Plan Review Details - Permit 17061303
Plan Review Stops For Permit 17061303
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-08-16 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2017-08-16 Time 07:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-07 Cont ID  
Sent By jwitmer Date 2017-07-07 Time 15:15 Rev Time  
Received By jwitmer Date 2017-07-07 Time 11:38 Sent To  
Notes
2017-07-07 15:15:122014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17061303
 ADD: 701 S. OLIVE AVE. SUITE NUMBER 619
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-719-0725/ MICHAEL COLAPRETE
 E-MAIL: ???????? WE PREFER TO COMMUNICATE BY E-MAIL!!!
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JULY 07/2017
 ACTION: DENIED
  
 1A) SHEET A-1 THE DOOR SCHEDULE INDICATES DOORS 4, 6,
 9, 10, 11, 12, 13 & 14 ALL BEING 2 FT. 8 INCHES WIDE.
 2014 FBC-EXISTING BUILDING CODE 301.1 THE DOORS CANNOT
 BE LESS COMPLIANT THAN AT THE TIME THE BUILDING WAS
 BUILT. THE ORIGINAL BUILDING WAS BUILT UNDER PERMIT
 04120353 IN OTHER WORDS APPLIED FOR PERMIT APRIL OF
 2004. BUILDINGS THAT WERE IN DESIGN OR PERMITTED FOR
 FIRST OCCUPANCY AFTER 13, 1991 MUST BE DESIGNED FOR
 FAIR HOUSING. THE INTERIOR DOORS ARE CONSIDERED USABLE
 DOORS UNDER FAIR HOUSING THAT ALLOWS PASSAGE WITHIN THE
 DWELLING UNIT. USABLE DOORS ARE INTENDED TO PROVIDE 32
 INCHES CLEAR WIDTH. PLEASE SEE THE 2014
 FBC-ACCESSIBILITY CODE/ FAIR HOUSING REQUIREMENT 3.
 USABLE DOORS, FIGURE 1 (A) HINGED DOORS & ( C ) FOR
 SLIDING OR POCKET DOORS.
  
 1B) SHEET A-1 THE FLOOR PLAN INDICATES A NEW ISLAND
 CABINET AND COUNTERTOP AND A DISTANCE OF 39 INCHES
 BETWEEN THE ISLAND AND THE BACK WALL. PLEASE SEE FAIR
 HOUSING REQUIREMENTS UNDER REQUIREMENT 7 FOR USABLE
 KITCHENS (B) CLEARANCE BETWEEN COUNTERS AND ALL
 OPPOSING BASE CABINETS, COUNTERTOPS, APPLIANCES
 (REFRIGERATOR DOORS) OR WALLS IS AT LEAST 40 INCHES.
  
 2) SHEET A2 DETAILS 1-3 PROVIDE THE TYPE OF ANCHOR AND
 SPACING FOR THE FRAMING MEMBERS FOR THE DROP CEILING
 BUT MISSING THE ANCHOR AND SPACING FOR THE 7/8 INCH
 HI-HAT METAL. PLEASE PROVIDE ADDITIONAL INFORMATION.
 107.2.1.3.
  
 3) SHEET A2 TOP OF PAGE PALM BEACH COUNTY CONSTRUCTION
 NOTES. PLEASE NOTE THE JOB SITE LOCATION IS NOT IN PALM
 BEACH COUNTY UNINCORPORATED BUT IN THE CITY OF WEST
 PALM BEACH, THESE NOTES ARE NOT APPLICABLE! 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 4) THE PLANS DO NOT STATE IF THE FLOORS ARE BEING
 REMOVED, IF THEY ARE IN ANY ROOM AND EITHER MARBLE,
 TILE, WOOD LAMINATES OR VINYL FLOORING ARE BEING
 INSTALLED THEN COMPLIANCE WITH THESE SECTIONS OF THE
 2014 FBC-B WILL BE REQUIRED:
  
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 4A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-15 Cont ID  
Sent By jpearson Date 2017-08-15 Time 16:04 Rev Time 0.00
Received By jpearson Date 2017-08-15 Time 16:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-12 Cont ID  
Sent By jpearson Date 2017-07-12 Time 08:58 Rev Time 0.00
Received By jpearson Date 2017-07-12 Time 08:58 Sent To  
Notes
2017-07-12 09:25:57CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. ELECTRICAL RISER NOTE #5 STATES THAT AFCI PROTECTION
 SHALL BE "PER NEC 2010-12". THIS IS NOT A VALID CODE
 SECTION, PLEASE CORRECT. NEC 210.12; FBC 107.2.1
 2. ELECTRICAL RISER NOTE #6 STATES TAMPER RESISTANT
 RECEPTACLES "PER NEC 406.11". THIS CODE SECTION DOES
 NOT APPLY TO TAMPER RESISTANT. PROVIDE CORRECTION. NEC
 406.12; FBC 107.2.1
 3. AFCI PROTECTION IS REQUIRED FOR MORE THAN JUST
 RECEPTACLES. INDICATE AFCI PROTECTION PER CODE: "ALL
 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION". NEC 210.12
 4. SCOPE OF WORK ON A-1 STATES THAT THE ELECTRICAL
 PANEL WILL BE RELOCATED. PLAN ONLY SHOWS THE EXISTING
 LOCATION. SHOW NEW LOCATION ON PLAN. FBC 107.2.1
 5. SMOKE ALARMS SHOULD BE INSTALLED IN EACH BEDROOM AND
 ON THE CEILING OR WALL OUTSIDE OF EACH SEPARATE
 SLEEPING AREA IN THE IMMEDIATE VICINITY OF BEDROOMS.
 THESE SHOULD BE FED FROM SAME POWER SOURCE,
 INTERCONNECTED, AND NOT TIED TO THE BUILDING FIRE ALARM
 SYSTEM. THERE IS A NOTE IN THE SYMBOLS LEGEND THAT
 STATES TO CONNECT TO BUILDING FIRE ALARM SYSTEM. REMOVE
 AND/OR REVISE THIS NOTE AND PROVIDE CORRECTIONS FOR
 ITEMS PREVIOUSLY STATED. FBC 907.2.11.2; NFPA 101,
 9.6.2.10.4
 6. THE SPECS FOR THE TANKLESS WATER HEATER SPECIFIED ON
 PLUMBING PLAN DOES NOT MATCH THE DATA IN THE PANEL
 SCHEDULE. PROVIDE CORRECTION FOR WIRE AND BREAKER SIZE,
 ADJUST LOAD CALCULATION ACCORDINGLY. NEC 110.3, 240.4,
 310.15(B)(16)
 7. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS. MASTER CLOSET SHOWS
 STANDARD RECESS LIGHTS. PROVIDE CORRECTION. NEC
 410.16(B)
 8. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. THESE AREAS SHOW STANDARD
 RECESS LIGHTS. PROVIDE CORRECTION. NEC 410.10(D)
 9. NOTE FOR ENERGY COMPLIANCE IN THE SYMBOLS LEGEND IS
 NOT CORRECT. "A MINIMUM OF 75 PERCENT OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICACY LAMPS". PROVIDE CORRECTION. FBC EC
 R404.1
 10. PLAN SHOWS A GFCI OUTLET BY THE TUB IN MASTER BATH.
 RECEPTACLES ARE NOT PERMITTED IN THIS LOCATION.
 HOWEVER, THIS COULD BE FOR A JACUZZI TUB, BUT THE PLAN
 IS UNCLEAR AND THERE IS NO CIRCUIT LISTED FOR A JACUZZI
 TYPE TUB IN THE PANEL SCHEDULE. CORRECT AND/OR CLARIFY.
 FBC 107.2.1; NEC 406.9(C)
 11. LIVING ROOM TV SHOWS A CABLE OUTLET AT 60", BUT
 DOES NOT SHOW A RECEPTACLE AT THE SAME HEIGHT. WILL
 THERE BE ONE LOCATED HERE? CORRECT AND/OR CLARIFY. FBC
 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-14 Cont ID  
Sent By pleduc Date 2017-08-14 Time   Rev Time 0.00
Received By pleduc Date 2017-08-11 Time 15:05 Sent To  
Notes
2017-08-14 09:33:322ND REVIEW
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) ANY WORK ON THE FIRE ALARM EQUIPMENT SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-06-30 Cont ID  
Sent By pleduc Date 2017-06-30 Time   Rev Time 0.00
Received By pleduc Date 2017-06-30 Time 13:50 Sent To  
Notes
2017-06-30 15:36:10THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) ANY WORK ON THE FIRE ALARM EQUIPMENT SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-10-11 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-05 Time 14:59 Sent To  
Notes
2017-10-06 15:00:03RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-22 Cont ID  
Sent By gjohnson Date 2017-08-22 Time 12:55 Rev Time 0.00
Received By gjohnson Date 2017-08-09 Time 13:49 Sent To  
Notes
2017-08-10 13:49:30B15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-07-14 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-28 Time 14:13 Sent To  
Notes
2017-06-29 14:13:36B17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-07-07 Cont ID  
Sent By jwitmer Date 2017-07-07 Time 15:15 Rev Time 0.00
Received By jwitmer Date 2017-07-07 Time 15:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-10-11 Cont ID  
Sent By ccole Date 2017-10-11 Time 10:44 Rev Time 0.00
Received By ccole Date 2017-10-10 Time 16:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-21 Cont ID  
Sent By ccole Date 2017-08-21 Time 09:04 Rev Time 0.00
Received By ccole Date 2017-08-18 Time 18:04 Sent To  
Notes
2017-08-21 09:13:492ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17061303
 8/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET AC-1: MAKEUP AIR IS REQUIRED FOR THE NEW 625
 CFM EXHAUST HOOD- SECTION 505.2 FBC-14 MECHANICAL. THE
 RATE OF AIR PROVIDED SHALL BE APPROXIMATELY EQUAL TO
 THE EXHAUST AIR RATE.
  
 2) AC-1: SHOW THE POINT OF CONNECTION OF THE NEW HOOD
 EXHAUST VENT TO THE EXISTING VENT SYSTEM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-13 Cont ID  
Sent By ccole Date 2017-07-13 Time 18:21 Rev Time 0.00
Received By ccole Date 2017-07-13 Time 18:20 Sent To  
Notes
2017-07-13 18:23:471ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17061303
 7/13/17
  
 PLAN REVIEW RESULTS: DENIED
  
 1) SHEET A-3: SHOW THE LOCATION OF DEMOLITION KEY NOTE
 D10 ON THE FLOOR PLAN.
  
 2) PROVIDE MECHANICAL PLANS SHOWING ALL PROPOSED
 CHANGES TO THE EXISTING HVAC SYSTEMS.
  
 3) CLARIFY IF ANY CHANGES TO THE KITCHEN EXHAUST
 VENTILATION ARE PROPOSED SUCH AS A NEW EXHAUST HOOD AND
 DUCT. PROVIDE DETAILS IF APPLICABLE AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE COOK TOP AND
 EXHAUST HOOD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-22 Cont ID  
Sent By gjohnson Date 2017-08-22 Time 12:55 Rev Time 0.00
Received By gjohnson Date 2017-08-22 Time 10:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-13 Cont ID  
Sent By gjohnson Date 2017-07-13 Time 14:24 Rev Time 0.00
Received By gjohnson Date 2017-07-13 Time 14:24 Sent To  
Notes
2017-07-13 15:15:471ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THIS BUILDING WAS ORIGINALLY DESIGNED TO COMPLY WITH
 THE FAIR HOUSING ACT ANY RENOVATIONS MADE TO THE UNITS
 SHALL MAINTAIN THE SAME LEVEL OR ACCESSIBILITY. THE
 ORIGINAL PLAN SHOWED THE BATHROOMS WERE DESIGN SPEC B
 PLEASE SHOW ON THE PLAN THE CLEAR FLOOR SPACE WITH
 DIMENSIONS FOR ALL FIXTURES IN THE B BATHROOM ALSO SHOW
 THE HEIGHT DIMENSIONS FOR THE LAVATORY AND GRAB BAR
 BACKING FOR THE NEW LAYOUT TO COMPLY WITH FHA.
  
 2. PLEASE INDICATE ON THE PLAN WHICH DESIGN DOCUMENT
 YOU WILL USE TO COMPLY WITH FHA.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  