Plan Review Details - Permit 17061148
Plan Review Stops For Permit 17061148
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-03-15 Cont ID  
Sent By jgomez Date 2018-03-14 Time 19:01 Rev Time 0.00
Received By jgomez Date 2018-03-14 Time 17:34 Sent To  
Notes
2018-03-14 17:51:26BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE FLAT ROOF RAS 117 CALCULATIONS SUBMITTED:
 (A) APPROVED SYSTEM DOESN'T MATCH SYSTEM SYSTEM
 SUBMITTED WITH NOA 14-0529.02.
 (B)RAS 117 CALCULATIONS NEED TO BE SIGNED AND SEALED BY
 THE ENGINEER. CHAPTER 471 F.S

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-10-12 Cont ID  
Sent By jgomez Date 2017-10-12 Time 12:38 Rev Time 0.00
Received By jgomez Date 2017-10-12 Time 12:10 Sent To  
Notes
2017-10-05 09:14:11RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- SOME PLANS ARE MISSING THE SIGNATURE AND SEAL OF THE
 ARCHITECT OF RECORD. ALL PLANS NEED TO BE PROPERLY
 SIGNED AND SEALED AS REQUIRED BY SEC. 61G1-16.001 FAC
 AND CHAPTER 481 FLORIDA STATUTE.
 REPEAT COMMENT.
  
 2- SIZE OF FOOTINGS SPECIFIED ON PLANS AND SIZE OF
 FOOTINGS RECOMMENDED ON THE SOIL TEST REPORT SUBMITTED
 DON'T MATCH. ARCHITECT OF RECORD TO REVIEW SOIL TEST
 REPORT AND REVISE SIZE OF FOOTINGS PER GEOTECHNICAL
 ENGINEER RECOMMENDATIONS OR PROVIDE CALCULATIONS
 SHOWING THAT PROPOSED SIZES ARE ADEQUATE BASED ON THE
 SOIL CONDITIONS SHOWN ON THE SOIL TEST REPORT. SEC.
 R301.1 FBC-RESIDENTIAL, 5TH EDITION.
  
 3- IT LOOKS LIKE THE WINDOWS TYPE AND SIZE SPECIFIED
 FOR THE SECOND FLOOR BEDROOMS DON'T COMPLY WITH THE
 MINIMUM OPENING HEIGHT OF THE EGRESS REQUIREMENTS.
 REVISE AS REQUIRED TO COMPLY. SEC. R310.1.2
 FBC-RESIDENTIAL.
 NOTE: ACCORDING TO PGT WINDOW MANUFACTURER THE SINGLE
 HUNG WINDOW SIZE SPECIFIED ON PLANS DOESN'T COMPLY WITH
 THE REQUIRED EGRESS HEIGHT. PROVIDE MANUFACTURER'S CUT
 SHEETS SHOWING COMPLIANCE WITH ALL THE EGRESS
 REQUIREMENTS.
 REPEAT COMMENT.
  
 4- OVERHEAD DOOR JAMB DETAIL 2/A6:
 A) FASTENING SPECIFICATIONS OF THE 2X8 JAMB DON'T SEEM
 TO BE ADEQUATE TO SUPPORT THE LOADS TRANSFERED FROM THE
 DOOR TRACK. ORIGINAL DETAIL SPECIFIED 1/4" TAPCONS. NOW
 SPECIFICATIONS CALL FOR A REDUCED SCREW SIZE (#10).
 REVISE FASTENING SPECIFICATIONS OR PROVIDE CALCULATIONS
 SHOWING THAT SPECIFIED #10 SCREWS ARE ADEQUATE TO
 RESIST THE LOADS. SEE GARAGE DOOR PRODUCT APPROVAL
 SUBMITTED FOR JAMB SPECIFICATIONS AND REVISE AS
 REQUIRED. SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
 REPEAT COMMENT. PARTIALLY ADDRESSED.
  
 B) DETAIL SPECIFIES (3)2X4 STUDS. STUD BEARING WALL
 FRAMING DETAIL 3/A6 SPECIFIES. (4) 2X4 STUDS. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
 REPEAT COMMENT.
  
 5- THE LIVE LOAD OF THE SECOND FLOOR SPECIFIED ON THE
 GRAVITY LOADS ON SHEET S1 NEED TO BE REVISED TO COMPLY
 WITH TABLE R301.5 FBC-RESIDENTIAL.
 NOTE: SPECIFY THE LIVE LOADS FOR ROOMS OTHER THAN
 SLEEPING ROOMS, STAIRS, ETC.
 REPEAT COMMENT.
  
 6- ACCORDING TO SEC. R301.2.1.4 THIS BUILDING IS
 LOCATED IN EXPOSURE "C" NOT EXPOSURE "B". REVISE THE
 SURFACE ROUGHNESS, EXPOSURE CATEGORY AND HEIGHT
 ADJUSTMENT COEFFICIENT ON THE WIND LOAD FACTORS SHOWN
 ON SHEET S1.
 REPEAT COMMENT. NOT ADDRESSED.
  
 7- GARAGE DOOR LEADING TO THE HOUSE NEED TO BE EQUIPPED
 WITH SELF CLOSING DEVICE AS REQUIRED BY SEC. R302.5.1
 FBC-RESIDENTIAL. PROVIDE SPECIFICATIONS ON PLANS ADDING
 THIS REQUIREMENT.
  
 8- UPDATE THE YEAR OF ALL THE STANDARDS REFERENCED ON
 THE CONCRETE AND MASONRY WALLS NOTES ON SHEET S1. SEE
 CHAPTER 46 OF THE FBC-RESIDENTIAL FOR CURRENT YEAR OF
 EACH STANDARD AND REVISED AS REQUIRED.
 REPEAT COMMENT. NOT ADDRESSED.
  
 9- SHEET S2: SPECIFY ROOF SLOPE FOR NEW ROOF OVER PATIO
 AS REQUIRED BY SEC. R905.11.1 FBC-RESIDENTIAL.
 REPEAT COMMENT. NOT ADDRESSED.
  
 10- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AT THE
 BOTTOM OF FORM AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 REPEAT COMMENT. NOT ADDRESSED.
  
 NOTE: LABEL REQUIRED FOR THE DOORS AND WINDOWS SHOWING
 THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS IS REQUIRED WHEN CALCULATIONS DON'T USE
 THE DEFAULT FACTORS FOR GLAZING.
  
 11- FLAT ROOF NOA 14-0529.02 SUBMITTED: THE DESIGN
 PRESSURE OF SELECTED ASSEMBLY ON PAGE 26 OF 42 DOESN'T
 MEET THE DESIGN PRESSURE FOR ALL ROOF ZONES. PROVIDE
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT THE PERIMETER AND CORNER AREAS AS REQUIRED
 BY GENERAL LIMITATION #7 ON LAST PAGE OF THE NOA. NEED
 THE CALCULATIONS TO MEET THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL.
 REPEAT COMMENT.
  
 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) PRECAST LINTELS AS SPECIFIED ON PLANS.
 REPEAT COMMENT.
  
 B) CEMENT BOARD SOFFIT AS SPECIFIED ON PLANS.
 REPEAT COMMENT.
  
 13- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVAL AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 NOTE: DESIGNER OF RECORD MAY BE CHARGED 4 TIMES THE
 PLAN REVIEW FEE FOR MULTIPLE REJECTIONS AS REQUIRED BY
 FLORIDA STATUTE 553.80(2)(B).
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-24 Cont ID  
Sent By jgomez Date 2017-07-24 Time 15:41 Rev Time 0.00
Received By jgomez Date 2017-07-21 Time 18:50 Sent To  
Notes
2017-07-21 18:56:41RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. BRING
 BACK COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF
 FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  
 2- THE PROPOSED GARAGE SHOWS A DOOR LEADING TO THE
 EXISTING MASTER BEDROOM. GARAGE LEADING TO A BEDROOM IS
 NOT ALLOWED. REVISE PLANS AS REQUIRED BY SEC. R302.5.1
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- PROVIDE SOIL TEST REPORT. SEC. R401.4
 FBC-RESIDENTIAL.
  
 4- IT LOOKS LIKE THE WINDOWS TYPE AND SIZE SPECIFIED
 FOR THE SECOND FLOOR BEDROOMS DON'T COMPLY WITH THE
 MINIMUM OPENING AREA AND MINIMUM OPENING HEIGHT OF THE
 EGRESS REQUIREMENTS. REVISE AS REQUIRED TO COMPLY. OR
 PROVIDE WINDOW MANUFACTURER'S CUT SHEETS SHOWING
 COMPLIANCE. SEC. R310.1.1 AND SEC. R310.1.2
 FBC-RESIDENTIAL.
  
 5- SPECIFY ROOF CROSS VENTILATION FOR THE NEW GARAGE AS
 REQUIRED BY SEC. R806 FBC-RESIDENTIAL.
  
 6- OVERHEAD DOOR JAMB DETAIL 2/A6:
 A) FASTENING SPECIFICATIONS ARE FOR BLOCK CONSTRUCTION.
 THE FRAMING FOR THE GARAGE DOOR IS WOOD. REVISE AS
 REQUIRED TO MATCH PLANS. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) DETAIL SPECIFIES (3)2X4 STUDS. STUD BEARING WALL
 FRAMING DETAIL 3/A6 SPECIFIES. (4) 2X4 STUDS. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 7- THE LIVE LOAD OF THE SECOND FLOOR SPECIFIED ON THE
 GRAVITY LOADS ON SHEET S1 NEED TO BE REVISED TO COMPLY
 WITH TABLE R301.5 FBC-RESIDENTIAL.
  
 8- ACCORDING TO SEC. R301.2.1.4 THIS BUILDING IS
 LOCATED IN EXPOSURE "C" NOT EXPOSURE "B". REVISE THE
 SURFACE ROUGHNESS, EXPOSURE CATEGORY AND HEIGHT
 ADJUSTMENT COEFFICIENT ON THE WIND LOAD FACTORS ON
 SHEET S1.
  
 9- UPDATE THE YEAR OF ALL THE STANDARDS REFERENCED ON
 THE CONCRETE AND MASONRY WALLS NOTES ON SHEET S1. SEE
 CHAPTER 46 OF THE FBC-RESIDENTIAL FOR CURRENT YEAR OF
 EACH STANDARD AND REVISED AS REQUIRED.
  
 10- SHEET S2: SPECIFY ROOF SLOPE FOR NEW ROOF OVER
 PATIO AS REQUIRED BY SEC. R905.11.1 FBC-RESIDENTIAL.
  
 11- EXTERIOR ELEVATIONS ON SHEET A4 AND DOOR SCHEDULE
 ON SHEET A2 SPECIFIES DOOR "C" TO BE FIBERGLASS SOLID
 DOOR. DOOR NOA 14-1117.05 SUBMITTED IS FOR ALUMINUM
 DOOR WITH GLAZING. PLANS AND PRODUCT APPROVAL NEED TO
 MATCH. DOOR WITH GLAZING NEEDS TO BE CONSIDERED IN THE
 ENERGY CALCULATIONS. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 12- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AT THE
 BOTTOM OF FORM AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) NEED THE NAME AT THE BOTTOM OF FORM OF THE PERSON
 PREPARING THE CALCULATIONS AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING CORRECT OWNER'S NAME AND BUILDER'S NAME. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) THIS IS A TWO STORY ADDITION. SPECIFY THE FLOOR AREA
 OF THE SECOND FLOOR ON ITEM #8. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E) THIS IS A TWO STORY ADDITION. REVISE THE UNDER ATTIC
 AREA SPECIFIED ON ITEM #10. THE UNDER ATTIC AREA IS THE
 AREA ABOVE THE SECOND FLOOR. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 F) REVISE ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4 TO
 MATCH PLANS AND PRODUCT APPROVAL SUBMITTED. IT'S NOT
 SHINGLES. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) DOORS INFORMATION ON PAGE 3 OF 4 NEED TO BE
 COORDINATED WITH PLANS AND PRODUCT APPROVAL SUBMITTED.
 COORDINATE WITH ITEM #11 ABOVE. REVISE AS REQUIRED TO
 MATCH. DOOR WITH GLASS NEEDS TO BE CONSIDERED WITH THE
 WINDOWS AREAS AS REQUIRED BY SEC. R405.5.3.3 FBC-ENERGY
 CONSERVATION.
  
 H) GARAGE AREA SHOWN ON PAGE 3 OF 4 DOESN'T MATCH
 GARAGE AREA SHOWN ON PLANS. REVISE AS REQUIRED TO
 MATCH. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 NOTE: LABEL REQUIRED FOR THE DOORS AND WINDOWS SHOWING
 THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS IS REQUIRED WHEN CALCULATIONS DON'T USE
 THE DEFAULT FACTORS FOR GLAZING.
  
 13- ALL THE PLANS NEED TO BE SIGNED, SEALED AND DATED
 BY THE ARCHITECT OF RECORD. SEC. 61G1-16.001 FAC.
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) FLAT ROOF. AND CLEARLY IDENTIFY WHICH APPROVED
 ASSEMBLY IS GOING TO BE INSTALLED. NOTE: IF THE DESIGN
 PRESSURES OF THE SELECTED ASSEMBLY DON'T MEET THE
 DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND
 SEALED RAS 117 CALCULATIONS WILL BE REQUIRED.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 C) CEMENT BOARD SOFFIT AND TRIM AS SPECIFIED ON PLANS.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVAL
 (INCLUDING THE ONES THAT WERE ALREADY SUBMITTED) AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 16- DESIGNER OF RECORD TO SPECIFY CARBON MONOXIDE
 ALARMS FOR ALL THE BEDROOMS IN THE EXISTING HOUSE AS
 REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-03-15 Cont ID  
Sent By jpearson Date 2018-03-15 Time 11:59 Rev Time 0.00
Received By jpearson Date 2018-03-15 Time 11:05 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-10-17 Cont ID  
Sent By jpearson Date 2017-10-17 Time 11:15 Rev Time 0.00
Received By jpearson Date 2017-10-17 Time 07:32 Sent To  
Notes
2017-10-17 11:15:08CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS CORRECTED ARE NOTED, THE
 REMAINING ITEMS NEED FURTHER CORRECTION. EXPLANATION IN
 (PARENTHESES):
  
 1. BASED ON THE LOAD CALCULATION PROVIDED, THE EXISTING
 SERVICE IS TOO SMALL TO ACCOMMODATE THE LOAD. PROVIDE
 CORRECTION. NEC 215.2, 220, FBC RE3602.1 (THE LAUNDRY
 CIRCUIT MUST BE CALCULATED AT 1500 VA. ALTHOUGH THIS
 DOESN'T CHANGE THE SERVICE SIZE, PROVIDE CORRECTION SO
 RECORDS ARE CORRECT.)
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. PROVIDE PANEL SCHEDULE/SIZING FOR ALL PANELS.
 INDICATE ANY NEW OR ALTERED CIRCUITS, AFCI OR GFCI
 PROTECTION AS REQUIRED. NEC 215.5, 408.4, 408.30 FBC
 RE3706.1 (PANEL SP SHOWS THE WATER HEATER ON A 30 AMP
 BREAKER. BASED ON 125% OF THE LOAD, THIS BREAKER SHOULD
 BE A 25 AMP. PROVIDE CORRECTION. ALSO, THE NEW PANEL SP
 DOES NOT INDICATE AFCI OR GFCI AS REQUESTED. A NOTE
 WILL SUFFICE, STATING: "ALL 120-VOLT, SINGLE PHASE, 15
 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN
 DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC
 RE3902.12")
 6. CORRECTED.
 7. CORRECTED.
 8. PROVIDE DETAILS OF SAUNA. DOES THIS REQUIRE GFCI
 PROTECTION? NEC 110.3; FBC 107.2.1 (DETAILS AND/OR SPEC
 SHEETS NOT PROVIDED, AND THERE IS CONFLICTING
 INFORMATION ON PLAN. THERE IS A STATEMENT ON PLAN THAT
 "SAUNA DOES NOT REQUIRE POWER, CONTROLS ARE BATTERY
 POWERED". HOWEVER, THE PANEL SCHEDULE SHOWS A 30 AMP
 CIRCUIT WITH A 5300 VA LOAD FOR THE SAUNA. PROVIDE
 PREVIOUSLY REQUESTED INFORMATION AND CORRECT PLAN.)
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. ELECTRICAL PLAN MUST BE SIGNED AND SEALED BY DESIGN
 PROFESSIONAL. FS 471, FAC61G15-23, FBC 107.3.5 (ONE SET
 OF PLANS STILL HAS THE OLD ELECTRICAL DRAWING. BOTH
 SETS NEED THE CORRECTED DRAWING, SIGNED AND SEALED.)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-14 Cont ID  
Sent By jpearson Date 2017-07-14 Time 14:53 Rev Time 0.00
Received By jpearson Date 2017-07-14 Time 14:53 Sent To  
Notes
2017-07-14 15:09:27CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. BASED ON THE LOAD CALCULATION PROVIDED, THE EXISTING
 SRVICE IS TOO SMALL TO ACCOMODATE THE LOAD. PROVIDE
 CORRECTION. NEC 215.2, 220, FBC RE3602.1
 2. 2/0 WIRE FROM MBP TO MLC IS TOO SMALL. THIS WIRE
 SIZE CAN ONLY BE USED WHEN IT SERVES 100% OF THE LOAD.
 PROVIDE CORRECTION. NEC 310.15(B)(7); FBC RE3602.2
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 4. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 5. PROVIDE PANEL SCHEDULE/SIZING FOR ALL PANELS.
 INDICATE ANY NEW OR ALTERED CIRCUITS, AFCI OR GFCI
 PROTECTION AS REQUIRED. NEC 215.5, 408.4, 408.30 FBC
 RE3706.1
 6. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION PER CODE.
 SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE EXISTING
 OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC R314.3
 7. #6 ROMEX WIRE, WHICH IS TYPICAL IN RESIDENTIAL
 WIRING, IS NOT RATED FOR 60 AMPS. PROVIDE CORRECTION
 FOR AC/HVAC. NEC 334.80; FBC RE3705.4.4
 8. PROVIDE DETAILS OF SAUNA. DOES THIS REQUIRE GFCI
 PROTECTION? NEC 110.3; FBC 107.2.1
 9. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS. PROVIDE CORRECTION. NEC
 410.16(B), FBC RE4003.12
 10. LIGHTING IN PORCH AREAS SHALL BE SUITABLE FOR DAMP
 LOCATIONS. PROVIDE COMPLIANCE. NEC 410.10; FBC RE4003.9
 11. THE CURRENT CODE BEING USED IS THE 2011 NEC, PLEASE
 CORRECT NOTES. FBC PREFACE, 107.2.1
 12. ELECTRICAL PLAN MUST BE SIGNED AND SEALED BY DESIGN
 PROFESSIONAL. FS 471, FAC61G15-23, FBC 107.3.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2017-07-17 Cont ID  
Sent By gjohnson Date 2017-07-17 Time 09:46 Rev Time 0.00
Received By gjohnson Date 2017-07-17 Time 09:46 Sent To  
Notes
2017-07-17 09:46:46GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-03-15 Time   Rev Time 0.00
Received By lmarchan Date 2018-02-16 Time 15:29 Sent To  
Notes
2018-02-20 15:29:40R36

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-30 Cont ID  
Sent By cpuell Date 2017-10-30 Time 09:36 Rev Time 0.00
Received By cpuell Date 2017-09-28 Time 12:52 Sent To  
Notes
2017-09-29 12:52:14R23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-24 Cont ID  
Sent By jgomez Date 2017-07-24 Time 17:38 Rev Time 0.00
Received By jgomez Date 2017-06-26 Time 14:10 Sent To  
Notes
2017-06-27 14:10:38R23

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-10-05 Cont ID  
Sent By jgomez Date 2017-10-05 Time 09:17 Rev Time 0.00
Received By jgomez Date 2017-10-05 Time 09:14 Sent To  
Notes
2017-10-05 09:18:46$236.59 PAID. MU-2017-026146.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-07-24 Cont ID  
Sent By jgomez Date 2017-07-24 Time 09:11 Rev Time 0.00
Received By jgomez Date 2017-07-24 Time 07:37 Sent To  
Notes
2017-07-24 09:11:19 
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. BRING
 BACK COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF
 FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-03-15 Cont ID  
Sent By jgomez Date 2018-03-15 Time 11:01 Rev Time 0.00
Received By jgomez Date 2018-03-15 Time 11:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-12 Cont ID  
Sent By jgomez Date 2017-10-12 Time 13:31 Rev Time 0.00
Received By jgomez Date 2017-10-12 Time 13:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-07-24 Cont ID  
Sent By jgomez Date 2017-07-24 Time 17:38 Rev Time 0.00
Received By jgomez Date 2017-07-24 Time 12:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-03-15 Cont ID  
Sent By jgomez Date 2018-03-15 Time 10:35 Rev Time 0.00
Received By jgomez Date 2018-03-15 Time 10:34 Sent To  
Notes
2018-03-15 10:35:59TRAP PRIMER REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-12 Cont ID  
Sent By gjohnson Date 2017-10-12 Time 15:43 Rev Time 0.00
Received By gjohnson Date 2017-10-12 Time 15:11 Sent To  
Notes
2017-10-12 13:02:05NEW DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-07-17 Cont ID  
Sent By gjohnson Date 2017-07-17 Time 09:45 Rev Time 0.00
Received By gjohnson Date 2017-07-17 Time 08:59 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2018-03-15 Cont ID  
Sent By jgomez Date 2018-03-15 Time 10:20 Rev Time 0.00
Received By jgomez Date 2018-03-15 Time 10:20 Sent To  
Notes
2018-03-15 10:21:06APPROVED WITH PROVISO:
  
 1- REVISE FLAT ROOF RAS 117 CALCULATIONS SUBMITTED:
 (A) APPROVED SYSTEM DOESN'T MATCH SYSTEM SYSTEM
 SUBMITTED WITH NOA 14-0529.02.
 (B)RAS 117 CALCULATIONS NEED TO BE SIGNED AND SEALED BY
 THE ENGINEER. CHAPTER 471 F.S

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2017-10-12 Cont ID  
Sent By jgomez Date 2017-10-12 Time 13:00 Rev Time 0.00
Received By jgomez Date 2017-10-12 Time 13:00 Sent To  
Notes
2017-10-12 13:01:041- FLAT ROOF NOA 14-0529.02 SUBMITTED: THE DESIGN
 PRESSURE OF SELECTED ASSEMBLY ON PAGE 26 OF 42 DOESN'T
 MEET THE DESIGN PRESSURE FOR ALL ROOF ZONES. PROVIDE
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT THE PERIMETER AND CORNER AREAS AS REQUIRED
 BY GENERAL LIMITATION #7 ON LAST PAGE OF THE NOA. NEED
 THE CALCULATIONS TO MEET THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL.
 REPEAT COMMENT.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-07-24 Cont ID  
Sent By jgomez Date 2017-07-24 Time 16:03 Rev Time 0.00
Received By jgomez Date 2017-07-24 Time 16:03 Sent To  
Notes
2017-07-24 16:04:271- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) FLAT ROOF. AND CLEARLY IDENTIFY WHICH APPROVED
 ASSEMBLY IS GOING TO BE INSTALLED. NOTE: IF THE DESIGN
 PRESSURES OF THE SELECTED ASSEMBLY DON'T MEET THE
 DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND
 SEALED RAS 117 CALCULATIONS WILL BE REQUIRED.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVAL
 (INCLUDING THE ONES THAT WERE ALREADY SUBMITTED) AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.

Review Stop Z ZONING
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2018-03-21 Time   Rev Time 0.00
Received By   Date 2018-03-21 Time   Sent To  
Notes
2018-03-21 10:57:13**************************ZONING
 PROVISO******************************
  
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE FOLLOWING CONDITIONS SHALL BE ADDRESSED:
  
 1. A LANDSCAPE PERMIT, WHCH INCLUDES A LANDSCAPE PLAN,
 SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW.
  
 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2018-03-01 Cont ID  
Sent By awooten Date 2018-03-01 Time 15:54 Rev Time 0.00
Received By awooten Date 2018-03-01 Time 15:54 Sent To  
Notes
2018-03-01 15:59:43******ZONING REVIEW FAILED****************
  
  
 THE INTERNAL HALLWAY THAT WAS ADDED ADDRESSES THE
 INTERNAL CONNECTIVITY ISSUE.
  
 THE VALUE OF THE PROJECT ($200,000) EXCEEDS 50% OF THE
 VALUE OF THE PROPERTY, TRIGGERING THE LANDSCAPE CODE.
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PLAN WITH TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 GENERAL LANDSCAPING STANDARDS FOR SINGLE-FAMILY
 DWELLING UNITS SHALL BE AS FOLLOWS:
  
 A. SINGLE-FAMILY DWELLING UNITS. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
  
  
 PLEASE ADDRESS COMMENTS IN WRITTEN FORM ATTACHED TO
 PLAN.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2017-10-24 Time   Rev Time 0.00
Received By   Date 2017-10-24 Time   Sent To  
Notes
2017-10-24 15:17:49 
 ******ZONING REVIEW FAILED****************
  
 THIS PROPERTY IS ZONED SF-7 AND IS SINGLE FAMILY.
  
 THERE IS NO INTERNAL CONNECTIVITY BETWEEN THE PRINCIPAL
 HOUSE AND THE 2 STORY ADDITION, OR THE GARAGE AND THE 2
 STORY ADDITION AND WITHOUT INTERNAL CONNECTIVITY, THIS
 IS AN ACCESSORY STRUCTURE.
  
 A SMALL UNDER COUNTER FRIDGE AND A SINK WITHOUT A STOVE
 ARE THE ONLY THINGS PERMITTED IN THE TWO STORY
 STRUCTURE.
  
 ACCESSORY BUILDINGS ARE ONLY ALLOWED TO BE A MAXIMUM OF
 1000 SQ/FT.
  
 PLEASE ADDRESS COMMENTS IN WRITTEN FORM ATTACHED TO
 PLAN.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2017-06-30 Time   Rev Time  
Received By   Date 2017-06-30 Time   Sent To  
Notes
2017-06-30 16:17:41******ZONING REVIEW FAILED****************
  
 DRIVEWAY MUST BE SUBMITTED UNDER A SEPARATE PERMIT.
  
 WHAT IS THE TWO STORY PROPOSED ADDITION GOING TO BE
 USED FOR?
  
 THIS PROPERTY IS ZONED SF-7 AND IS SINGLE FAMILY.
  
 ONLY ONE UNIT PER LOT/ACRE IS PERMITTED IN THIS
 DISTRICT.
  
 THE ACCESSORY BUILDING WITH A FULL KITCHEN IS
 CONSIDERED AN ADDITIONAL UNIT.
 THERE IS AN OVEN RANGE SHOWN ON THE ELECTRICAL PLANS
 FOR THE TWO STORY ACCESSORY BUILDING.
 THIS ACCESSORY STRUCTURE CANNOT HAVE A FULL KITCHEN.
 A SMALL UNDER COUNTER FRIDGE AND A SINK WITHOUT A STOVE
 ARE THE ONLY THINGS PERMITTED IN THE TWO STORY
 STRUCTURE.
 ACCESSORY BUILDINGS ARE ONLY ALLOWED TO BE A MAXIMUM OF
 1000 SQ/FT.
  
 ADDITIONAL COMMENTS MAY FOLLOW.
  
 PLEASE ADDRESS COMMENTS IN WRITTEN FORM ATTACHED TO
 PLAN.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]
  