Plan Review Details - Permit 17061360
Plan Review Stops For Permit 17061360
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-25 Cont ID  
Sent By jwitmer Date 2017-08-25 Time 06:29 Rev Time 0.00
Received By jwitmer Date 2017-08-25 Time 06:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-07 Cont ID  
Sent By jwitmer Date 2017-07-07 Time 16:33 Rev Time 0.00
Received By jwitmer Date 2017-07-07 Time 16:18 Sent To  
Notes
2017-07-07 16:33:52 
 2014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17061360
 ADD: 400 N. FLAGLER DR. SUITE: 2602/ PHB2
 CONT: B.A.C.H. LAND DEVELOPMENT
 TEL: 813-559-8555
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JULY 07/ 2017
 ACTION: DENIED
  
 1) THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE
 SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE
 AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR
 NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED
 IN AND PLANS DRAWN. 107.3.4.3 CERTIFICATION BY
 CONTRACTOR.
  
 2) THE PLANS BY BUIGAS & ASSOCIATES ARCHITECTS ARE
 COPIES AND WILL NEED TO BE SIGNED AND SEALED. PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY
 THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS
 PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE
 ARCHITECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST
 AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC
 61G1-16.003
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-09-05 Cont ID  
Sent By jpearson Date 2017-08-30 Time 09:51 Rev Time 0.00
Received By jpearson Date 2017-08-30 Time 09:51 Sent To  
Notes
2017-08-30 09:51:28PASS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-12 Cont ID  
Sent By jpearson Date 2017-07-12 Time 09:53 Rev Time 0.00
Received By jpearson Date 2017-07-12 Time 09:53 Sent To  
Notes
2017-07-12 09:56:05CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY DESIGN PROFESSIONAL OR THE ELECTRICAL
 CONTRACTOR QUALIFIER. FS 471, FAC61G15-23, FBC 107.3.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-24 Cont ID  
Sent By pleduc Date 2017-08-24 Time   Rev Time 0.00
Received By pleduc Date 2017-08-23 Time 11:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-07-05 Cont ID  
Sent By pleduc Date 2017-07-05 Time   Rev Time 0.00
Received By pleduc Date 2017-07-05 Time 11:05 Sent To  
Notes
2017-07-05 13:24:56THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLANS DO NOT PROVIDE SUFFICIENT
 INFORMATION TO DETERMINE COMPLIANCE WITH ANY FIRE CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
  
 2) THERE IS NO REFERENCE TO WORK RELATING TO THE FIRE
 SPRINKLER SYSTEM. ANY WORK THAT REMOVES AND/OR ADDS
 WALLS IN AN EXISTING FIORE SPRINKLED AREA SHALL BE
 ELAVUATED FOR CODE COMPLIANT FIRE SPRINKLER PROTECTION.
  
 ANY WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED FIRE
 SPRINKLER CONTRACTORS.
  
 PLEASE INDICATE IF THE AREA IS SPRINKLED AND A NOTE OF
 SHOP DRAWINGS AS NOTED ABOVE.
  
  
  
 3) IT IS UNCLEAR WHAT WALLS WILL BE REMOVED AND WHAT
 WALLS WILL BE INSTALLED WITH THE PROJECT. PLEASE
 PROVIDE GREATER DETAIL.
  
  
  
 4) THERE IS NO SPECIFIC ADDRESS IN THE TITLE BLOCK ON
 THE PLAN SHEETS.
  
 PLEASE PROVIDE ON EACH SHEET.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-07 Cont ID  
Sent By thunt Date 2017-09-07 Time 13:33 Rev Time 0.00
Received By thunt Date 2017-08-21 Time 10:45 Sent To  
Notes
2017-08-22 10:45:49B02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-13 Cont ID  
Sent By gjohnson Date 2017-07-13 Time 12:45 Rev Time 0.00
Received By gjohnson Date 2017-06-29 Time 13:41 Sent To  
Notes
2017-06-30 13:41:58B25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-07-07 Cont ID  
Sent By jwitmer Date 2017-07-07 Time 16:34 Rev Time 0.00
Received By jwitmer Date 2017-07-07 Time 16:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-09-07 Cont ID  
Sent By thunt Date 2017-09-07 Time 13:33 Rev Time 0.00
Received By thunt Date 2017-09-07 Time 13:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-13 Cont ID  
Sent By gjohnson Date 2017-07-13 Time 12:40 Rev Time 0.00
Received By gjohnson Date 2017-07-13 Time 12:40 Sent To  
Notes
2017-07-13 12:45:471ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE AN EXISTING FLOOR PLAN. PER WPB AMEND
 TO FBC 107.2.1
  
 2. ALL PLAN SHEETS ARE REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR DESIGN. . PER WPB AMEND TO FBC 107.2.1
 SEE ALSO BUILDINGS COMMENTS
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  