Plan Review Details - Permit 17061260
Plan Review Stops For Permit 17061260
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-04-19 Cont ID  
Sent By jwitmer Date 2018-04-19 Time 15:43 Rev Time 0.00
Received By jwitmer Date 2018-04-18 Time 16:56 Sent To  
Notes
2018-04-19 15:43:102014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17061260
 ADD: 425 24TH ST.
 CONT: CLEAR SPAN STRUCTURES
 TEL: 561-803-8100
 E-MAIL: MIACOBUCCICSSBUILDS.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. APRIL 19, 2018
 ACTION: DENIED
  
 1) COMPLIED.
  
 2A) 3RD REVIEW. THIS REVIEW THERE ARE (4) MIAMI-DADE
 NOA 15-0820.06 SUBMITTED NONE OF THE SCHEDULES ON THE 4
 TECHNICAL SHEETS CIRCLED TO IDENTIFY WHICH SUB-SYSTEM,
 SIZE OF BRACKET/ UNIT, ANCHOR AND TYPE OF MATERIAL THE
 ANCHOR IS TO BE FASTEN. 107.2.1.3/ , 1609.6.4.4.1
 COMPONENTS & CLADDING. RULE 61G-20-3.
 THERE IS A 2ND WHAT APPEARS TO BE A SHOP DRAWING FROM
 THE METAL SHOP, NOT A PRODUCT APPROVAL, NO COVER PAGE
 FOR A FLORIDA OR MIAMI-DADE NOA. 107.2.1.3/ ,
 1609.6.4.4.1 COMPONENTS & CLADDING. RULE 61G-20-3.
  
 1ST ROUND COMMENT. THE SUBMITTED MIAMI-DADE NOA
 15-0820.06 WAS SUBMITTED BUT NONE OF THE TABLES ON THE
 TECHNICAL SHEETS IDENTIFY THE UNIT SIZE / BRACKET, WALL
 TYPE, ANCHOR TYPE, MINIMUM EMBEDMENT, MINIMUM E. D.,
 RISK CATEGORY, BUILDING HEIGHT, ETC.? FBC-B 2014 FBC-B
 1604.4 ANALYSIS.
  
 2B) SUBMITTED WALL BRACKET FROM THE METAL SHOP THERE IS
 NO PRODUCT APPROVAL FOR THIS WALL BRACKET. IT HAS AN
 ENGINEERS SEAL JOSEPH HILLER, THE SEAL IS NOT A LEGAL
 SIZE SEAL AND THE SIGNATURE IS A COPY. EITHER THE
 PRODUCT APPROVAL NEEDS TO BE EITHER A MIAMI-DADE NOA OR
 FLORIDA APPROVAL. IT WOULD APPEAR THIS ALUMINUM WALL
 BRACE WOULD NEED TO BE EITHER A LOCAL APPROVAL OR A
 SITE SPECIFIC APPROVAL.
  
 3) 3RD REQUEST. FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4) COMPLIED.
  
 5) COMPLIED. ROLLING GARAGE DOOR IS DELETED FROM THE
 PROJECT.
  
 6) SEMI- COMPLIED. HOOD WILL BE DETERMINED BY THE
 MECHANICAL REVIEWER IF CODE COMPLIANT PLEASE NOTE THE
 COMMENT STANDS. PLEASE SEE THE DEFINITION OF A
 COMMERCIAL KITCHEN UNDER THE 2014 FBC- MECHANICAL CODE.
 COMMERCIAL COOKING APPLIANCES. FOR THE PURPOSE OF THIS
 DEFINITION, A FOOD SERVICE ESTABLISHMENT SHALL INCLUDE
 ANY BUILDING OR A PORTION THEREOF USED FOR THE
 PREPARATION AND SERVING OF FOOD. APPLIANCES USED IN A
 COMMERCIAL FOOD SERVICE ESTABLISHMENT FOR HEATING OR
 COOKING FOOD AND WHICH PRODUCE GREASE VAPORS, STEAM,
 FUMES, SMOKE OR ODORS THAT ARE REQUIRED TO BE REMOVED
 THROUGH A LOCAL EXHAUST VENTILATION SYSTEM. SUCH
 APPLIANCES INCLUDE DEEP FAT FRYERS; UPRIGHT BROILERS;
 GRIDDLES; BROILERS; STEAM-JACKETED KETTLES; HOT-TOP
 RANGES; UNDER-FIRED BROILERS (CHAR BROILERS); OVENS;
 BARBECUES; ROTISSERIES; AND SIMILAR APPLIANCES.
  
 904.2 WHERE REQUIRED. AUTOMATIC FIRE-EXTINGUISHING
 SYSTEMS INSTALLED AS AN ALTERNATIVE TO THE REQUIRED
 AUTOMATIC SPRINKLER SYSTEMS OF SECTION 903 SHALL BE
 APPROVED BY THE FIRE CODE OFFICIAL. AUTOMATIC
 FIRE-EXTINGUISHING SYSTEMS SHALL NOT BE CONSIDERED
 ALTERNATIVES FOR THE PURPOSES OF EXCEPTIONS OR
 REDUCTIONS ALLOWED BY OTHER REQUIREMENTS OF THIS CODE.
  
 904.2.1 COMMERCIAL HOOD AND DUCT SYSTEMS. EACH REQUIRED
 COMMERCIAL KITCHEN EXHAUST HOOD AND DUCT SYSTEM
 REQUIRED BY THE FLORIDA FIRE PREVENTION CODE OR CHAPTER
 5 OF THE FLORIDA BUILDING CODE, MECHANICAL TO HAVE A
 TYPE I HOOD SHALL BE PROTECTED WITH AN APPROVED
 AUTOMATIC FIRE-EXTINGUISHING SYSTEM INSTALLED IN
 ACCORDANCE WITH THIS CODE.
  
 7) 3RD. SHEET A-101 DETAIL #9 ILLUSTRATES THE USE OF A
 WALL OVEN, WHEN SCALED THE OPERATING KNOBS ARE LOCATED
 AT 4 FT. 9 INCHES ABOVE THE FINISH FLOOR OUT OF RANGE
 FOR REACH RANGES IN 308 OF THE ACCESSIBILITY CODE AND
 309 OPERABLE PARTS.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-17 Cont ID  
Sent By jwitmer Date 2017-08-17 Time 16:20 Rev Time 0.00
Received By jwitmer Date 2017-08-17 Time 11:53 Sent To  
Notes
2017-08-17 16:20:392014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17061260
 ADD: 425 24TH ST.
 CONT: CLEAR SPAN STRUCTURES
 TEL: 561-803-8100
 E-MAIL: MIACOBUCCICSSBUILDS.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. AUGUST 17, 2017
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) THIS REVIEW THERE ARE (4) MIAMI-DADE NOA 15-0820.06
 SUBMITTED NONE OF THE SCHEDULES ON THE 4 TECHNICAL
 SHEETS CIRCLED TO IDENTIFY WHICH SUB-SYSTEM, SIZE OF
 BRACKET/ UNIT, ANCHOR AND TYPE OF MATERIAL THE ANCHOR
 IS TO BE FASTEN. 107.2.1.3/ , 1609.6.4.4.1 COMPONENTS &
 CLADDING. RULE 61G-20-3.
 THERE IS A 2ND WHAT APPEARS TO BE A SHOP DRAWING FROM
 THE METAL SHOP, NOT A PRODUCT APPROVAL, NO COVER PAGE
 FOR A FLORIDA OR MIAMI-DADE NOA. 107.2.1.3/ ,
 1609.6.4.4.1 COMPONENTS & CLADDING. RULE 61G-20-3.
  
 1ST ROUND COMMENT. THE SUBMITTED MIAMI-DADE NOA
 15-0820.06 WAS SUBMITTED BUT NONE OF THE TABLES ON THE
 TECHNICAL SHEETS IDENTIFY THE UNIT SIZE / BRACKET, WALL
 TYPE, ANCHOR TYPE, MINIMUM EMBEDMENT, MINIMUM E. D.,
 RISK CATEGORY, BUILDING HEIGHT, ETC.? FBC-B 2014 FBC-B
 1604.4 ANALYSIS.
  
 3) 2ND REQUEST. FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4) COMPLIED.
  
 5) 2ND REQUEST. THE NEW ROLLING GARAGE DOOR IS SHOWN ON
 A-100 IN DETAIL 8. A SHOP DRAWING BY PEDRO FIGUEIREDO
 P. E. WAS SUBMITTED. IF THIS DOES NOT HAVE EITHER A
 FLORIDA APPROVAL OR A MIAMI-DADE NOA, A LOCAL APPROVAL
 CAN BE APPLIED FOR, THE CITY USES THE SAME CRITERIA AS
 THE STATE. . 107.2.1.3/ , 1609.6.4.4.1 COMPONENTS &
 CLADDING. RULE 61G-20-3.
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 1ST ROUND COMMENT. SHEET A-100 SHOWS THE ROLLING GARAGE
 DOOR AS EXISTING, THIS SAME PAGE SHOWS DETAIL W1 & S1
 FOR WINDOW AND SHUTTER, SHEET A-101 DETAIL 5 SHOWS
 PRESSURES FOR THIS OPENING, IS THIS PART OF THIS
 REVIEW, OR UNDER THE ORIGINAL BUILDING PERMIT?
 ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.3.
  
 6) 2ND REQUEST. PLEASE NOTE THE COMMENT STANDS. PLEASE
 SEE THE DEFINITION OF A COMMERCIAL KITCHEN UNDER THE
 2014 FBC- MECHANICAL CODE. COMMERCIAL COOKING
 APPLIANCES. FOR THE PURPOSE OF THIS DEFINITION, A FOOD
 SERVICE ESTABLISHMENT SHALL INCLUDE ANY BUILDING OR A
 PORTION THEREOF USED FOR THE PREPARATION AND SERVING OF
 FOOD. APPLIANCES USED IN A COMMERCIAL FOOD SERVICE
 ESTABLISHMENT FOR HEATING OR COOKING FOOD AND WHICH
 PRODUCE GREASE VAPORS, STEAM, FUMES, SMOKE OR ODORS
 THAT ARE REQUIRED TO BE REMOVED THROUGH A LOCAL EXHAUST
 VENTILATION SYSTEM. SUCH APPLIANCES INCLUDE DEEP FAT
 FRYERS; UPRIGHT BROILERS; GRIDDLES; BROILERS;
 STEAM-JACKETED KETTLES; HOT-TOP RANGES; UNDER-FIRED
 BROILERS (CHARBROILERS); OVENS; BARBECUES; ROTISSERIES;
 AND SIMILAR APPLIANCES.
  
 1ST ROUND OF COMMENTS. SHEET A-101 DETAIL #9
 ILLUSTRATES THE USE OF A SLIDE IN RANGE, PLEASE PROVIDE
 COMPLIANCE WITH THE FBC-B SECTIONS:
 9.3.2.11.5 COMMERCIAL COOKING OPERATIONS. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE INSTALLED IN COMMERCIAL
 KITCHEN EXHAUST HOOD AND DUCT SYSTEM WHERE AN AUTOMATIC
 SPRINKLER SYSTEM IS USED TO COMPLY WITH SECTION 904.
 904.2 WHERE REQUIRED. AUTOMATIC FIRE-EXTINGUISHING
 SYSTEMS INSTALLED AS AN ALTERNATIVE TO THE REQUIRED
 AUTOMATIC SPRINKLER SYSTEMS OF SECTION 903 SHALL BE
 APPROVED BY THE FIRE CODE OFFICIAL. AUTOMATIC
 FIRE-EXTINGUISHING SYSTEMS SHALL NOT BE CONSIDERED
 ALTERNATIVES FOR THE PURPOSES OF EXCEPTIONS OR
 REDUCTIONS ALLOWED BY OTHER REQUIREMENTS OF THIS CODE.
  
 904.2.1 COMMERCIAL HOOD AND DUCT SYSTEMS. EACH REQUIRED
 COMMERCIAL KITCHEN EXHAUST HOOD AND DUCT SYSTEM
 REQUIRED BY THE FLORIDA FIRE PREVENTION CODE OR CHAPTER
 5 OF THE FLORIDA BUILDING CODE, MECHANICAL TO HAVE A
 TYPE I HOOD SHALL BE PROTECTED WITH AN APPROVED
 AUTOMATIC FIRE-EXTINGUISHING SYSTEM INSTALLED IN
 ACCORDANCE WITH THIS CODE.
  
 7) 2ND REQUEST. SHEET A-101 DETAIL #9 ILLUSTRATES THE
 USE OF A WALL OVEN, WHEN SCALED THE OPERATING KNOBS ARE
 LOCATED AT 4 FT. 9 INCHES ABOVE THE FINISH FLOOR OUT OF
 RANGE FOR REACH RANGES IN 308 OF THE ACCESSIBLITY CODE
 AND 309 OPERABLE PARTS.
  
 1ST ROUND OF COMMENT. SHEET A-101 DETAIL #9 ILLUSTRATES
 THE USE OF A WALL OVEN, PLEASE PROVIDE COMPLIANCE WITH
 THE ACCESS. CODE SECTIONS 308 FOR REACH RANGES AND 309
 FOR OPERABLE PARTS.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-07 Cont ID  
Sent By jwitmer Date 2017-07-07 Time 08:11 Rev Time 0.00
Received By jwitmer Date 2017-07-07 Time 07:22 Sent To  
Notes
2017-07-07 08:11:132014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17061260
 ADD: 425 24TH ST.
 CONT: CLEAR SPAN STRUCTURES
 TEL: 561-803-8100
 E-MAIL: MIACOBUCCICSSBUILDS.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JULY 07/2017
 ACTION: DENIED
  
 1) SHEET A-100 AND A-101 BOTH INDICATE THE NEW LOCATION
 OF A ROOF TOP A/C CONDENSING UNIT. THE UNIT IS LOCATED
 ABOVE 16 FEET ABOVE GRADE. PLEASE PROVIDE COMPLIANCE
 WITH 2014 FBC-B SECTION:
 ? 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR
 ELEVATED STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES HIGH OR WALKING ON ROOFS HAVING
 A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 1.1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES (762 MM).
 1.2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES (356 MM) ON CENTER.
 1.3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN
 6-INCHES (152 MM) DEEP.
 .4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM)
 BETWEEN RAILS.
 1.5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM)
 DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND
 (136.1 KG) LOAD.
 1.6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE
 PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF
 WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2).
 1.7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE
 REQUIRED ACCESS SHALL BE NOT LESS THAN 24-INCHES (610
 MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR
 SERVICE PLATFORMS.
  
 2) THE SUBMITTED MIAMI-DADE NOA 15-0820.06 WAS
 SUBMITTED BUT NONE OF THE TABLES ON THE TECHNICAL
 SHEETS IDENTIFY THE UNIT SIZE / BRACKET, WALL TYPE,
 ANCHOR TYPE, MINIMUM EMBEDMENT, MINIMUM E. D., RISK
 CATEGORY, BUILDING HEIGHT, ETC.? FBC-B 2014 FBC-B
 1604.4 ANALYSIS.
  
 3) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) SHEET A-101 SHOWS THE TICKET BOOTH TOWER AT A HIGHER
 FINISH ROOF ELEVATION THAN THE SURROUNDING PARAPET
 WALLS. IT APPEARS THAT THE PARAPET WALLS WILL REQUIRE
 GUARD RAILS IN COMPLIANCE WITH FBC-B 1013.7.
  
 5) SHEET A-100 SHOWS THE ROLLING GARAGE DOOR AS
 EXISTING, THIS SAME PAGE SHOWS DETAIL W1 & S1 FOR
 WINDOW AND SHUTTER, SHEET A-101 DETAIL 5 SHOWS
 PRESSURES FOR THIS OPENING, IS THIS PART OF THIS
 REVIEW, OR UNDER THE ORIGINAL BUILDING PERMIT?
 ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.3.
  
 6) SHEET A-101 DETAIL #9 ILLUSTRATES THE USE OF A SLIDE
 IN RANGE, PLEASE PROVIDE COMPLIANCE WITH THE FBC-B
 SECTIONS:
 9.3.2.11.5 COMMERCIAL COOKING OPERATIONS. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE INSTALLED IN COMMERCIAL
 KITCHEN EXHAUST HOOD AND DUCT SYSTEM WHERE AN AUTOMATIC
 SPRINKLER SYSTEM IS USED TO COMPLY WITH SECTION 904.
 904.2 WHERE REQUIRED. AUTOMATIC FIRE-EXTINGUISHING
 SYSTEMS INSTALLED AS AN ALTERNATIVE TO THE REQUIRED
 AUTOMATIC SPRINKLER SYSTEMS OF SECTION 903 SHALL BE
 APPROVED BY THE FIRE CODE OFFICIAL. AUTOMATIC
 FIRE-EXTINGUISHING SYSTEMS SHALL NOT BE CONSIDERED
 ALTERNATIVES FOR THE PURPOSES OF EXCEPTIONS OR
 REDUCTIONS ALLOWED BY OTHER REQUIREMENTS OF THIS CODE.
  
 904.2.1 COMMERCIAL HOOD AND DUCT SYSTEMS. EACH REQUIRED
 COMMERCIAL KITCHEN EXHAUST HOOD AND DUCT SYSTEM
 REQUIRED BY THE FLORIDA FIRE PREVENTION CODE OR CHAPTER
 5 OF THE FLORIDA BUILDING CODE, MECHANICAL TO HAVE A
 TYPE I HOOD SHALL BE PROTECTED WITH AN APPROVED
 AUTOMATIC FIRE-EXTINGUISHING SYSTEM INSTALLED IN
 ACCORDANCE WITH THIS CODE.
  
 7) SHEET A-101 DETAIL #9 ILLUSTRATES THE USE OF A WALL
 OVEN, PLEASE PROVIDE COMPLIANCE WITH THE ACCESS. CODE
 SECTIONS 308 FOR REACH RANGES AND 309 FOR OPERABLE
 PARTS.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-04-27 Cont ID  
Sent By jpearson Date 2018-04-27 Time 13:41 Rev Time 0.00
Received By jpearson Date 2018-04-27 Time 13:25 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-23 Cont ID  
Sent By jpearson Date 2017-08-23 Time 12:51 Rev Time 0.00
Received By jpearson Date 2017-08-23 Time 12:51 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-12 Cont ID  
Sent By jpearson Date 2017-07-12 Time 08:01 Rev Time 0.00
Received By jpearson Date 2017-07-12 Time 08:01 Sent To  
Notes
2017-07-12 08:09:57CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE LIGHTING CONTROLS PER FBC ENERGY CODE. FBC
 C405.2.2
 2. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2
 AND ASHREA 90.1: 8.4.2
 3. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT (CU-1) PER CODE. NEC 210.63
 4. LABEL PLANS ACCURATELY. THE DRAWINGS ON THE E-1 ARE
 LABELED AS MECHANICAL PLANS. FBC 107.2.1
 5. PROVIDE GFCI PROTECTION FOR OUTLETS IN BREAKROOM
 KITCHEN AREA. NEC 210.8(B)(2)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-04-18 Cont ID  
Sent By pleduc Date 2018-04-18 Time   Rev Time 0.00
Received By pleduc Date 2018-04-17 Time 16:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-08-22 Cont ID  
Sent By pleduc Date 2017-08-22 Time   Rev Time 0.00
Received By pleduc Date 2017-08-22 Time 07:58 Sent To  
Notes
2017-08-22 14:36:542ND REVIEW RESPONSE
  
  
 ORIGINAL COMMENTS:
  
 1) ANY WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
 THE AREA OF THE KITCHEN INDICATES A NEW WALL; P 1.
 ANYTIME A WALL IS REMOVED AND/OR ADDED IN AN EXISTING
 SPRINKLERED BUILDING, A REVIEW OF THE PROTECTION
 COVERAGE IS REQUIRED. THE PROPOSED PROJECT REQUIRES A
 REVIEW OF THE SPRINKLER COVERAGE BY A DESIGN
 PROFESSIONAL TO DETERMINE PROPER CODE COVERAGE.
  
 THIS CAN NO LONGER BE A PROVISO COMMENT.
  
 A NOTE SHALL BE ADDED TO THE SUBMITTED THAT ANY WORK ON
 THE FIRE SPRINKLER SYSTEM SHALL BE DONE UNDER SEPARATE
 SHOP DRAWINGS BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 SHOULD INCOMPLETE FIRE SPRINKLER COVERAGE BE FOUND
 DURING FIRE INSPECTIONS THE INSPECTION WILL FAIL UNTIL
 PROPER COVERAGE IS COMPLETED.
  
  
  
 2) A RANGE AND HOOD VENT IS INDICATED. PER NFPA 101,
 THE SYSTEMS SHALL BE INSTALLED PER NFPA 96 AND WITH A
 SEPARATE FIRE SUPPRESSION SYSTEM. THE HOOD SYSTEM AND
 FIRE SUPPRESSION SHALL BE SUBMITTED UNDER SEPARATE SHOP
 DRAWINGS.
  
  
 PER NFPA 101, CHAPTER 13, EXISTING ASSEMBLY OCCUPANCIES
 AND CHAPTER 39, EXISTING BUSINESS OCCUPANCIES COOKING
 EQUIPMENT SHALL BE PROTECTED:
  
 13.3.2.2 COOKING EQUIPMENT. COOKING EQUIPMENT SHALL BE
 PROTECTED IN ACCORDANCE WITH 9.2.3, UNLESS THE COOKING
 EQUIPMENT IS ONE OF THE FOLLOWING TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) PORTABLE EQUIPMENT NOT FLUE-CONNECTED
 (3) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 39.3.2.3 COOKING EQUIPMENT. COOKING EQUIPMENT SHALL BE
 PROTECTED IN ACCORDANCE WITH 9.2.3, UNLESS THE COOKING
 EQUIPMENT IS ONE OF THE FOLLOWING TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) PORTABLE EQUIPMENT NOT FLUE-CONNECTED
 (3) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING
 EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE.
  
 THE PROPOSED EQUIPMENT DOES NOT MEET THESE REQUIREMENTS
 AND SHALL BE PROTECTED ACCORDINGLY. THE STOVE AND RANGE
 TOP WOULD HAVE TO REMOVED AND REPLACED WITH EQUIPMENT
 DESIGNED TO WARM FOOD ONLY OR A SUPPRESSION SYSTEM
 WOULD NEED TO BE INSTALLED.
  
 THIS COMMENT CAN NO LONGER BE A PROVISO COMMENT. SEE
 ALSO THE BUILDING REVIEW COMMENT.
  
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-07-05 Cont ID  
Sent By pleduc Date 2017-07-05 Time   Rev Time 0.00
Received By pleduc Date 2017-07-05 Time 11:05 Sent To  
Notes
2017-07-05 13:11:20THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 2) A RANGE AND HOOD VENT IS INDICATED. PER NFPA 101,
 THE SYSTEMS SHALL BE INSTALLED PER NFPA 96 AND WITH
 ASEPARATE FIRE SUPPRESSION SYSTEM. THE HOOD SYSTEM AND
 FIRE SUPPRESSION SHALL BE SUBMITTED UNDER SEPARATE SHOP
 DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-04-27 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-13 Time 14:18 Sent To  
Notes
2018-04-16 14:19:46B20

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-25 Time   Rev Time 0.00
Received By cpuell Date 2017-08-15 Time 11:36 Sent To  
Notes
2017-08-15 11:37:38B21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-07-13 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-28 Time 14:29 Sent To  
Notes
2017-06-29 14:29:39B20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-07-07 Cont ID  
Sent By jwitmer Date 2017-07-07 Time 07:22 Rev Time 0.00
Received By jwitmer Date 2017-07-07 Time 07:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-04-24 Cont ID  
Sent By ccole Date 2018-04-24 Time 14:29 Rev Time 0.00
Received By ccole Date 2018-04-24 Time 14:29 Sent To  
Notes
2018-04-24 14:44:503RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17061260
 4/24/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ACCUREX MODEL XRRS RESIDENTIAL RECIRCULATION
 HOOD IS NOT UL 710B LISTED AND THEREFORE CANNOT BE
 INSTALLED IN A COMMERCIAL KITCHEN. PLEASE NOTE THAT
 HOODS THAT ARE UL 710B LISTED DO NOT HAVE TO BE IN
 COMPLIANCE WITH SECTION 507.12 WHICH REQUIRES THE 6"
 OVERHANG- SEE SECTION 507.1 EXCEPTION 2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-25 Cont ID  
Sent By ccole Date 2017-08-25 Time 08:31 Rev Time 0.00
Received By ccole Date 2017-08-25 Time 08:30 Sent To  
Notes
2017-08-25 08:34:492ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17061260
 8/25/17
  
 1) COMPLY WITH BUILDING REVIEW COMMENTS REGARDING THE
 CONDENSER RACK.
  
 2) TYPE II EXHAUST HOODS ARE REQUIRED FOR THE NEW
 COOKING APPLIANCES PER SECTION 507.2.3. THE HOODS MUST
 BE CONSTRUCTED WITH MATERIALS THAT ARE IN COMPLIANCE
 WITH SECTION 507.5- NO, 22 GAUGE STEEL OR NO. 24 GAGE
 STAINLESS STEEL. THE SUBMITTED SPEC SHEET FOR THE
 ELECTROLUX RANGE HOOD DOES NOT PROVIDE DATA TO SHOW
 COMPLIANCE. PLEASE NOTE THAT ONLY ONE HOOD IS SHOWN ON
  
 THE PLANS HOWEVER THERE ARE TWO HEAT PRODUCING
 APPLIANCES. IF THE INTENTION IS NOT TO PROVIDE A HOOD
 FOR THE WALL OVEN, PLEASE REFER TO SECTION 507.2.2 AND
 PROVIDE EXHAUST VENTILATION AT A RATE OF 0.70 USING 100
 SQ. FT. AS THE OCCUPYING EXHAUST AREA OF THE APPLIANCE.
  
 3) PLEASE PROVIDE A DIMENSIONED ELEVATION VIEW OF THE
 HOOD OVER THE OVEN THAT INDICATES THE MINIMUM 6"
 OVERHANG OF THE HOOD ON EACH SIDE OF THE APPLIANCE, AND
 THE DISTANCE BETWEEN THE FRONT LOWER LIP OF THE HOOD
 AND THE COOKING SURFACE- SECTION 507.12.
  
 4) AUTOMATICALLY CONTROLLED MAKE UP AIR IS REQUIRED FOR
 THE HOODS AT A RATE APPROXIMATELY EQUAL TO THE EXHAUST
 RATE- SECTION 508.1. THE TEMPERATURE DIFFERENTIAL
 BETWEEN THE MAKE UP AIR AND THE AIR IN THE CONDITIONED
 SPACE SHALL NOT EXCEED 10 DEGREES F- SECTION 508.1.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-13 Cont ID  
Sent By ccole Date 2017-07-13 Time 18:03 Rev Time 0.00
Received By ccole Date 2017-07-13 Time 17:49 Sent To  
Notes
2017-07-13 18:11:061ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17061260
 7/13/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 NEW TICKET BOOTH AND KITCHEN PER TABLE 403.3 FBC-14
 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. PLEASE NOTE
 THAT EXHAUST VENTILATION AT A RATE OF 0.70 CFMS PER SQ.
 FT. IS REQUIRED FOR THE KITCHEN.
  
 2) PROVIDE AIR BALANCE CALCULATIONS FOR THE KITCHEN.
  
 3) PLACE A NOTE ON THE PLAN TO INDICATE SEPARATE
 PERMITS ARE REQUIRED FOR THE KITCHEN EXHAUST HOOD AND
 FIRE SUPPRESSION SYSTEM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  