Plan Review Details - Permit 17060978
Plan Review Stops For Permit 17060978
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-07-05 Cont ID  
Sent By rmcdouga Date 2017-07-05 Time 15:24 Rev Time 0.00
Received By rmcdouga Date 2017-07-05 Time 15:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-07-05 Cont ID  
Sent By rmcdouga Date 2017-07-05 Time 13:52 Rev Time 0.00
Received By rmcdouga Date 2017-07-05 Time 12:33 Sent To  
Notes
2017-07-05 13:52:10PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO COPIES OF A KEY PLAN THAT TIES TO THE
 WINDOW SCHEDULE AND SHOWS THE WINDOW LOCATIONS. FBC
 107.2.1
  
 2) IN ORDER TO VERIFY THAT THE EMERGENCY EGRESS
 REQUIREMENTS FOR THE SLEEPING ROOMS WILL NOT BE MADE
 LESS COMPLIANT, LABEL THE BEDROOMS AND ANY ROOMS THAT
 ARE USED FOR SLEEPING ON THE KEY PLAN AND SPECIFY THE
 SIZE AND TYPE OF THE EXISTING EGRESS WINDOW. FBC
 EXISTING BUILDING SECTION 704.
  
 3) THE PRODUCT APPROVAL PRESSURES THAT ARE LISTED IN
 THE WINDOW SCHEDULE ARE THE MAXIMUM PRESSURES FOR THE
 PRODUCT AND NOT NECESSARILY THE PRESSURES FOR THE
 WINDOW YOU WILL BE INSTALLING. THE PRESSURES CHANGE
 BASED ON WINDOW SIZE, GLASS TYPE, REINFORCING, ETC.
 THIS MAY CAUSE CONFUSION. REVISE THE SCHEDULE TO SHOW
 THE PRODUCT APPROVAL PRESSURES THAT ARE SPECIFIC TO THE
 WINDOW THAT WILL BE INSTALLED. FBC 107.2.1
  
 4) THE SCHEDULE INDICATES THAT THREE WINDOWS HAVE
 STRUCTURAL MULLIONS. IT IS NOT CLEAR FROM THE SCHEDULE
 HOW THE WINDOWS ARE MULLED TOGETHER. THE ROUGH OPENING
 DIMENSION IS LISTED AS 36" X 50". DOES THIS MEAN THAT
 TWO 36" X 50" WINDOWS ARE MULLED TOGETHER SIDE BY SIDE
 OR TWO 18" X 50" WINDOWS ARE JOINED TOGETHER TO FIT IN
 A 36" X 50" ROUGH OPENING? PROVIDE ADDITIONAL
 INFORMATION TO DETERMINE THE SIZES OF THE WINDOWS AND
 THERE ARRANGEMENT (SIDE BY SIDE, ONE ABOVE THE OTHER,
 ETC.) FBC 107.2.1
  
 5) PROVIDE A COPY OF THE SIGNED CONTRACT TO VERIFY THE
 VALUATION FOR THE WORK. THE VALUE OF $7500.00 APPEARS
 LOW FOR REPLACING TWENTY WINDOWS WITH IMPACT RATED
 WINDOWS IN A TWO STORY HOUSE. THAT IS ONLY $375.00 PER
 WINDOW. FBC 109.3
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-05 Cont ID  
Sent By rmcdouga Date 2017-07-05 Time 15:24 Rev Time 0.00
Received By rmcdouga Date 2017-07-05 Time 15:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-05 Cont ID  
Sent By rmcdouga Date 2017-07-05 Time 13:52 Rev Time 0.00
Received By rmcdouga Date 2017-06-21 Time 11:35 Sent To  
Notes
2017-06-22 11:35:39BLDG MISC 1