| 2017-07-19 13:43:52 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. LOAD CALCULATION PROVIDED DOES NOT INCLUDE THE |
| | RANGE. PROVIDE CORRECTION TO INCLUDE THE RANGE. NEC |
| | 210.19(3), 220.55; FBC RE3602.2, 3702.9.1 |
| | 2. NOTE 2 ON PANEL SCHEDULE STATES RECEPTACLES SHALL BE |
| | "TEMPER RESISTANT PER 210.12". THERE IS SIMILAR WORDING |
| | IN NOTE 4, BUT THIS NOTE STATES "PER 406.11".IF YOU ARE |
| | REFERRING TO TAMPER RESISTANT REQUIREMENTS, NEITHER OF |
| | THESE CODE SECTIONS APPLY. PROVIDE CLARIFICATION AND/OR |
| | CORRECTION. NEC 406.12; FBC RE4002.14 |
| | 3. NOTE 3 STATES THAT "ALL NEW BRANCH CIRCUITS SHALL BE |
| | AFCI PROTECTED PER 210.12". NEC 210.12 DOES NOT REQUIRE |
| | ALL CIRCUITS TO BE AFCI PROTECTED, BUT THE STATEMENT |
| | DOES. IS THIS THE INTENTION, OR WILL ONLY THE CIRCUITS |
| | REQUIRED PER NEC 210.12 BE AFCI PROTECTED? PLEASE |
| | CLARIFY AND/OR CORRECT. NEC 210.12; FBC RE3902.12 |
| | 4. CIRCUIT 25,27 SHOWS THE AHU ON A 25 AMP BREAKER. |
| | SPECS FROM MECHANICAL DRAWING SHOW A MAX 40 AMP |
| | BREAKER. PROVIDE CORRECTION. NEC 440.22(C); FBC |
| | RE3702.11 |
| | 5. CIRCUIT 26,28 SHOWS THE CU ON A 45 AMP BREAKER. |
| | SPECS FROM MECHANICAL DRAWING SHOW A MAX 30 AMP |
| | BREAKER. PROVIDE CORRECTION. NEC 440.22(C); FBC |
| | RE3702.11 |
| | 6. CIRCUIT 4 SHOW A 15 AMP CIRCUIT TO THE |
| | RANGE/COOKTOP. A MINIMUM 40 AMP CIRCUIT IS REQUIRED. |
| | PROVIDE CORRECTION. NEC 210.19(3), 220.55; FBC |
| | RE3602.2, 3702.9.1 |
| | 7. CIRCUIT 15 SHOWS THE DINING ROOM ON A 15 AMP |
| | CIRCUIT, WHICH IS NOT PERMITTED PER CODE. THE LIGHT IN |
| | DINING ROOM SHOULD NOT BE ON THE SAME CIRCUIT AS THE |
| | OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(1), |
| | 210.52(B)(2),(3); FBC RE3703.2 |
| | 8. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| | EQUIPMENT PER CODE. THE ONLY OUTLET SHOWN IS FOR THE |
| | TANKLESS WATER HEATER (CIRCUIT A-11), AND ALSO IS |
| | CONNECTED TO BATH #2 GFCI OUTLET. BATH GFCI OUTLETS ARE |
| | REQUIRED TO BE A 20 AMP CIRCUIT, AND NO OTHER ITEMS CAN |
| | BE ON THE SAME CIRCUIT, UNLESS THE CIRCUIT REMAINS IN |
| | ONE BATHROOM ONLY. PROVIDE CORRECTION. NEC 210.63, |
| | 210.11(C)(3), 210.52(D); FBC RE3901.12, 3703.4 |
| | 9. CIRCUIT A-22 TO BATH 1 GFCI OUTLET NEEDS TO BE A 20 |
| | AMP CIRCUIT. PROVIDE CORRECTION. NEC 210.11(C)(3); FBC |
| | 3703.4 |
| | 10. MASTER BEDROOM DOES NOT COMPLY WITH THE WALL |
| | SPACING REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| | FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC |
| | 210.52; FBC RE3901.2.1 |
| | 11. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |