Plan Review Details - Permit 17061198
Plan Review Stops For Permit 17061198
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-10-17 Cont ID  
Sent By rmcdouga Date 2017-10-17 Time 14:37 Rev Time 0.00
Received By rmcdouga Date 2017-10-17 Time 14:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-18 Cont ID  
Sent By rmcdouga Date 2017-08-18 Time 15:08 Rev Time 0.00
Received By rmcdouga Date 2017-08-18 Time 14:38 Sent To  
Notes
2017-08-18 15:27:32APPROVED WITH EXCEPTION
 * THE 1 HOUR FIRE RATED FLOOR/CEILING AND WALL
 ASSEMBLIES BETWEEN THE DWELLING UNITS SHALL BE
 MAINTAINED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-21 Cont ID  
Sent By rmcdouga Date 2017-07-21 Time 14:40 Rev Time 0.00
Received By rmcdouga Date 2017-07-20 Time 17:47 Sent To  
Notes
2017-07-21 14:40:01PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS STRUCTURE HAS THREE SEPARATE LIVING SPACES EACH
 ONE HAS A KITCHEN. THEREFORE, IT IS NOT CONSIDERED A
 SINGLE FAMILY RESIDENCE (R3). THE FBC BUILDING WILL
 APPLY RATHER THAN THE FBC RESIDENTIAL. PLEASE REVISE
 THE GENERAL NOTES, DESIGN PARAMETERS AND REFERENCED
 CODES ON SHEET A2.1. FBC SECTION 310
  
 2) THE AREA TABULATIONS ON SHEETS A1.1 AND A2.1 ARE
 INCORRECT. THE EXISTING TOTAL UNDER ROOF SHOULD BE 2963
 SQFT., PLEASE CORRECT. FBC 107.2.1
  
 3) PLEASE NOTE: THIS HOUSE IS A DESIGNATED HISTORIC
 STRUCTURE AND IS EXEMPT FROM THE FBC ENERGY
 CONSERVATION REQUIREMENTS. HOWEVER, THE HEATING AND
 COOLING SYSTEM DESIGN LOAD CALCULATIONS FOR SIZING THE
 EQUIPMENT ARE REQUIRED PER FBC MECHANICAL SECTION
 312.1.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-09-25 Cont ID  
Sent By jpearson Date 2017-09-25 Time 16:09 Rev Time 0.00
Received By jpearson Date 2017-09-25 Time 16:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-08-14 Cont ID  
Sent By jpearson Date 2017-08-14 Time 10:24 Rev Time 0.00
Received By jpearson Date 2017-08-14 Time 10:24 Sent To  
Notes
2017-08-14 10:24:39CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM PROVIDED DOES NOT SHOW THE REQUIRED
 EQUIPMENT GROUNDING CONDUCTOR TO THE INTERIOR PANELS.
 ADDITIONALLY, THE INTERSYSTEM BONDING TERMINATION POINT
 IS NOT SHOWN. PROVIDE CORRECTION. NEC 250.122, 250.94
 2. PLAN PROVIDED SHOWS ONE OF THE METERS BEING
 RELOCATED TO THE REAR BUILDING. ONLY ONE SERVICE, WITH
 A MAXIMUM OF SIX DISCONNECTS, IS PERMITTED PER CODE.
 ADDITIONALLY, FPL ELECTRIC SERVICE STANDARDS STATE THAT
 ONLY ONE SERVICE DROP IS PROVIDED PER LOT. RISER
 DIAGRAM NEEDS TO BE REVISED TO SHOW ALL METERS AT THE
 SAME LOCATION, FED FROM A SINGLE SERVICE. LOAD
 CALCULATION FOR THIS SERVICE SHOULD BE PROVIDED AS
 PREVIOUSLY REQUESTED TO CONFIRM THE SERVICE SIZE IS
 ADEQUATE. MORE DETAIL SHOULD BE PROVIDED IN REFERENCE
 TO THE SERVICE CONDUCTORS IN THE RISER. WILL THERE BE 2
 SETS OF THREE 4/0 AL? PLEASE CLARIFY. NEC 230.2,
 230.71, 310.15(B)(7), FBC 107.2.1
 3. 1ST FLOOR ELECTRICAL PLAN SHOWS ONE OF THE PANELS
 LOCATED IN WHAT APPEARS TO BE THE BATHROOM AREA.
 OVERCURRENT PROTECTION DEVICES ARE NOT PERMITTED IN
 BATHROOMS. PROVIDE CORRECTION. NEC 240.24(E)
 4. ONLY ONE PANEL SCHEDULE WAS PROVIDED. PROVIDE
 SCHEDULE FOR EACH PANEL WITH THE APPROPRIATE NAME FOR
 THAT PANEL. BREAKER FOR WATER HEATER SHOULD BE A 25 AMP
 BREAKER, BASED ON THE LOAD. NEC 215.5, 408.4, 422.13,
 FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-10 Cont ID  
Sent By jpearson Date 2017-07-10 Time 14:41 Rev Time 0.00
Received By jpearson Date 2017-07-10 Time 14:41 Sent To  
Notes
2017-07-10 14:51:18CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE COMPLETE RISER DIAGRAM WITH DETAILS OF ALL
 CONDUCTOR SIZES AND THE GROUNDING ELECTRODE SYSTEM. NEC
 215.5, 250.50
 2. PROVIDE OUTLETS SPACES AS REQUIRED PER NEC. NEC
 210.52
 3. SHOW LOCATION OF ALL SMOKE ALARMS. IF NONE ARE
 EXISTING, OR ARE NOT TO CODE, SHOW AS NEW INSTALLATION
 WITH AFCI PROTECTION. FBC 907.2.11; NEC 210.12
 4. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE, INCLUDE
 ALL LOADS FROM BOTH BUILDINGS TO DETERMINE THAT SERVICE
 IS SUFFICIENTLY SIZED. NEC 220
 5. PROVIDE AFCI PROTECTION FOR ANY NEW OR ALTERED
 CIRCUITS. NEC 210.12(B)
 6. SHOW LOCATION OF ANY EXISTING ELECTRICAL PANELS. FBC
 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2017-07-21 Cont ID  
Sent By pleduc Date 2017-07-21 Time   Rev Time 0.00
Received By pleduc Date 2017-07-21 Time 17:05 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2017-10-18 Cont ID  
Sent By fmittner Date 2017-10-18 Time 10:26 Rev Time 0.00
Received By fmittner Date 2017-10-18 Time 10:26 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status F Date 2017-09-18 Cont ID  
Sent By fmittner Date 2017-09-18 Time 13:42 Rev Time 0.00
Received By fmittner Date 2017-09-18 Time 13:41 Sent To  
Notes
2017-09-18 13:42:57COVER SHEET OF COA WAS SUBMITTED BUT NO REQUIRED
 ATTACHMENTS. TOLD PERMIT RUNNER RE DEFICIENCY.

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2017-08-25 Cont ID  
Sent By fmittner Date 2017-08-25 Time 09:58 Rev Time 0.00
Received By fmittner Date 2017-08-25 Time 09:58 Sent To  
Notes
2017-08-25 09:58:51COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED.
 FRIEDERIKE E-MAILED JOE FORM.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2017-07-17 Cont ID  
Sent By aaponte Date 2017-07-17 Time 13:14 Rev Time 0.00
Received By fmittner Date 2017-07-17 Time 13:14 Sent To  
Notes
2017-07-17 13:15:41PROPERTY IN OLD NORTHWOOD HISTORIC DISTRICT: EXTERIOR
 WINDOW AND DOOR MODIFICATIONS REQUIRES A COA.
  
 QUESTIONS, CONTACT: FRIEDERIKE MITTNER, CITY HISTORIC
 PRESERVATION PLANNER AT 822-1457

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2017-10-25 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-13 Time 14:33 Sent To  
Notes
2017-10-16 14:33:58R29

Review Stop I INCOMING/PROCESSING
Rev No 3 Status F Date 2017-10-02 Cont ID  
Sent By gjohnson Date 2017-10-02 Time 15:31 Rev Time 0.00
Received By gjohnson Date 2017-09-07 Time 12:11 Sent To  
Notes
2017-09-07 12:12:02R18

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-05 Cont ID  
Sent By cpuell Date 2017-09-05 Time 16:21 Rev Time 0.00
Received By cpuell Date 2017-08-07 Time 12:49 Sent To  
Notes
2017-08-09 12:49:58R26
 **TRAVELLING WITH 17061197**

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-09 Cont ID  
Sent By lmarchan Date 2017-08-09 Time 12:49 Rev Time 0.00
Received By lmarchan Date 2017-06-27 Time 11:15 Sent To  
Notes
2017-06-29 11:15:50R26

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-10-25 Cont ID  
Sent By ccole Date 2017-10-25 Time 08:34 Rev Time 0.00
Received By ccole Date 2017-10-25 Time 07:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-09-26 Cont ID  
Sent By ccole Date 2017-09-26 Time 11:29 Rev Time 0.00
Received By ccole Date 2017-09-26 Time 08:48 Sent To  
Notes
2017-09-26 11:30:343RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17061198
 9/26/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RESUBMITTED AC CALCULATIONS FOR ZONE 1 AND ZONE
 2 ARE IDENTICAL WHICH INDICATES ONE WAS COPIED FROM THE
 OTHER. PLEASE SUBMIT ORIGINAL CALCULATIONS FOR EACH
 ZONE.
  
 2) THE RESUBMITTED AC CALCULATIONS SHOW AHRI REFERENCE
 NUMBERS THAT DO NOT MATCH THE CERTIFICATES SUBMITTED.
  
 3) AS PREVIOUSLY REQUESTED PLEASE SUBMIT SPEC SHEETS
 FOR THE RANGE HOODS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-16 Cont ID  
Sent By ccole Date 2017-08-16 Time 18:05 Rev Time 0.00
Received By ccole Date 2017-08-16 Time 12:50 Sent To  
Notes
2017-08-16 18:07:332ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17061198
 8/16/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 SOME OF THE COMMENTS FROM THE 1ST REVIEW STILL EXIST. I
 AM REPRINTING THEM BELOW WITH ADDITIONAL COMMENTS AND
 CLARIFICATIONS. PLEASE COMPLY.
  
 1ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17061198
 7/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DIRECTIONAL ORIENTATION OF SOUTH SHOWN ON THE AC
 CALCULATIONS APPEARS TO BE INCORRECT. THE HOUSE APPEARS
 TO BE FACING EAST ACCORDING TO AERIAL MAPS- SEE SECTION
 312.1
  
 2) PROVIDE THE AHRI REFERENCE NUMBER ON THE CALCULATION
 SHEET AND SUBMIT A CERTIFICATE- SECTION 301.2.
 (CERTIFICATE FOR AC# 3 SUBMTTED, BUT CERTIFICATES FOR
 AC #1 & 2 SYSTEMS NOT SUBMITTED.)
  
 4) SHEET 4.1: SHOW THE REQUIRED CLEARANCE SPACE AROUND
 AHU-1 IN THE NEW CLOSET- SECTION 603.1.1.
  
 5) 4.1: CLARIFY WHAT TYPE OF DOOR IS BEING INSTALLED AT
 THE AHU-1 CLOSET. PLEASE NOTE THAT PER SECTION 602.2
 THE DOOR SHALL BE NON-COMBUSTIBLE. (IN OTHER WORDS A
 PLENUM-RATED METAL DOOR MUST BE INSTALLED BECAUSE THIS
 IS NOT A SINGLE-FAMILY HOME. IT IS REGULATED BY THE
 COMMERCIAL CODE).
  
 7) 4.1: PROVIDE EXHAUST VENTILATION FOR THE NEW
 KITCHENS AT A RATE OF 0.70 CFMS PER SQ. FT.- TABLE
 403.3. CLARIFY IS A NEW RANGE HOOD AND EXHAUST DUCT ARE
 BEING INSTALLED AND PROVIDE DETAILS AND SUBMITTALS-
 SECTION 505. (PLEASE NOTE THE SPECS FOR THE RANGE HOODS
 WERE NOT SUBMIITED).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-07-21 Cont ID  
Sent By ccole Date 2017-07-21 Time 15:29 Rev Time 0.00
Received By ccole Date 2017-07-21 Time 15:28 Sent To  
Notes
2017-07-21 16:17:521ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17061198
 7/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DIRECTIONAL ORIENTATION OF SOUTH SHOWN ON THE AC
 CALCULATIONS APPEARS TO BE INCORRECT. THE HOUSE APPEARS
 TO BE FACING EITHER NORTH OR EAST ACCORDING TO AERIAL
 MAPS- SEE SECTION 312.1
  
 2) PROVIDE THE AHRI REFERENCE NUMBER ON THE CALCULATION
 SHEET AND SUBMIT A CERTIFICATE- SECTION 301.2.
  
 3) PLEASE CLARIFY THE SCOPE OF WORK FOR MECHANICAL ON
 THE PROJECT: SHEET 1.1 INDICATES EXISTING DUCTS AND
 DIFFUSERS, BUT SHEET 4.1 APPEARS TO INDICATE NEW DUCTS,
 DIFFUSERS, AND RETURN TRANSFERS ALONG WITH NEW AC
 SYSTEMS.
  
 4) SHEET 4.1: SHOW THE REQUIRED CLEARANCE SPACE AROUND
 AHU-1 IN THE NEW CLOSET- SECTION 603.1.1.
  
 5) 4.1: CLARIFY WHAT TYPE OF DOOR IS BEING INSTALLED AT
 THE AHU-1 CLOSET. PLEASE NOTE THAT PER SECTION 602.2
 THE DOOR SHALL BE NON-COMBUSTIBLE.
  
 6) 4.1: CLARIFY HOW THE 6" DUCT IS RUNNING THROUGH THE
 LIVING ROOM TO THE SITTING ROOM ON THE NORTH SIDE. ALL
 OTHER DUCTS ARE IN SOFFITS.
  
 7) 4.1: PROVIDE EXHAUST VENTILATION FOR THE NEW
 KITCHENS AT A RATE OF 0.70 CFMS PER SQ. FT.- TABLE
 403.3. CLARIFY IS A NEW RANGE HOOD AND EXHAUST DUCT ARE
 BEING INSTALLED AND PROVIDE DETAILS AND SUBMITTALS-
 SECTION 505.
  
 8) 4.1: PLEASE LABEL THE BATH EXHAUST FANS CORRECTLY IN
 THE LEGEND.
  
 9) 4.1: CLARIFY IF NEW CLOTHES DRYERS WILL BE INSTALLED
 IN THE APARTMENTS. SHOW THEIR LOCATIONS AND PROVIDE
 EXHAUST VENTING PLANS IF APPLICABLE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-10-21 Cont ID  
Sent By gjohnson Date 2017-10-21 Time 09:28 Rev Time 0.00
Received By gjohnson Date 2017-10-21 Time 09:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-10-02 Cont ID  
Sent By gjohnson Date 2017-10-02 Time 15:26 Rev Time 0.00
Received By gjohnson Date 2017-10-02 Time 15:26 Sent To  
Notes
2017-10-02 15:31:093RD REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS HAS NOT COMPLIED
  
 1. MISSING 2ND FLOOR KITCHEN ON THE RISER DIAGRAM
 PLEASE CLARIFY. PER WPB AMEND TP FBC 107.2.1
  
 2ND REQUEST 2. A CLEANOUT SHALL BE PROVIDED AT THE BASE
 OF EACH WASTE OR SOIL STACK. PER FBC RES P3005.2.6
  
 3.PLEASE PROVIDE WATER RISER PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 4. SHT. 2.1 DETAIL 2/2.1 THE SHOWER PAN LINERS SHALL BE
 PITCHED ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE
 FIXTURE DRAINS AND BE SECURELY FASTENED TO THE WASTE
 OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT
 JOINT BETWEEN THE LINER AND THE OUTLET. THE COMPLETED
 LINER SHALL BE TESTED IN ACCORDANCE WITH SECTION 312.9.
 PER FBC PL 417.5.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-08-22 Cont ID  
Sent By gjohnson Date 2017-08-22 Time 14:14 Rev Time 0.00
Received By gjohnson Date 2017-08-22 Time 10:24 Sent To  
Notes
2017-08-22 14:36:441ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. MISSING 2ND FLOOR KITCHEN ON THE RISER DIAGRAM
 PLEASE CLARIFY. PER WPB AMEND TP FBC 107.2.1
  
 2ND REQUEST 2. A CLEANOUT SHALL BE PROVIDED AT THE BASE
 OF EACH WASTE OR SOIL STACK. PER FBC RES P3005.2.6
  
 3.PLEASE PROVIDE WATER RISER PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 4. SHT. 2.1 DETAIL 2/2.1 THE SHOWER PAN LINERS SHALL BE
 PITCHED ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE
 FIXTURE DRAINS AND BE SECURELY FASTENED TO THE WASTE
 OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT
 JOINT BETWEEN THE LINER AND THE OUTLET. THE COMPLETED
 LINER SHALL BE TESTED IN ACCORDANCE WITH SECTION 312.9.
 PER FBC PL 417.5.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-07-11 Cont ID  
Sent By gjohnson Date 2017-07-11 Time 18:49 Rev Time 0.00
Received By gjohnson Date 2017-07-11 Time 17:48 Sent To  
Notes
2017-07-11 18:56:531ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE NEW SHOWER AND WATER CLOSET ON FIRST FLOOR ARE
 NOT VENTED. FBC RES P3101.2.1
  
 2. A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK. PER FBC RES P3005.2.6
  
 3. THE TWOWAY CLEAN OUT AT THE SEWER IS UNDER SIZED.
 CLEANOUTS SHALL BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102 MM). FOR PIPES LARGER
 THAN 4 INCHES (102 MM) NOMINAL SIZE, THE SIZE OF THE
 CLEANOUT SHALL BE NOT LESS THAN 4 INCHES (102 MM). PER
 FBC RES P3005.2.9
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  