Plan Review Details - Permit 17061006
Plan Review Stops For Permit 17061006
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-07-21 Cont ID  
Sent By wjolin Date 2017-07-21 Time 13:06 Rev Time 0.00
Received By wjolin Date 2017-07-21 Time 13:05 Sent To M
Notes
2017-07-21 13:06:44NOTE: DRAWINGS DO NOT CONTAIN A REVIEWED STAMP FROM THE
 ENGINEER OF RECORD.
  
 FBC 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE:
 DEFERRED SUBMITTALS.
 THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE
 CHARGE SHALL REVIEW THE DEFERRED SUBMITTAL WITH A
 NOTATION INDICATING THAT THE SUBMITTED DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE CONSTRUCTION DOCUMENTS.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-23 Cont ID  
Sent By wjolin Date 2017-06-23 Time 14:36 Rev Time 0.00
Received By wjolin Date 2017-06-23 Time 14:00 Sent To M
Notes
2017-06-23 14:36:371901 SOUTH FLAGLER DRIVE
 PERMIT #17061006
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 A SEPARATE PERMIT IS NEEDED FOR THE BACKFLOW PREVENTER.
  
 PLANS INDICATE OUTDATED FLOW TEST DATA FOR 720 8TH
 STREET.
  
 RISER DETAIL INDICATES 1-1/4" CHECK AND CONTROL VALVES
 ON A 4-INCH RISER.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 NO PRODUCT CUT SHEETS SUBMITTED FOR SPRINKLER SYSTEM
 COMPONENTS OR UNDERGROUND PIPING.
  
 INDICATE HOW THE UNDERGROUND PIPING WILL BE RESTRAINED
 FROM MOVEMENT. IF UTILIZING JOINT RESTRAINTS, SUBMIT
 PRODUCT DATA INDICATING REQUIRED TORQUE.
  
 INADEQUATE SPRINKLER PROTECTION PROVIDED AT THE TOP OF
 THE TWO INTERNAL STAIRS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-07-26 Time   Rev Time 0.00
Received By cpuell Date 2017-07-13 Time 16:31 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-06-29 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-22 Time 11:44 Sent To  
Notes
2017-06-23 11:44:59ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-07-26 Cont ID  
Sent By ccole Date 2017-07-26 Time 11:44 Rev Time 0.00
Received By ccole Date 2017-07-26 Time 11:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-29 Cont ID  
Sent By ccole Date 2017-06-29 Time 11:19 Rev Time 0.00
Received By ccole Date 2017-06-29 Time 11:19 Sent To  
Notes
2017-06-29 11:26:031ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17061006
 6/29/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMPLY WITH FIRE REVIEW COMMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  