Plan Review Details - Permit 17061233
Plan Review Stops For Permit 17061233
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-12 Cont ID  
Sent By rmcdouga Date 2017-10-12 Time 18:40 Rev Time 0.00
Received By rmcdouga Date 2017-10-12 Time 17:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-29 Cont ID  
Sent By rmcdouga Date 2017-06-29 Time 10:53 Rev Time 0.00
Received By rmcdouga Date 2017-06-29 Time 10:34 Sent To  
Notes
2017-06-29 11:09:30PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS SPECIFY A 90 LB HOT MOP ON 30 LB FELT
 ROOFING SYSTEM. THE PRODUCT APPROVAL THAT WAS SUBMITTED
 IS FOR A SBS SELF ADHERED ROOFING SYSTEM. SUBMIT
 PRODUCT APPROVALS FOR THE SYSTEM SPECIFIED ON THE PLANS
 OR A SIGNED AND SEALED LETTER FROM THE ARCHITECT,
 BERNARD JONES, REVISING THE ROOF COVERING SYSTEM. FBC
 107.2.1
  
 2) THE SELF ADHERED SBS ROOFING SYSTEM (W-138 FROM
 FL1654) HAS A MAXIMUM DESIGN UPLIFT PRESSURE OF - 90
 PSF. THE STRUCTURE HAS A 12' MRH AND IS LOCATED IN
 EXPOSURE C WITH A 170 MPH VULT WINDSPEED. ROOF ZONE 3
 (CORNERS) REQUIRES AN UPLFT PRESSURE OF -95.7 PSF. THE
 SELECTED PRODUCT IS NOT ACCEPTABLE. FBC-R301.1

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-12 Cont ID  
Sent By rmcdouga Date 2017-10-12 Time 18:40 Rev Time 0.00
Received By rmcdouga Date 2017-10-11 Time 13:20 Sent To  
Notes
2017-10-12 13:20:16RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-29 Cont ID  
Sent By rmcdouga Date 2017-06-29 Time 10:53 Rev Time 0.00
Received By rmcdouga Date 2017-06-27 Time 10:11 Sent To  
Notes
2017-06-28 10:11:48RMCDOUGAL


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved