| Plan Review Stops For Permit 17061198 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2017-10-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-10-17 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-10-17 |
Time |
14:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2017-08-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-08-18 |
Time |
15:08 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-08-18 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2017-08-18 15:27:32 | APPROVED WITH EXCEPTION | | | * THE 1 HOUR FIRE RATED FLOOR/CEILING AND WALL | | | ASSEMBLIES BETWEEN THE DWELLING UNITS SHALL BE | | | MAINTAINED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-07-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-07-21 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-07-20 |
Time |
17:47 |
Sent To |
|
|
| Notes |
| 2017-07-21 14:40:01 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THIS STRUCTURE HAS THREE SEPARATE LIVING SPACES EACH | | | ONE HAS A KITCHEN. THEREFORE, IT IS NOT CONSIDERED A | | | SINGLE FAMILY RESIDENCE (R3). THE FBC BUILDING WILL | | | APPLY RATHER THAN THE FBC RESIDENTIAL. PLEASE REVISE | | | THE GENERAL NOTES, DESIGN PARAMETERS AND REFERENCED | | | CODES ON SHEET A2.1. FBC SECTION 310 | | | | | | 2) THE AREA TABULATIONS ON SHEETS A1.1 AND A2.1 ARE | | | INCORRECT. THE EXISTING TOTAL UNDER ROOF SHOULD BE 2963 | | | SQFT., PLEASE CORRECT. FBC 107.2.1 | | | | | | 3) PLEASE NOTE: THIS HOUSE IS A DESIGNATED HISTORIC | | | STRUCTURE AND IS EXEMPT FROM THE FBC ENERGY | | | CONSERVATION REQUIREMENTS. HOWEVER, THE HEATING AND | | | COOLING SYSTEM DESIGN LOAD CALCULATIONS FOR SIZING THE | | | EQUIPMENT ARE REQUIRED PER FBC MECHANICAL SECTION | | | 312.1. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2017-09-25 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-09-25 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-09-25 |
Time |
16:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2017-08-14 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-08-14 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-08-14 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2017-08-14 10:24:39 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. RISER DIAGRAM PROVIDED DOES NOT SHOW THE REQUIRED | | | EQUIPMENT GROUNDING CONDUCTOR TO THE INTERIOR PANELS. | | | ADDITIONALLY, THE INTERSYSTEM BONDING TERMINATION POINT | | | IS NOT SHOWN. PROVIDE CORRECTION. NEC 250.122, 250.94 | | | 2. PLAN PROVIDED SHOWS ONE OF THE METERS BEING | | | RELOCATED TO THE REAR BUILDING. ONLY ONE SERVICE, WITH | | | A MAXIMUM OF SIX DISCONNECTS, IS PERMITTED PER CODE. | | | ADDITIONALLY, FPL ELECTRIC SERVICE STANDARDS STATE THAT | | | ONLY ONE SERVICE DROP IS PROVIDED PER LOT. RISER | | | DIAGRAM NEEDS TO BE REVISED TO SHOW ALL METERS AT THE | | | SAME LOCATION, FED FROM A SINGLE SERVICE. LOAD | | | CALCULATION FOR THIS SERVICE SHOULD BE PROVIDED AS | | | PREVIOUSLY REQUESTED TO CONFIRM THE SERVICE SIZE IS | | | ADEQUATE. MORE DETAIL SHOULD BE PROVIDED IN REFERENCE | | | TO THE SERVICE CONDUCTORS IN THE RISER. WILL THERE BE 2 | | | SETS OF THREE 4/0 AL? PLEASE CLARIFY. NEC 230.2, | | | 230.71, 310.15(B)(7), FBC 107.2.1 | | | 3. 1ST FLOOR ELECTRICAL PLAN SHOWS ONE OF THE PANELS | | | LOCATED IN WHAT APPEARS TO BE THE BATHROOM AREA. | | | OVERCURRENT PROTECTION DEVICES ARE NOT PERMITTED IN | | | BATHROOMS. PROVIDE CORRECTION. NEC 240.24(E) | | | 4. ONLY ONE PANEL SCHEDULE WAS PROVIDED. PROVIDE | | | SCHEDULE FOR EACH PANEL WITH THE APPROPRIATE NAME FOR | | | THAT PANEL. BREAKER FOR WATER HEATER SHOULD BE A 25 AMP | | | BREAKER, BASED ON THE LOAD. NEC 215.5, 408.4, 422.13, | | | FBC 107.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-07-10 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-07-10 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-07-10 |
Time |
14:41 |
Sent To |
|
|
| Notes |
| 2017-07-10 14:51:18 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW COMMENTS: | | | | | | 1. PROVIDE COMPLETE RISER DIAGRAM WITH DETAILS OF ALL | | | CONDUCTOR SIZES AND THE GROUNDING ELECTRODE SYSTEM. NEC | | | 215.5, 250.50 | | | 2. PROVIDE OUTLETS SPACES AS REQUIRED PER NEC. NEC | | | 210.52 | | | 3. SHOW LOCATION OF ALL SMOKE ALARMS. IF NONE ARE | | | EXISTING, OR ARE NOT TO CODE, SHOW AS NEW INSTALLATION | | | WITH AFCI PROTECTION. FBC 907.2.11; NEC 210.12 | | | 4. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE, INCLUDE | | | ALL LOADS FROM BOTH BUILDINGS TO DETERMINE THAT SERVICE | | | IS SUFFICIENTLY SIZED. NEC 220 | | | 5. PROVIDE AFCI PROTECTION FOR ANY NEW OR ALTERED | | | CIRCUITS. NEC 210.12(B) | | | 6. SHOW LOCATION OF ANY EXISTING ELECTRICAL PANELS. FBC | | | 107.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
N |
Date |
2017-07-21 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-07-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-07-21 |
Time |
17:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
4 |
Status |
P |
Date |
2017-10-18 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2017-10-18 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2017-10-18 |
Time |
10:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
F |
Date |
2017-09-18 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2017-09-18 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2017-09-18 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2017-09-18 13:42:57 | COVER SHEET OF COA WAS SUBMITTED BUT NO REQUIRED | | | ATTACHMENTS. TOLD PERMIT RUNNER RE DEFICIENCY. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
F |
Date |
2017-08-25 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2017-08-25 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2017-08-25 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2017-08-25 09:58:51 | COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. | | | FRIEDERIKE E-MAILED JOE FORM. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-07-17 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2017-07-17 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2017-07-17 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2017-07-17 13:15:41 | PROPERTY IN OLD NORTHWOOD HISTORIC DISTRICT: EXTERIOR | | | WINDOW AND DOOR MODIFICATIONS REQUIRES A COA. | | | | | | QUESTIONS, CONTACT: FRIEDERIKE MITTNER, CITY HISTORIC | | | PRESERVATION PLANNER AT 822-1457 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-10-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-10-13 |
Time |
14:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
F |
Date |
2017-10-02 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-02 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-09-07 |
Time |
12:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-09-05 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-09-05 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-08-07 |
Time |
12:49 |
Sent To |
|
|
| Notes |
| 2017-08-09 12:49:58 | R26 | | | **TRAVELLING WITH 17061197** |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-08-09 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2017-08-09 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-06-27 |
Time |
11:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2017-10-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-10-25 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-10-25 |
Time |
07:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2017-09-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-09-26 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-09-26 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2017-09-26 11:30:34 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #17061198 | | | 9/26/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE RESUBMITTED AC CALCULATIONS FOR ZONE 1 AND ZONE | | | 2 ARE IDENTICAL WHICH INDICATES ONE WAS COPIED FROM THE | | | OTHER. PLEASE SUBMIT ORIGINAL CALCULATIONS FOR EACH | | | ZONE. | | | | | | 2) THE RESUBMITTED AC CALCULATIONS SHOW AHRI REFERENCE | | | NUMBERS THAT DO NOT MATCH THE CERTIFICATES SUBMITTED. | | | | | | 3) AS PREVIOUSLY REQUESTED PLEASE SUBMIT SPEC SHEETS | | | FOR THE RANGE HOODS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-08-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-08-16 |
Time |
18:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-08-16 |
Time |
12:50 |
Sent To |
|
|
| Notes |
| 2017-08-16 18:07:33 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17061198 | | | 8/16/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | SOME OF THE COMMENTS FROM THE 1ST REVIEW STILL EXIST. I | | | AM REPRINTING THEM BELOW WITH ADDITIONAL COMMENTS AND | | | CLARIFICATIONS. PLEASE COMPLY. | | | | | | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17061198 | | | 7/21/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE DIRECTIONAL ORIENTATION OF SOUTH SHOWN ON THE AC | | | CALCULATIONS APPEARS TO BE INCORRECT. THE HOUSE APPEARS | | | TO BE FACING EAST ACCORDING TO AERIAL MAPS- SEE SECTION | | | 312.1 | | | | | | 2) PROVIDE THE AHRI REFERENCE NUMBER ON THE CALCULATION | | | SHEET AND SUBMIT A CERTIFICATE- SECTION 301.2. | | | (CERTIFICATE FOR AC# 3 SUBMTTED, BUT CERTIFICATES FOR | | | AC #1 & 2 SYSTEMS NOT SUBMITTED.) | | | | | | 4) SHEET 4.1: SHOW THE REQUIRED CLEARANCE SPACE AROUND | | | AHU-1 IN THE NEW CLOSET- SECTION 603.1.1. | | | | | | 5) 4.1: CLARIFY WHAT TYPE OF DOOR IS BEING INSTALLED AT | | | THE AHU-1 CLOSET. PLEASE NOTE THAT PER SECTION 602.2 | | | THE DOOR SHALL BE NON-COMBUSTIBLE. (IN OTHER WORDS A | | | PLENUM-RATED METAL DOOR MUST BE INSTALLED BECAUSE THIS | | | IS NOT A SINGLE-FAMILY HOME. IT IS REGULATED BY THE | | | COMMERCIAL CODE). | | | | | | 7) 4.1: PROVIDE EXHAUST VENTILATION FOR THE NEW | | | KITCHENS AT A RATE OF 0.70 CFMS PER SQ. FT.- TABLE | | | 403.3. CLARIFY IS A NEW RANGE HOOD AND EXHAUST DUCT ARE | | | BEING INSTALLED AND PROVIDE DETAILS AND SUBMITTALS- | | | SECTION 505. (PLEASE NOTE THE SPECS FOR THE RANGE HOODS | | | WERE NOT SUBMIITED). | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-07-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-07-21 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-07-21 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2017-07-21 16:17:52 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17061198 | | | 7/21/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE DIRECTIONAL ORIENTATION OF SOUTH SHOWN ON THE AC | | | CALCULATIONS APPEARS TO BE INCORRECT. THE HOUSE APPEARS | | | TO BE FACING EITHER NORTH OR EAST ACCORDING TO AERIAL | | | MAPS- SEE SECTION 312.1 | | | | | | 2) PROVIDE THE AHRI REFERENCE NUMBER ON THE CALCULATION | | | SHEET AND SUBMIT A CERTIFICATE- SECTION 301.2. | | | | | | 3) PLEASE CLARIFY THE SCOPE OF WORK FOR MECHANICAL ON | | | THE PROJECT: SHEET 1.1 INDICATES EXISTING DUCTS AND | | | DIFFUSERS, BUT SHEET 4.1 APPEARS TO INDICATE NEW DUCTS, | | | DIFFUSERS, AND RETURN TRANSFERS ALONG WITH NEW AC | | | SYSTEMS. | | | | | | 4) SHEET 4.1: SHOW THE REQUIRED CLEARANCE SPACE AROUND | | | AHU-1 IN THE NEW CLOSET- SECTION 603.1.1. | | | | | | 5) 4.1: CLARIFY WHAT TYPE OF DOOR IS BEING INSTALLED AT | | | THE AHU-1 CLOSET. PLEASE NOTE THAT PER SECTION 602.2 | | | THE DOOR SHALL BE NON-COMBUSTIBLE. | | | | | | 6) 4.1: CLARIFY HOW THE 6" DUCT IS RUNNING THROUGH THE | | | LIVING ROOM TO THE SITTING ROOM ON THE NORTH SIDE. ALL | | | OTHER DUCTS ARE IN SOFFITS. | | | | | | 7) 4.1: PROVIDE EXHAUST VENTILATION FOR THE NEW | | | KITCHENS AT A RATE OF 0.70 CFMS PER SQ. FT.- TABLE | | | 403.3. CLARIFY IS A NEW RANGE HOOD AND EXHAUST DUCT ARE | | | BEING INSTALLED AND PROVIDE DETAILS AND SUBMITTALS- | | | SECTION 505. | | | | | | 8) 4.1: PLEASE LABEL THE BATH EXHAUST FANS CORRECTLY IN | | | THE LEGEND. | | | | | | 9) 4.1: CLARIFY IF NEW CLOTHES DRYERS WILL BE INSTALLED | | | IN THE APARTMENTS. SHOW THEIR LOCATIONS AND PROVIDE | | | EXHAUST VENTING PLANS IF APPLICABLE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2017-10-21 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-21 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-21 |
Time |
09:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2017-10-02 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-02 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-02 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2017-10-02 15:31:09 | 3RD REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: PREVIOUS COMMENTS HAS NOT COMPLIED | | | | | | 1. MISSING 2ND FLOOR KITCHEN ON THE RISER DIAGRAM | | | PLEASE CLARIFY. PER WPB AMEND TP FBC 107.2.1 | | | | | | 2ND REQUEST 2. A CLEANOUT SHALL BE PROVIDED AT THE BASE | | | OF EACH WASTE OR SOIL STACK. PER FBC RES P3005.2.6 | | | | | | 3.PLEASE PROVIDE WATER RISER PER WPB AMEND TO FBC | | | 107.3.5.1.3(13) | | | | | | 4. SHT. 2.1 DETAIL 2/2.1 THE SHOWER PAN LINERS SHALL BE | | | PITCHED ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL | | | (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE | | | FIXTURE DRAINS AND BE SECURELY FASTENED TO THE WASTE | | | OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT | | | JOINT BETWEEN THE LINER AND THE OUTLET. THE COMPLETED | | | LINER SHALL BE TESTED IN ACCORDANCE WITH SECTION 312.9. | | | PER FBC PL 417.5.2 | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2017-08-22 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-08-22 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-08-22 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2017-08-22 14:36:44 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. MISSING 2ND FLOOR KITCHEN ON THE RISER DIAGRAM | | | PLEASE CLARIFY. PER WPB AMEND TP FBC 107.2.1 | | | | | | 2ND REQUEST 2. A CLEANOUT SHALL BE PROVIDED AT THE BASE | | | OF EACH WASTE OR SOIL STACK. PER FBC RES P3005.2.6 | | | | | | 3.PLEASE PROVIDE WATER RISER PER WPB AMEND TO FBC | | | 107.3.5.1.3(13) | | | | | | 4. SHT. 2.1 DETAIL 2/2.1 THE SHOWER PAN LINERS SHALL BE | | | PITCHED ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL | | | (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE | | | FIXTURE DRAINS AND BE SECURELY FASTENED TO THE WASTE | | | OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT | | | JOINT BETWEEN THE LINER AND THE OUTLET. THE COMPLETED | | | LINER SHALL BE TESTED IN ACCORDANCE WITH SECTION 312.9. | | | PER FBC PL 417.5.2 | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-07-11 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-07-11 |
Time |
18:49 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-07-11 |
Time |
17:48 |
Sent To |
|
|
| Notes |
| 2017-07-11 18:56:53 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE NEW SHOWER AND WATER CLOSET ON FIRST FLOOR ARE | | | NOT VENTED. FBC RES P3101.2.1 | | | | | | 2. A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH | | | WASTE OR SOIL STACK. PER FBC RES P3005.2.6 | | | | | | 3. THE TWOWAY CLEAN OUT AT THE SEWER IS UNDER SIZED. | | | CLEANOUTS SHALL BE THE SAME NOMINAL SIZE AS THE PIPE | | | THEY SERVE UP TO 4 INCHES (102 MM). FOR PIPES LARGER | | | THAN 4 INCHES (102 MM) NOMINAL SIZE, THE SIZE OF THE | | | CLEANOUT SHALL BE NOT LESS THAN 4 INCHES (102 MM). PER | | | FBC RES P3005.2.9 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | |
|
|