Plan Review Details - Permit 17061197
Plan Review Stops For Permit 17061197
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-10-25 Cont ID  
Sent By rmcdouga Date 2017-10-25 Time 15:01 Rev Time 0.00
Received By rmcdouga Date 2017-10-25 Time 15:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-10-17 Cont ID  
Sent By rmcdouga Date 2017-10-17 Time 14:04 Rev Time 0.00
Received By rmcdouga Date 2017-10-17 Time 14:04 Sent To  
Notes
2017-10-17 14:05:04PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY FORMS R405-2014. FBC ENERGY CONSERVATION
 R103.1.1.2
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-18 Cont ID  
Sent By rmcdouga Date 2017-08-18 Time 13:58 Rev Time 0.00
Received By rmcdouga Date 2017-08-17 Time 11:51 Sent To  
Notes
2017-08-18 13:58:32PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY FORMS R405-2014. FBC ENERGY CONSERVATION
 R103.1.1.2
  
 2) CLARIFY HOW THE PENETRATIONS OF THE FIRE RATED
 CEILING/FLOOR ASSEMBLY FOR THE MECHANICAL DUCT WORK AND
 ELECTRICAL CEILING FIXTURES WILL ADDRESSED. R302.4
 DWELLING UNIT RATED PENETRATIONS. PENETRATIONS OF WALL
 OR FLOOR/CEILING ASSEMBLIES REQUIRED TO BE
 FIRE-RESISTANCE RATED IN ACCORDANCE WITH SECTION R302.2
 OR R302.3 SHALL BE PROTECTED IN ACCORDANCE WITH THIS
 SECTION.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-20 Cont ID  
Sent By rmcdouga Date 2017-07-20 Time 17:16 Rev Time 0.00
Received By rmcdouga Date 2017-07-20 Time 11:21 Sent To  
Notes
2017-07-20 16:35:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY FORMS R405-2014. FBC ENERGY CONSERVATION
 R103.1.1.2
  
 2) THE EXISTING AREA TABULATION TABLES ON THE PLANS ARE
 INCORRECT. THE GARAGE/STORAGE SPACE ON THE FIRST FLOOR
 SHOULD NOT BE INCLUDED IN THE EXISTING LIVING AREA. FBC
 107.2.1
  
 3) SHOW THAT THE GARAGE/STORAGE AREA WILL COMPLY WITH
 THE FOLLOWING: FBC - R302.3 TWO-FAMILY DWELLINGS.
 DWELLING UNITS IN TWO-FAMILY DWELLINGS SHALL BE
 SEPARATED FROM EACH OTHER BY WALL AND/OR FLOOR
 ASSEMBLIES HAVING NOT LESS THAN A 1-HOUR
 FIRE-RESISTANCE RATING WHEN TESTED IN ACCORDANCE WITH
 ASTM E 119 OR UL 263. FIRE-RESISTANCE-RATED
 FLOOR/CEILING AND WALL ASSEMBLIES SHALL EXTEND TO AND
 BE TIGHT AGAINST THE EXTERIOR WALL, AND WALL ASSEMBLIES
 SHALL EXTEND FROM THE FOUNDATION TO THE UNDERSIDE OF
 THE ROOF SHEATHING. R302.3.1 SUPPORTING CONSTRUCTION.
 WHEN FLOOR ASSEMBLIES ARE REQUIRED TO BE
 FIRE-RESISTANCE RATED BY SECTION R302.3, THE SUPPORTING
 CONSTRUCTION OF SUCH ASSEMBLIES SHALL HAVE AN EQUAL OR
 GREATER FIRE-RESISTANCE RATING. R302.4 DWELLING UNIT
 RATED PENETRATIONS. PENETRATIONS OF WALL OR
 FLOOR/CEILING ASSEMBLIES REQUIRED TO BE FIRE-RESISTANCE
 RATED IN ACCORDANCE WITH SECTION R302.2 OR R302.3 SHALL
 BE PROTECTED IN ACCORDANCE WITH THIS SECTION.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-09-25 Cont ID  
Sent By jpearson Date 2017-09-25 Time 16:09 Rev Time 0.00
Received By jpearson Date 2017-09-25 Time 16:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-08-14 Cont ID  
Sent By jpearson Date 2017-08-14 Time 10:34 Rev Time 0.00
Received By jpearson Date 2017-08-14 Time 10:33 Sent To  
Notes
2017-08-14 10:33:49CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM PROVIDED DOES NOT SHOW THE REQUIRED
 EQUIPMENT GROUNDING CONDUCTOR TO THE INTERIOR PANELS.
 PROVIDE CORRECTION. NEC 250.122
 2. PLAN PROVIDED SHOWS A SEPARATE SERVICE FOR THE REAR
 BUILDING. PREVIOUS COMMENT MENTIONED THIS AND WAS NOT
 ADDRESSED SATISFACTORILY. ONLY ONE SERVICE, WITH A
 MAXIMUM OF SIX DISCONNECTS, IS PERMITTED PER CODE.
 ADDITIONALLY, FPL ELECTRIC SERVICE STANDARDS STATE THAT
 ONLY ONE SERVICE DROP IS PROVIDED PER LOT. RISER
 DIAGRAM NEEDS TO BE REVISED TO SHOW ALL METERS AT THE
 SAME LOCATION, FED FROM A SINGLE SERVICE LOCATED AT THE
 FRONT BUILDING. THE RISER DIAGRAM PROVIDED STATES THAT
 IT IS FOR THE FRONT BUILDING, BUT PLAN SUBMITTED FOR
 PERMIT 17061198 SHOWS DIFFERENT INFORMATION. PLEASE
 CLARIFY AND/OR CORRECT. NEC 230.2, 230.71,
 310.15(B)(7), FBC 107.2.1
 3. PANELS ARE SHOWN AS MAIN LUG ONLY. A DISCONNECT IS
 REQUIRED FOR SEPARATE STRUCTURES. PROVIDE CORRECTION.
 NEC 225.31, 225.32
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-10 Cont ID  
Sent By jpearson Date 2017-07-10 Time 13:25 Rev Time 0.00
Received By jpearson Date 2017-07-10 Time 13:25 Sent To  
Notes
2017-07-10 13:50:59CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. ONLY ONE SERVICE IS PERMITTED. CURRENTLY, THE
 SERVICE FOR THE DOWNSTAIRS IS LOCATED ON THE MAIN
 HOUSE. IT IS NOT PERMISSIBLE TO ADD AN ADDITIONAL
 SERVICE FED FROM A DIFFERENT LOCATION. PROVIDE LOAD
 CALCULATION FOR ENTIRE SERVICE SHOWING REQUIRED SERVICE
 SIZE. NEC 230.2, 220
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE AND GROUNDING ELECTRODE SYSTEM. NEC 215.5,
 250.50
 2. PROVIDE SERVICE DISCONNECT FOR EACH PANEL. NEC
 230.70
 3. WIRE SIZE SHOWN TO UPSTAIRS PANEL IS #3 CU, WHICH IS
 NOT RATED FOR 125 AMPS. PROVIDE CORRECTION. NEC
 310.15(B)(7), 310.15(B)(16)
 4. INDICATE CIRCUIT FOR SMOKE ALARMS INSTALLED, PROVIDE
 AFCI PROTECTION AND INTERCONNECTION AS REQUIRED. FBC
 R314; FBC 107.3.5, 107.2.1; NEC 210.12
 5. THERE IS A NOTE THAT STATES TAMPER RESISTANT OUTLETS
 ARE REQUIRED PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT OUTLETS. PROVIDE CORRECTION.
 NEC 406.12; FBC 107.2.1
 6. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS. PROVIDE NOTE TO COMPLY.
 NEC 410.16
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2017-10-18 Cont ID  
Sent By fmittner Date 2017-10-18 Time 10:27 Rev Time 0.00
Received By fmittner Date 2017-10-18 Time 10:27 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status F Date 2017-09-18 Cont ID  
Sent By fmittner Date 2017-09-18 Time 13:48 Rev Time 0.00
Received By fmittner Date 2017-09-18 Time 13:48 Sent To  
Notes
2017-09-18 13:49:06STILL NO DETAILED SITE PLAN/SURVEY DEMONSTARTING
 ADEQUATE PARKING FOR SITE, ESPECIALLY AFTER LOSS OF
 GARAGE.

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2017-08-25 Cont ID  
Sent By fmittner Date 2017-08-25 Time 10:07 Rev Time 0.00
Received By fmittner Date 2017-08-25 Time 10:07 Sent To  
Notes
2017-08-25 10:08:47PROVIDE SITE PLAN SHOWING PARKING REQUIREMENTS ARE
 STILL BEING MET ON SITE WITH LOSS OF GARAGE.
  
 FRIEDERIKE MITTNER, 822-1457

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2017-07-17 Cont ID  
Sent By fmitner Date 2017-07-17 Time 13:17 Rev Time 0.00
Received By fmittner Date 2017-07-17 Time 13:17 Sent To  
Notes
2017-07-17 13:19:10PLANS CONFLICT. IS WINDOW BEING INFILLED OR REPLACED?
 PROPERTY IN HISTORIC DISTRICT.....NEED ELEVATIONS,
 WINDOW DETAILS.
  
 QUESTIONS, CONTATC: FRIEDERIKE MITTNER, CITY HISOTIC
 PRESERVATION PLANNER AT 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-10-17 Cont ID  
Sent By rmcdouga Date 2017-10-17 Time 14:05 Rev Time 0.00
Received By rmcdouga Date 2017-09-07 Time 12:13 Sent To  
Notes
2017-10-16 14:34:38R29

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-05 Cont ID  
Sent By cpuell Date 2017-09-05 Time 16:21 Rev Time 0.00
Received By cpuell Date 2017-08-07 Time 12:49 Sent To  
Notes
2017-08-09 12:49:16R26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-20 Cont ID  
Sent By rmcdouga Date 2017-07-20 Time 17:16 Rev Time 0.00
Received By rmcdouga Date 2017-06-27 Time 11:13 Sent To  
Notes
2017-06-29 11:13:12R26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2017-10-26 Cont ID  
Sent By rmcdouga Date 2017-10-26 Time 09:33 Rev Time 0.00
Received By rmcdouga Date 2017-10-26 Time 09:33 Sent To  
Notes
2017-10-26 09:34:00NO FEES WERE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-10-17 Cont ID  
Sent By rmcdouga Date 2017-10-17 Time 14:03 Rev Time 0.00
Received By rmcdouga Date 2017-10-17 Time 14:03 Sent To  
Notes
2017-10-17 14:05:33BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-07-20 Cont ID  
Sent By rmcdouga Date 2017-07-20 Time 11:21 Rev Time 0.00
Received By rmcdouga Date 2017-07-20 Time 11:21 Sent To  
Notes
2017-07-20 11:22:57BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-07-20 Cont ID  
Sent By rmcdouga Date 2017-07-20 Time 11:21 Rev Time 0.00
Received By rmcdouga Date 2017-07-20 Time 11:21 Sent To  
Notes
2017-08-18 11:10:27CONTRIBUTING HISTORIC STRUCTURE

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-07-11 Cont ID  
Sent By gjohnson Date 2017-07-11 Time 18:41 Rev Time 0.00
Received By gjohnson Date 2017-07-11 Time 18:41 Sent To  
Notes
***NONE***