont ID  
Sent By lcrespo Date 2017-10-13 Time 13:24 Rev Time 0.00
Received By lcrespo Date 2017-10-13 Time 13:24 Sent To  
Notes
2017-10-13 13:25:3910/13/17 APPROVED BY PLUMBING LAC

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-19 Cont ID  
Sent By gjohnson Date 2017-07-19 Time 17:45 Rev Time 0.00
Received By gjohnson Date 2017-07-19 Time 09:40 Sent To  
Notes
2017-07-19 17:52:231ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE PLUMBING RISER DIAGRAM. PER WPB AMEND TO FBC
 107.3.5.3(11)
  
 2. PROVIDE FLOOR PLAN SHOWING WHOLE HOUSE. PER WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2017-10-18 Cont ID  
Sent By jgomez Date 2017-10-18 Time 15:25 Rev Time 0.00
Received By jgomez Date 2017-10-18 Time 15:25 Sent To  
Notes
2017-10-18 15:25:39NO ROOFING WORK SHOWN ON PLANS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-07-28 Cont ID  
Sent By jgomez Date 2017-07-28 Time 18:20 Rev Time 0.00
Received By jgomez Date 2017-07-28 Time 18:06 Sent To  
Notes
2017-07-28 18:21:051- PLANS ARE NO CLEAR. PRODUCT APPROVAL FOR NEW ROOF,
 WINDOWS?, MAY BE REQUIRED. FAC 61G20-3.001.

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2017-11-08 Time   Rev Time 0.00
Received By awooten Date 2017-11-07 Time 15:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2017-10-11 Time   Rev Time 0.00
Received By   Date 2017-10-11 Time   Sent To  
Notes
2017-10-11 09:18:18***************ZONING REVIEW**************
  
 PROVIDE A SURVEY FOR PROPERTY. PLANS SITE A SIGNED AND
 SEALED SURVEY.
  
 PLEASE LET ME KNOW WHAT QUESTIONS YOU HAVE.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2017-07-12 Cont ID  
Sent By awooten Date 2017-07-12 Time 13:01 Rev Time 0.00
Received By awooten Date 2017-07-12 Time 12:57 Sent To  
Notes
2017-07-12 13:01:18************************************ZONING REVIEW
 FAILED*********************************************
  
 IS THE FOOTPRINT OF THE BUILDING CHANGING/EXPANDING?
  
 PROVIDE A FLOOR PLAN AND A SURVEY OF PROPERTY SHOWING
 ADDITION.
  
 ADDITIONAL COMMENTS MAY FOLLOW THIS REVIEW.
  
 PLEASE LET ME KNOW IF YOU HAVE QUESTIONS.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING AND ZONING
 561-822-1449
 [email protected]